TECHNICAL PRODUCT INFORMATION
Barel reserves the right to change technical specifications without further notice
8
Technical datasheet HFX and HFXE_LED_26
5
What to do if…
Do not energize circuit before all components and lamps are connected properly.
In case of no function or malfunction: first de-energize the circuit. Disconnect mains and
battery supply before lamps are disconnected.
- No light in LED lamp when connected to mains supply-
- Make sure all components are the correct type and suitable for lamp/driver type,
mains supply voltage and frequency range
- Make sure all connections are correct.
- Allow a reset of mains supply.
- Some internal protection circuits require a reset of mains supply before resuming operation
after a fault is detected.
- Contact Barel if no fault was found and the reset does not restart the unit.
- Do not attempt to open or repair these units. Both HFX/E and ARC should be replaced in
case of failure – to avoid premature failure of the other component.
- HFXE only, No light in emergency mode:
- Reconnect mains supply
- Check the indicator LED status-
- If green; There is a fault in the HFXE. De-energize the unit. Disconnect
battery before lamp. Contact Barel.
- If red or no light in indicator;
- Allow the battery to charge 24h
- Retest emergency mode.
If problems with conducted emission during EMC measurements, contact Barel for assistance.
Important issues are:
-
Keep all wires short.
-
Separate lamp wires from mains supply wires
-
Ground the LED-driver through a short wire connection, and if
possible separate from mains cabling internally in luminaire.