PRODUCT MANUAL - BARIX X8 - V01.05 - 10/26/2006
Configuration
The BARIX X8 is configured via the RS-485 interface using
standard Modbus commands.
If the address of the device is not known, it can be reset to default
parameters by the following method:
•
disconnect the device from power supply
•
install a wire between pin 8 and pin 9 on J1
•
reapply power to the device
The BARIX X8 will lite up all 4 LEDs and the 3
rd
LED will blink
showing that the default parameters are stored in the non volatile
memory. No communication is possible at this moment.
•
disconnect the device from power supply
•
remove the wire between pin 8 and pin 9 on J1
•
reapply power to the device
Now the device can be addressed on Modbus address 255 using
the following serial settings: 19200 Baud, even parity, 1 stop bit
Configuration · 11
Default Parameters
LED
LED
| 1 | 2 | 3 | 4 |
| 1 | 2 | 3 | 4 |