Technical datasheet HFX and HFXE T8_10 

 

4.4  Operation HFXE 

 

Setting of 1.5h and 3h operation is selected by connection of Charging Indicator (LED) to terminals 5, 6 and 7 as described in table below. 
For manual operation (no selftest) a single colour LED is used,   
For a Selftest operation a bidirectional LED is used (RED / GREEN) connected such that OK = GREEN. For connection of the bicoulor LED the green 
coloured LED is refered to as Anode and Cathode 

 

TEST :  

 
NOTE :  A full test should not be activated when the battery is empty or low capacity - this could result in a wrong error-message. 
A test is activated manually, as a selftest or by connection of a test-switch. 
 

Manual test:  

 

By disconnecting the mains when the battery has been charged for a minimum of 24 hours. 

 

Status of the test must be observed manually. 

 

Self test:

 

 

By using a Bipolar LED connected to the 2 of the 3 pins 5, 6 or 7 as shown above, then a self 
test will be performed. This test will automatically run a short Monthly test and one  Full Annual test operating the Emergency Lamp (LAMP 1) from the battery.  

 

The test sequence will follow the requirement given in the standard IEC62034 2006-05   

  

“Automatic test systems for battery powered emergency escape lighting”. 

 

Indicator LED 

System status 

Action 

Continuous green 

System ok 

Battery charging ok and no faults apparent. 

Continuous blinking red 

Battery capacity problem 

24 h charge periode after last discharge not completed, or faulty battery. Restest 
system after 24h charging period, or replace battery 

Intermittent blinking red 

Faulty lamp 

Faulty or missing lamp. Replace lamp. Lower lamp power in emergency mode may 
cause lamp-fault detection on functioning lamp. Fluorescent lamps are sensitive to 
lower ambient temperatures. 

Continuous red 

Charging error 

Battery defective or missing. Connect or replace battery. 

    

 

     

 

Summary of Contents for HFX 18

Page 1: ...INED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX ENVIRONMENT Author Barel AS Rev 10 Date 03 11 2014 Barel AS 9917 Kirkenes Norway www barel no CONTENTS 1 APPLICATIONS 2 2 APPROVALS 2 3 TECHNICAL...

Page 2: ...table for use in explosive gas athmospheres like Oil Industry Off On shore Installations Gas Stations Fuel Reservoirs Oil Tankers Mining Industry Mines Plants Mills Chemical Industry Production Plants...

Page 3: ...l reserves the right to change technical specifications without further notice 3 Technical datasheet HFX and HFXE T8_10 3 Technical data 3 1 Product range Power factor measured 230V 50Hz Ik max 1500A...

Page 4: ...ATION Barel reserves the right to change technical specifications without further notice 4 Technical datasheet HFX and HFXE T8_10 3 2 Mechanical data Aluminum housing fastened with 2 screws in the pla...

Page 5: ...95 C Operating temperature of the plastic material in the terminals is 30 C to 105 C Charging current 220mA 80mA permanent With one fault condition of the charging system the charging power is limite...

Page 6: ...or to a separate ground connection The aluminium chassis is internally connected to the gnd pin DC input Connect to N and to L L1 L4 HFXE Connect L1 via switch to allow battery charging while light i...

Page 7: ...hours Status of the test must be observed manually Self test By using a Bipolar LED connected to the 2 of the 3 pins 5 6 or 7 as shown above then a self test will be performed This test will automatic...

Page 8: ...oltage is in the voltage range of the ballast Check that the screws at the connection terminal are tightened Check that correct lightsources are connected and that these are ok The lamp s lights up bu...

Reviews: