ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models. It is imperative to match
the correct pressure table to the unit by model number.

Adjustable Delay On Make and Break Timer

On initial power up or any time power is interrupted to
the unit the delay on make period begins which will be
2 minutes plus 10% of the delay on break setting.
When the delay on make is complete and the high
pressure switch (and low pressure switch if employed)
is closed, the compressor contactor is  energized. Upon
shutdown the delay or break timer starts and prevents
restart until the delay on break and delay on make
periods have expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm relay
circuit will energize.   Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

Summary of Contents for WL4842

Page 1: ...NTED PACKAGE AIR CONDITIONERS MODELS WL4842 WL4843 WL6022 WL6023 WL602N Manual 2100 402 Supersedes File Volume III Tab 16 Date 01 28 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ah...

Page 2: ...gerant Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Pub...

Page 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Page 4: ...1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter...

Page 5: ...Manual 2100 402 Page 3 FIGURE 1 UNITDIMENSIONS WL602N WL6023 WL4843 ONLY MIS 1451...

Page 6: ...Manual 2100 402 Page 4 FIGURE 2 UNITDIMENSIONS WL6022 WL4842 ONLY MIS 1452...

Page 7: ...i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 4 8 4 L W 1 8 0 2 0 3 2 1 6 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 4 8 4 L W 3 8 0 2 0 3 2 1 5 2 5...

Page 8: ...h filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WL6023 and WL4843 models require the use of a return air filter grille While these...

Page 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1...

Page 10: ...Manual 2100 402 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS WL602N WL6023 WL4843 ONLY MIS 1349...

Page 11: ...Manual 2100 402 Page 9 FIGURE 4 MOUNTINGINSTRUCTIONS WL6022 WL4842 ONLY MIS 1444...

Page 12: ...RNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 i...

Page 13: ...STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED...

Page 14: ...Manual 2100 402 Page 12 FIGURE 8 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Page 15: ...base to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important i...

Page 16: ...Manual 2100 402 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A...

Page 17: ...ined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may...

Page 18: ...ntil the delay on break and delay on make periods have expired During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch...

Page 19: ...t a r e p m e T D O 2 8 e r u t a r e p m e T 2 0 6 L W 0 0 7 1 5 5 3 5 2 6 0 6 4 8 4 L W 0 5 5 1 6 5 4 5 7 6 5 6 TABLE 8 RATED CFM AND ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c...

Page 20: ...1 1 5 1 1 2 0 6 L W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6 e d...

Page 21: ...L4842A WL4843B WL4842B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e...

Reviews: