Manual   2100-351
Page  16

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models. It is imperative to match the
correct pressure table to the unit by model number.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor and
phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm relay
circuit will energize.   Recycling the wall thermostat
resets the manual lockout.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds.

Summary of Contents for WL4822

Page 1: ...ACKAGE AIR CONDITIONERS MODELS WL4822 WL4823 WL6022 WL6023 WL602N Manual 2100 351D Supersedes 2100 351C File Volume III Tab 16 Date 09 20 01 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Movi...

Page 2: ...gerant Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Pub...

Page 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Page 4: ...0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filt...

Page 5: ...Manual 2100 351 Page 3 FIGURE 1 UNIT DIMENSIONS WL602N WL6023 WL4823 ONLY MIS 1451...

Page 6: ...Manual 2100 351 Page 4 FIGURE 2 UNIT DIMENSIONS WL6022 WL4822 ONLY MIS 1452...

Page 7: ...K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 2 8 4 L W 1 8 0 2 0 3 2 1 8 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 2 8 4 L W 3 8 0 2 0 3 2 1 6 2 5 3 8 0 1 A N A N A N A N A N A N...

Page 8: ...h filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WL6023 and WL4823 models require the use of a return air filter grille While these...

Page 9: ...pply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1...

Page 10: ...Manual 2100 351 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WL602N WL6023 WL4823 ONLY MIS 1349...

Page 11: ...Manual 2100 351 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WL6022 WL4822 ONLY MIS 1444...

Page 12: ...ARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4...

Page 13: ...LL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHE...

Page 14: ...Manual 2100 351 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS MIS 550...

Page 15: ...entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are s...

Page 16: ...Manual 2100 351 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A...

Page 17: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 18: ...mage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are revers...

Page 19: ...y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 0 5 8 1 5 5 7 1 0 0 7 1 5 7 6 1 0...

Page 20: ...0 1 1 5 1 1 2 0 6 L W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6 e...

Page 21: ...L4822A WL4823B WL4822B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e...

Reviews: