background image

Manual 2100-465A
Page

14 of 16

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit, the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will
go into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minutes (120 seconds) DOB = 132 second DOM
3.0 minutes (180 seconds) DOB = 138 second DOM
4.0 minutes (240 seconds) DOB = 144 second DOM
5.0 minutes (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

Summary of Contents for YL253

Page 1: ...Manual 2100 465A Page 1 of 16 Models YL253 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 465A Supersedes 2100 465 Date 07 25 06 Copyright 2005...

Page 2: ...Low Voltage Wiring Diagram 12 Figure 8 Fan Blade Setting 15 Start Up Important Installer Note 13 High Pressure Switch 13 Three Phase Scroll Compressor Start Up Information 13 Phase Monitor 13 Service...

Page 3: ...CA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washingto...

Page 4: ...I C E L G N I S l e d o M s t l o V d e t a R e s a h P d n a r e b m u N r e w o P d l e i F s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F...

Page 5: ...D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 5 2 L Y 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9...

Page 6: ...ype Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a variance with instructions installer should adhere to local codes SHIPPING DAMAGE Upon receipt of equipme...

Page 7: ...perly sized for the design airflow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditi...

Page 8: ...d See Figure 3 INSTALLATION INSTRUCTIONS 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the ri...

Page 9: ...ual 2100 465A Page 9 of 16 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIO...

Page 10: ...Manual 2100 465A Page 10 of 16 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 11: ...bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole...

Page 12: ...Manual 2100 465A Page 12 of 16 FIGURE 7 LOW VOLTAGE WIRING DIAGRAM...

Page 13: ...ion pressure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially redu...

Page 14: ...has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the w...

Page 15: ...delivery across the outdoor coil Any service work requiring removal or adjustment in the fan and or motor area will require that the dimensions below be checked and blade adjusted in or out on the mo...

Page 16: ...e d i S h g i H 2 7 2 1 2 3 7 4 2 2 5 7 9 3 2 6 7 4 5 2 8 7 9 6 2 9 7 7 8 2 9 7 5 0 3 1 8 4 2 3 2 8 4 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 7 7 1 2 8 7 0 3 2 0 8 5 4 2 1 8 0 6 2 3 8 6 7...

Reviews: