IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor
coil with a dishwater detergent.

HIGH PRESSURE SWITCH

The YL25 models are supplied with a remote reset high
pressure switch.  If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.  All three
phase units incorporate a phase monitor to ensure
proper field wiring.  See the 

Phase Monitor 

section in

this manual.

Verification of 

proper rotation

 must be made any time

a compressor is changed or rewired.  If improper
rotation is corrected at this time there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor's
internal protector will trip.

All three phase ZR3 compressors are wired identical
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulated values.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces airflow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On all 230 volt
units, there is a one-minute off delay on the blower
motor.  460 volt models do not have an off delay.

HEATING – Circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation.  On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

START-UP

Summary of Contents for YL253

Page 1: ...Manual 2100 465A Page 1 of 16 Models YL253 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 465A Supersedes 2100 465 Date 07 25 06 Copyright 2005...

Page 2: ...Low Voltage Wiring Diagram 12 Figure 8 Fan Blade Setting 15 Start Up Important Installer Note 13 High Pressure Switch 13 Three Phase Scroll Compressor Start Up Information 13 Phase Monitor 13 Service...

Page 3: ...CA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washingto...

Page 4: ...I C E L G N I S l e d o M s t l o V d e t a R e s a h P d n a r e b m u N r e w o P d l e i F s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F...

Page 5: ...D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 5 2 L Y 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9...

Page 6: ...ype Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a variance with instructions installer should adhere to local codes SHIPPING DAMAGE Upon receipt of equipme...

Page 7: ...perly sized for the design airflow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditi...

Page 8: ...d See Figure 3 INSTALLATION INSTRUCTIONS 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the ri...

Page 9: ...ual 2100 465A Page 9 of 16 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIO...

Page 10: ...Manual 2100 465A Page 10 of 16 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 11: ...bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole...

Page 12: ...Manual 2100 465A Page 12 of 16 FIGURE 7 LOW VOLTAGE WIRING DIAGRAM...

Page 13: ...ion pressure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially redu...

Page 14: ...has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the w...

Page 15: ...delivery across the outdoor coil Any service work requiring removal or adjustment in the fan and or motor area will require that the dimensions below be checked and blade adjusted in or out on the mo...

Page 16: ...e d i S h g i H 2 7 2 1 2 3 7 4 2 2 5 7 9 3 2 6 7 4 5 2 8 7 9 6 2 9 7 7 8 2 9 7 5 0 3 1 8 4 2 3 2 8 4 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 7 7 1 2 8 7 0 3 2 0 8 5 4 2 1 8 0 6 2 3 8 6 7...

Reviews: