PRODUCT MANUAL - BARIX R6 - V01.03 - 07/20/2005
Technical specifications
PIC 16F688, 20MHz clock frequency
6 independent relays (250VAC 10
A, 16Amax <1sec)
Operate time: 7ms nominal, release time: 3ms nominal.
Contact resistance: 50mOhm (measured at 1A 6V)
Operating cycles: 10mio typical at no load.
Relay type: Massuse ME-11 or equivalent
3 screw terminal blocks non-removable, with common,
NO (normally open) and NC (normally closed) contacts
for wires AWG26 - AWG14 / 0.15 – 2.5mm
2
Detachable screw terminal block
for wires AWG28 - AWG16 / 0.08 - 1.3 mm
2
RS-485: 9600 and 19200 Baud, 8 bit, even or no parity.
2 extension connectors (4 pin) with RS-485 and power terminals,
Molex 22-27-2041, 4A max., extension cable (3”/75mm) included
(consisting of 2 Crimp Terminal Housings Molex 22-01-2045 and
8 female Crimp Terminals Molex 08-50-0114 of Molex 2759 series)
12 to 24 VAC / 9 to 30 VDC
3.5 Watt max. (all relays active)
1 LED for power indication
1 LED for active traffic indication
6 LEDs for relay status indication
High quality plastic, 220 grams, DIN-rail mountable
"
"
"
4.13 x 3.34 x 2.83 /105mm x 85mm x 32mm
Internal connector for default settings jumper
Temperature:32 to 104° F / 0 to 40° C
Humidity: < 70% relative humidity non-condensing
FCC A and B, CE A and B
Emission EN60730-1:2000 (Class B)
Immunity EN60730-1.2000
Technical specifications • 15
CPU
RS-485 / Power
Connector
Power Supply
Requirements
LED Indicators
Case
Misc.
Environmental
conditions
Relays
Extension
Connectors
Load Connectors
Host Interface
Conformity
Summary of Contents for R6