Barnes 3SCM Installation And Operation Manual Download Page 16

16

TROUBLE SHOOTING

CAUTION !

 Always disconnect the pump from the electrical power source before handling.

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.

If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER

.

NOTE:

 Not all problems and corrections will apply to each pump model.

PROBLEM

CAUSE

CORRECTION

Pump will not run

1.

 Poor electrical connection, blown fuse, 

tripped breaker or other interruption of power, 

improper power supply.

2.

 Motor or switch inoperative (to isolate 

cause, go to manual operation of pump).

2a.

 Float movement restricted.

2b.

 Switch will not activate pump or is defective.

2c.

 Defective motor

3.

 Insufficient liquid level.

1. Check all electrical connections for 

security. Have electrician measure current 

in motor leads, if current is within ±20% 

of locked rotor Amps, impeller is probably 

locked. If current is 0, overload may be 

tripped. Remove power, allow pump to cool, 

then recheck current.

2a. Reposition pump or clean basin as 

required to provide adequate clearance for 

float.

2b. Disconnect level control. Set ohmmeter 

for a low range, such as 100 ohms full scale 

and connect to level control leads. Actuate 

level control manually and check to see that 

ohmmeter shows zero ohms for closed switch 

and full scale for open switch. (Float Switch).

2c. Check winding insulation (Megger Test) 

and winding resistance. If check is outside 

of range, dry and recheck. If still defective, 

replace per service instructions.

3. Make sure liquid level is at least equal to 

suggested turn-on point.

4. Recheck all sizing calculations to 

determine proper pump size.

5. Check discharge line for restrictions, 

including ice if line passes through or into 

cold areas.

6. Remove and examine check valve for 

proper installation and freedom of operation.

7. Open valve.

8. Check impeller for freedom of operation, 

security and condition. Clean impeller and 

inlet of any obstruction.

9. Loosen union slightly to allow trapped air 

to escape.Verify that turn-off level of switch 

is set so that the suction is always flooded. 

Clean vent hole.

10. Check rotation. If power supply is three 

phase, reverse any two of three power supply 

leads to ensure proper impeller rotation..

11. Repair fixtures as required to eliminate 

leakage.

12. Check pump temperature limits & fluid 

temperature.

13. Replace portion of discharge pipe with 

flexible connector.

14. Turn to automatic position.

15. Check for leaks around basin inlet and 

outlets.

Pump will not turn off

2a. Float movement restricted.

2b. Switch will not activate pump or is defective.

4. Excessive inflow or pump not properly sized 

for application.

9. Pump may be airlocked

14. H-O-A switch on panel is in “HAND” position

Pump hums but does not run

1. Incorrect voltage

8. Impeller jammed or loose on shaft, worn or 

damaged, impeller cavity or inlet plugged.

Pump delivers insufficient capacity

1. Incorrect voltage.

4. Excessive inflow or pump not properly sized 

for application.

5. Discharge restricted.

6. Check valve stuck closed or installed backwards.

7. Shut-off valve closed.

8. Impeller jammed or loose on shaft, worn or 

damaged, impeller cavity or inlet plugged.

9. Pump may be airlocked.

10. Pump running backwards

Pump cycles too frequently or runs 

periodically when fixtures are not in 

use

6. Check valve stuck closed or installed 

backwards.

11. Fixtures are leaking.

15. Ground water entering basin.

Pump shuts off and turns on indepen-

dent of switch, (trips thermal overload 

protector). 

CAUTION!

  Pump may 

start unexpectedly. Disconnect power 

supply.

1. Incorrect voltage.

4. Excessive inflow or pump not properly sized 

for application.

8. Impeller jammed, loose on shaft, worn or 

damaged, impeller cavity or inlet plugged.

12. Excessive water temperature. 

(internal protection only)

Pump operates noisily or vibrates 

excessively

2c. Worn bearings, motor shaft bent.

5. Debris in impeller cavity or broken impeller

10. Pump running backwards

13. Piping attachments to buiding structure too 

rigid or too loose.

Summary of Contents for 3SCM

Page 1: ...56 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 133030S Rev H 3SCM Monovane Pumps 3 7 5HP 1750RPM 4SCM Monovane Pumps 3 10H...

Page 2: ...SHOOTING 16 SC CROSS SECTIONS Fig 9 EXPLODED VIEWS Fig 10 17 18 PARTS LISTS AND KITS 19 31 WARRANTY 33 RETURNED GOODS POLICY 34 WARRANTY REGISTRATION 34 START UP REPORT 35 36 Other brand and product...

Page 3: ...sert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety d...

Page 4: ...r Crane Pumps Systems Canada in Brampton Ontario 905 457 6223 SECTION B INSTALLATION B 1 Location These self contained pumping units are recommended for use in a sump lift station or basin This pump i...

Page 5: ...s into the clamping plate Slowly tighten the two screws alternating back and forth until the clamping plate is drawn down flush to the top of the cord boss on the pump The two screws should be torqued...

Page 6: ...8 6 46 2 125497 2 88 3SCMPA5054 5 0 575 3 60 1750 J 6 0 6 9 37 0 125497 12 4 18 4 86 02 4 32 3SCMPA75N4 7 5 208 3 60 1750 H 23 8 28 5 105 9 123 6 125496 12 4 18 4 86 02 0 43 230 23 7 27 2 0 43 460 11...

Page 7: ...MC Pump 4SCMC50N4 5 0 208 3 60 1750 J 15 8 18 7 82 4 92 4 125496 12 4 18 4 86 02 0 72 230 15 0 17 2 125496 12 4 18 4 86 02 0 72 460 7 5 8 6 46 2 125497 12 4 18 4 86 02 2 88 4SCMC5054 5 0 575 3 60 1750...

Page 8: ...4SCDG50N4 5 0 208 3 60 1750 J 15 8 18 7 82 4 92 4 125496 12 4 18 4 86 02 0 72 230 15 0 17 2 125496 12 4 18 4 86 02 0 72 460 7 5 8 6 46 2 125497 12 4 18 4 86 02 2 88 4SCDG5054 5 0 575 3 60 1750 J 6 0 6...

Page 9: ...r MOISTURE AND TEMPERATURE SENSORS MOISTURE AND TEMPERATURE SENSORS Power Cable Power Cable Lead ID Lead ID Brown P1 Temperature Sensor Yellow P2 Temperature Sensor Orange W1 Moisture Sensor Blue W2 M...

Page 10: ...IRCUIT Single Phase Cap Chart HP RPM Cap Kit Start Relay Start Cap Run Cap 5 1750 133042 Mars 64 440MFD 330V 50MFD 370V 5 3450 141361 Mars 64 297MFD 330V 40MFD 440V 3 1750 2 1750 Single Phase Start Co...

Page 11: ...0 220 240 2 00 18 0 B 4 4 Moisture Sensors A normally open N O detector is installed in the pump seal chamber which will detect any moisture present and a continuity test resistor built into the motor...

Page 12: ...for a three phase installation interchange any two power cable leads at the control box Recheck the kickback rotation again by momentarily applying power C 2 2 Test Procedure For Moisture Sensor Cont...

Page 13: ...k is done to the pump CAUTION Operating pump builds up heat and pressure allow time for pump to cool to room temperature before handling or servicing E 1 Lubrication E 1 1 Checking Oil 1 Place pump on...

Page 14: ...or shaft then retaining ring 5 spring 4C and rotating member 4B from shaft See Figure 6 Examine all seal parts and especially contact faces Inspect seal for signs of wear such as uneven wear pattern o...

Page 15: ...3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and...

Page 16: ...ller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so t...

Page 17: ...17 SC Pump Series Cross Section 4 5 9 3 2 7 11 8 6 10 8A OIL FILL FIGURE 9...

Page 18: ...18 FIGURE 10 SC Pump Series Exploded View 35 ITEMS NOT SHOWN 12 31 32...

Page 19: ...al Mechanical Type 21 1 5 C CE B 4B 1 133029SD Seal Mechanical Type 21 1 5 SC SC B 5 2 133048 Ring Retaining EXT 5100 420 SS 6 1 See Table Impeller Ductile Iron 6A 1 See Table Slicer Blade Stainless 4...

Page 20: ...en 6 Bar O Ring 8G 38 1 039462 Tie Cable 39 2 125855 Screw SHCS M5 x 0 8 x 8 Stainless Steel 40 2 134013 Connector Wire Clip 49 1 See Table Striker Plate 50 See Table Shims 51 8 143110 Screw SHCS M10...

Page 21: ...5499XC 30 400 600 59 0 8 4 18 4 1 12in 28 4mm 125499XF 50 400 600 59 0 8 4 18 4 1 12in 28 4mm 125499XJ 75 400 600 59 0 8 4 18 4 1 12in 28 4mm 125499XL 100 400 600 59 0 8 4 18 4 1 12in 28 4mm Volute Pi...

Page 22: ...KIT 142157 KIT 142633 4 KIT 142137 142174 259 4SCDF 4 INCH 4SCDG 5 INCH 129994SK 5 ASSY KIT 141601 ASSY KIT 141579 KIT 142633 5 KIT 141601 142174 260 141579 002 RED 141579 004 TAN 141579 010 BROWN 141...

Page 23: ...s Striker Plate Kit Volute Kit Striker Hardware Kit includes M10 Bolts qty 8 O ring Plate Spacing Kit includes Level 4 Cut Proof Gloves Spacer Gage Shim Stock Kit includes 0 002 Shims 12 0 004 Shims 1...

Page 24: ...6 10in 133052TG ASSY KIT 143277TG ASSY KIT 133052TG C 143277TG C 142136 142133 1000 150mm 5 91in 133052TH ASSY KIT 143277TH ASSY KIT 133052TH C 143277TH C 142136 142133 1000 145mm 5 71in 133052TJ ASS...

Page 25: ...F C 142126 142133 0750 170mm 6 69in 133044TG ASSY KIT 143288TG ASSY KIT 137223TG C 143288TG C 142126 142133 0750 S Impeller Trim Dia mm in Ductile Iron Slicer Blade Kit Nihard Slicer Blade Kit Kit Com...

Page 26: ...Jumper Wire Connector Clip 24 Orange Wire Jumper Seal Kit includes Lower Volute O Ring option 1 Lower Volute O Ring option 2 Lower Volute O Ring option 3 Seal Plate upper O ring and Stator Lower O ri...

Page 27: ...Seal Kit Bearing Kit Bearing Bracket Kit Hardware Kit Seal Plate Kit Terminal Block Kit Overhaul Kit Purchase Seal Kit and Hardware Kit Leg Kit includes 3 Legs painted attachement hardware Leg Kits Mo...

Page 28: ...r Shaft Snap Ring Rotor Stator Motor Housing Kit includes Motor Housing painted Pipe Plug Set Cap Screw Stator Self clinching Tie Cable Cap Plug 1750 RPM Model No Motor Kit Part No SH 30N4 145663 SH 5...

Page 29: ...127SK ASSY KIT 142633 4 KIT 3SCMPA50N4 See Motor Kit Table 138579 143127SK KIT 138583 138610 138593 138615 138613 138614 S 125506 137223TB ASSY KIT 142157 KIT 142125 AS SY KIT 143127SK ASSY KIT 142633...

Page 30: ...133044 AS SY KIT 142157 KIT 142137 AS SY KIT 133033SK ASSY KIT 142633 4 KIT 4SCMS7554 133961 133962 138579 133033SK KIT 138584 138610 138593 138615 138613 138614 S 125506 133044 AS SY KIT 142157 KIT 1...

Page 31: ...133052 AS SY KIT 142157 KIT 142137 AS SY KIT 133033SK ASSY KIT 142633 4 KIT 4SCDF7554 133961 133962 138579 133033SK KIT 138584 138610 138593 138615 138613 138614 S 125506 133052 AS SY KIT 142157 KIT 1...

Page 32: ...Notes...

Page 33: ...upport any Warranty claims This Warranty shall not apply to any product or part of product which has been subject to misuses negligence accident operation outside of our published hydraulic curve para...

Page 34: ...Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration...

Page 35: ..._ Type _________________________________ Number and size of short circuit device s ___________ Amp rating ___________________ Overload Type _____________ Size ______________ Amp rating _______________...

Page 36: ...ls installed away from turbulence YES___ NO___ Is level control operating properly YES___ NO___ Is pump fully submerged during operation YES___ NO___ Follow up Corrective Action Required YES___ NO___...

Reviews: