Bard WH422D Installation Instructions Manual Download Page 19

Manual   2100-443
Page    17

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 11.

When the outdoor temperature is in the lower 40° F
temperature range or colder, the outdoor coil
temperature is 32° F or below.  This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil.  Once coil temperature
reaches 30° F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.

After 60 minutes at 30° F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57° F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of
30, 60 or 90 minutes setting.  All models are shipped
from the factory on the 60 minute pin.  If special
circumstances require a change to another time, remove
the wire from the 60 minute terminal and reconnect to
the desired terminal.  The manufacturer's
recommendation is for 60 minute defrost cycles.  Refer
to Figure 11

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the SPEEDUP
terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals.  It
may take up to 10 seconds with the SPEEDUP
terminals shorted for  the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run
through the 1 minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a  0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the SEN JMP terminals (a
1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the SEN JMP
jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5 minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances it is helpful to
the service technician to override or speed up this timing
period, and shorting out the SPEEDUP terminals for a few
seconds can do this.

FIGURE  11

DEFROST CONTROL BOARD

Summary of Contents for WH422D

Page 1: ...T PUMPS MODELS WH422D WH484D WH603D INSTALLATION INSTRUCTIONS Copyright 2003 Manual 2100 443 Supersedes File Volume III Tab 17 Date 10 23 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Movi...

Page 2: ...or 19 Fan Blade Dimensions 20 Removal of Fan Shroud 20 Refrigerant Charge 20 Pressure Tables 21 22 Optional Accessories 23 Figures Figure 1 Unit Dimensions 3 Figure 2 Blower Damper Assembly 6 Figure 3...

Page 3: ...tems Load Calculation for ACCA Manual J or N Residential Winter and Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Q Duct System Design for Winter and Summer Air Conditioning For m...

Page 4: ...3 0 0 6 5 2 CONTROL MODULES NOTE For 0 KW and circuit breakers 230 208 V or pull disconnects 460 V applications insert 0Z in the KW field of model number MODEL NUMBER CAPACITY 42 3 1 2 Ton 48 4 Ton 6...

Page 5: ...Manual 2100 443 Page 3 FIGURE 1 UNITDIMENSIONS MIS 411...

Page 6: ...1 4 3 0 6 6 8 0 5 0 7 0 9 8 6 3 0 1 8 8 A N 4 3 4 3 A N 6 2 2 5 A N 0 5 0 5 A N 0 3 0 6 A N 8 8 A N 0 1 6 A N 0 1 0 1 A N 0 1 0 1 Z 0 B 0 0 B D 2 2 4 H W 6 0 B 3 9 0 B 3 8 0 2 0 3 2 1 1 1 6 2 4 4 3 5...

Page 7: ...rs of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent conde...

Page 8: ...er drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already atta...

Page 9: ...pening would then be 32 x 12 See Figures 2 4 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain fl...

Page 10: ...required from combustible materials Supply Air Duct Return Air Opening Wall Circuit breaker access door Heater access panel Note It is recommended that a bead of silicone caulking be placed behind the...

Page 11: ...3 Page 9 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 548 MIS 549 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DU...

Page 12: ...Manual 2100 443 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 550...

Page 13: ...WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable ope...

Page 14: ...ENERGY MONITOR FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and t...

Page 15: ...MMABLETHERMOSTATFULLTIMEDEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and th...

Page 16: ...tc that will prevent compressor from operating will cause red lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 3 THERMOSTATWIRESIZE r...

Page 17: ...nitor on page 15 of this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact...

Page 18: ...irculation HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provide heat pump heating If the room temperature falls below the 2nd stage heating se...

Page 19: ...ver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrum...

Page 20: ...l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o t...

Page 21: ...85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0...

Page 22: ...8 4 H W 3 0 6 H W 5 7 1 TABLE 9 INDOORBLOWERPERFORMANCE CFM 230V P S E H n i 2 O 4 8 4 H W 2 2 4 H W 3 0 6 H W V 0 3 2 w o L V 0 3 2 h g i H V 0 3 2 w o L V 0 3 2 h g i H l i o C y r D l i o C t e W l...

Page 23: ...7 5 0 2 5 7 0 2 2 7 7 5 3 2 8 7 1 5 2 9 7 6 6 2 0 8 2 8 2 0 8 7 9 2 1 8 3 1 3 2 8 9 2 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 0 1 2 0 8 6 2 2 2 8 1 4 2 3 8 7 5 2 4 8 3 7 2 5 8...

Page 24: ...ription 5 0 A 2 4 H W H E s e g a k c a P r e t a e H X 0 1 A 2 4 H W H E s e g a k c a P r e t a e H X 6 0 C 2 4 H W H E s e g a k c a P r e t a e H X 5 0 A 4 0 H W H E s e g a k c a P r e t a e H X...

Page 25: ...t a e H e g a t S t s 1 d e i p u c c O X X X X X X g n i t a e H e g a t S t s 1 m u h e D w X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c o n U X X X X X X X X X g n i t a e H e g a...

Reviews: