background image

Manual    2100-349
Page    13

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation. On all 208/230 volt
models, when G circuit is de-energized the indoor
blower motor will continue to run for one minute.  On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation. On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the
models covered by this manual.  The compressor
control is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit  the delay on make period begins which will be
2 minutes plus 10% of the delay on break setting.
When the delay on make is complete and the high
pressure switch (and low pressure switch if employed) is
closed, the compressor contactor is energized.  Upon
shutdown the delay or break timer starts and prevents
restart until the delay on break and delay on make
periods have expired.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will go
into manual lockout condition and the alarm relay
circuit will energize.   Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

Summary of Contents for WL701

Page 1: ...AGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 349B Supersedes 2100 349A File Volume III Tab 16 Date 05 13 02 Copyright 2002 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned MIS 861 ...

Page 2: ...e 11 Maximum ESP of Operation Electric Heat Only 15 Table 12 Cooling Pressure 16 Table 13 Optional Accessories 16 Getting Other Information and Publications For more information contact these publishers 1 Wall Mount General Information Air Conditioner Wall Mount Model Nomenclature 2 Shipping Damage 4 General 4 Duct Work 4 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions Wa...

Page 3: ...lculation for ACCA Manual J or Residential Winter and Manual N Summer Air Conditioning Low Pressure Low Velocity Duct ACCA Manual D or System Design for Winter and Manual Q Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National St...

Page 4: ...Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest version Article 310 for power conductor sizing CAUTION When more than one filed power conductor circuit is run through one conduit the conductors must be derated Pay special attention to Note of Table 310 regarding Ampacity Adjustment Factors when more than 3 conductors a...

Page 5: ...8 0 1 0 0 7 0 3 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 0 5 1 5 2 6 0 0 2 1 5 1 4 5 0 0 4 8 3 2 6 3 0 0 2 1 5 2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 All dimensions in inches TABLE 2 DIMENSION OF BASIC UNIT FOR ARCHITECTURAL AND INSTALLATIONREQUIREMENTS NOMINAL t i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 0 7 L W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 ...

Page 6: ... regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both c...

Page 7: ...d to the unit The damper blade is locked in the closed position to allow the damper to operate the maximum and minium blade position stops must be installed See Figure 2 All capacity efficiency and cost of operation information as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank...

Page 8: ... and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on left side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil Additional clearance may...

Page 9: ... 2 2 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operating condition Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 8 WIRING LOW VOLTAGE ...

Page 10: ... n o o t u a n a F l o o c o t u a t a e h m e t s y S 1 2 0 3 0 4 8 4 3 9 1 D 4 7 8 T 2 1 0 4 0 4 8 1 0 0 1 A 4 7 6 Q t a e h e g a t s 2 l o o c e g a t s 2 n o o t u a n a F l o o c o t u a t a e h m e t s y S 9 4 0 3 0 4 8 0 8 3 3 9 F 1 t a e h e g a t s 2 l o o c e g a t s 2 g n i m m a r g o r p y a d 7 c i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C l o o c e g a t s 1 t a e h e g a t s 1 n o o...

Page 11: ...49 Page 9 FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 1051 MIS 948 SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS ...

Page 12: ...Manual 2100 349 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 1050 ...

Page 13: ...Manual 2100 349 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1373C ...

Page 14: ...a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal protector will trip All three phase ZR3 c...

Page 15: ...ck all power fuses or circuit breakers to be sure they are the correct rating 3 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor...

Page 16: ...n be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB se...

Page 17: ...OUD 1 Disconnect all power to unit 2 Remove the screws holding both grills one on each side of unit and remove grills 3 Remove screws holding fan shroud to condenser and bottom 9 screws 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service motor fan as needed 7 Reverse steps to reinstall REFRIGERANT CHARGE The correct system R 22 ...

Page 18: ... 9 6 3 3 3 0 7 1 5 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 6 0 2 2 8 6 6 3 2 9 6 4 5 2 0 7 1 7 2 1 7 7 8 2 2 7 6 0 3 3 7 4 2 3 4 7 2 4 3 5 7 0 6 3 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 2 7 5 2 2 3 7 3 4 2 4 7 1 6 2 5 7 9 7 2 6 7 7 9 2 7 7 6 1 3 8 7 5 3 3 9 7 3 5 3 0 8 2 7 3 TABLE 13 OPTIONALACCESSORIES WL701 A WL701 B WL701 C L E D O M N O I T P I R C S E D L 5 0 A 5 0 A W H E e ...

Reviews: