Technical datasheet HFX and HFXE T8_10 

No light 

No function 

Connect to mains supply voltage within specified limits. 

4.5  Cable 

 

 

Cross sectional area of the cable can be between  1 – 2,5 mm2  (solid or multi wire). 
Terminal torque: 0,5NM.  
 

 

Wire insulation voltage should be minimum  660V.  
For Aluminium cables; a bi metallic connector should be used to provide a copper connection. 

 

What to do if…

 

 

• 

No light when first connected to the mains: 

 

-  Check that the mains voltage is in the voltage range of the ballast. 

 

-  Check that the screws at the connection terminal are tightened. 

 

-  Check that correct lightsources are connected and that these are ok.  

• The lamp(s) lights up, but stop immediately after.  

- Change the tubes with new ones. The ballast has a built-in lamp EOL protection, and will stop operation if the lamp has reached its EOL. 
- Check the wires, the contacts and the switches in both sides of the luminaire.  
- Check that the correct lamp type is used. Barel recommend using only high quality fluorescent lamps.  

If problems with conducted emission during EMC measurements, contact Barel for assistance.  
Important issues are:   

-

 

Keep all wires short. 

-

 

Separate lamp wires from mains supply wires 

-

 

Ground the ballast through a short wire connection 

Summary of Contents for HFX 18

Page 1: ...INED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX ENVIRONMENT Author Barel AS Rev 10 Date 03 11 2014 Barel AS 9917 Kirkenes Norway www barel no CONTENTS 1 APPLICATIONS 2 2 APPROVALS 2 3 TECHNICAL...

Page 2: ...table for use in explosive gas athmospheres like Oil Industry Off On shore Installations Gas Stations Fuel Reservoirs Oil Tankers Mining Industry Mines Plants Mills Chemical Industry Production Plants...

Page 3: ...l reserves the right to change technical specifications without further notice 3 Technical datasheet HFX and HFXE T8_10 3 Technical data 3 1 Product range Power factor measured 230V 50Hz Ik max 1500A...

Page 4: ...ATION Barel reserves the right to change technical specifications without further notice 4 Technical datasheet HFX and HFXE T8_10 3 2 Mechanical data Aluminum housing fastened with 2 screws in the pla...

Page 5: ...95 C Operating temperature of the plastic material in the terminals is 30 C to 105 C Charging current 220mA 80mA permanent With one fault condition of the charging system the charging power is limite...

Page 6: ...or to a separate ground connection The aluminium chassis is internally connected to the gnd pin DC input Connect to N and to L L1 L4 HFXE Connect L1 via switch to allow battery charging while light i...

Page 7: ...hours Status of the test must be observed manually Self test By using a Bipolar LED connected to the 2 of the 3 pins 5 6 or 7 as shown above then a self test will be performed This test will automatic...

Page 8: ...oltage is in the voltage range of the ballast Check that the screws at the connection terminal are tightened Check that correct lightsources are connected and that these are ok The lamp s lights up bu...

Reviews: