Bard WH422D Installation Instructions Manual Download Page 17

Manual   2100-443
Page    15

START UP

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor
coil with a dishwashing detergent.

CRANKCASE HEATERS

WH422 units are provided with compressor crankcase
heat.  WH484 and WH603 units are not provided with
crankcase heat.  These units utilize scroll compressors
which do not require crankcase heat in this application.

The WH422 models have an insertion well-type heater
located in the lower section of the compressor housing
this is a self-regulating type heater that draws only
enough power to maintain the compressor at a safe
temperature on these units.

Some form of crankcase heat is essential to prevent
liquid refrigerant from migrating to the compressor,
causing oil pump out on compressor start-up and
possible valve failure due to compressing a liquid.

The decal in Figure 10 is affixed to all WH422 units
detailing start-up procedure.  This is very important.
Please read carefully.

HIGH PRESSURE SWITCH

The models are supplied with a remote reset high
pressure switch.  If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made. All three
phase scroll  units incorporate a phase monitor to ensure
proper field wiring.  See the Phase Monitor" on page 15
of this manual.

Verification of proper rotation must be made any time
a compressor is change or rewired.  If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

FIGURE  10

START UP LABEL

IMPORTANT

THESE PROCEDURES MUST BE FOL-
LOWED AT INITIAL START UP AND AT
ANY TIME POWER HAS BEEN REMOVED
FOR 12 HOURS OR LONGER.

TO PREVENT COMPRESSOR DAMAGE WHICH
MAY RESULT FROM THE PRESENCE OF LIQ-
UID REFRIGERANT IN THE COMPRESSOR
CRANKCASE:

1.

MAKE CERTAIN THE ROOM THERMOSTAT IS
IN THE “OFF“ POSITION. (THE COMPRESSOR
IS NOT TO OPERATE.)

2.

APPLY POWER BY CLOSING THE SYSTEM
DISCONNECT SWITCH. THIS ENERGIZES THE
COMPRESSOR HEATER WHICH EVAPO-
RATES THE LIQUID REFRIGERANT IN THE
CRANKCASE.

3.

ALLOW 4 HOURS OR 60 MINUTES PER
POUND OF REFRIGERANT IN THE SYSTEM AS
NOTED ON THE UNIT RATING PLATE, WHICH-
EVER IS GREATER.

4.

AFTER PROPER ELAPSED TIME THE THER-
MOSTAT MAY BE SET TO OPERATE THE COM-
PRESSOR.

5.

EXCEPT AS REQUIRED FOR SAFETY WHILE
SERVICING, DO NOT OPEN SYSTEM DISCON-
NECT SWITCH.

7961-411

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor's
internal protector will trip.

All three phase ZR3 compressors are wired identical
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the  same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.

Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulated values.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

Summary of Contents for WH422D

Page 1: ...T PUMPS MODELS WH422D WH484D WH603D INSTALLATION INSTRUCTIONS Copyright 2003 Manual 2100 443 Supersedes File Volume III Tab 17 Date 10 23 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Movi...

Page 2: ...or 19 Fan Blade Dimensions 20 Removal of Fan Shroud 20 Refrigerant Charge 20 Pressure Tables 21 22 Optional Accessories 23 Figures Figure 1 Unit Dimensions 3 Figure 2 Blower Damper Assembly 6 Figure 3...

Page 3: ...tems Load Calculation for ACCA Manual J or N Residential Winter and Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Q Duct System Design for Winter and Summer Air Conditioning For m...

Page 4: ...3 0 0 6 5 2 CONTROL MODULES NOTE For 0 KW and circuit breakers 230 208 V or pull disconnects 460 V applications insert 0Z in the KW field of model number MODEL NUMBER CAPACITY 42 3 1 2 Ton 48 4 Ton 6...

Page 5: ...Manual 2100 443 Page 3 FIGURE 1 UNITDIMENSIONS MIS 411...

Page 6: ...1 4 3 0 6 6 8 0 5 0 7 0 9 8 6 3 0 1 8 8 A N 4 3 4 3 A N 6 2 2 5 A N 0 5 0 5 A N 0 3 0 6 A N 8 8 A N 0 1 6 A N 0 1 0 1 A N 0 1 0 1 Z 0 B 0 0 B D 2 2 4 H W 6 0 B 3 9 0 B 3 8 0 2 0 3 2 1 1 1 6 2 4 4 3 5...

Page 7: ...rs of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent conde...

Page 8: ...er drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already atta...

Page 9: ...pening would then be 32 x 12 See Figures 2 4 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain fl...

Page 10: ...required from combustible materials Supply Air Duct Return Air Opening Wall Circuit breaker access door Heater access panel Note It is recommended that a bead of silicone caulking be placed behind the...

Page 11: ...3 Page 9 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 548 MIS 549 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DU...

Page 12: ...Manual 2100 443 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 550...

Page 13: ...WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable ope...

Page 14: ...ENERGY MONITOR FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and t...

Page 15: ...MMABLETHERMOSTATFULLTIMEDEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and th...

Page 16: ...tc that will prevent compressor from operating will cause red lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 3 THERMOSTATWIRESIZE r...

Page 17: ...nitor on page 15 of this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact...

Page 18: ...irculation HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provide heat pump heating If the room temperature falls below the 2nd stage heating se...

Page 19: ...ver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrum...

Page 20: ...l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o t...

Page 21: ...85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0...

Page 22: ...8 4 H W 3 0 6 H W 5 7 1 TABLE 9 INDOORBLOWERPERFORMANCE CFM 230V P S E H n i 2 O 4 8 4 H W 2 2 4 H W 3 0 6 H W V 0 3 2 w o L V 0 3 2 h g i H V 0 3 2 w o L V 0 3 2 h g i H l i o C y r D l i o C t e W l...

Page 23: ...7 5 0 2 5 7 0 2 2 7 7 5 3 2 8 7 1 5 2 9 7 6 6 2 0 8 2 8 2 0 8 7 9 2 1 8 3 1 3 2 8 9 2 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 0 1 2 0 8 6 2 2 2 8 1 4 2 3 8 7 5 2 4 8 3 7 2 5 8...

Page 24: ...ription 5 0 A 2 4 H W H E s e g a k c a P r e t a e H X 0 1 A 2 4 H W H E s e g a k c a P r e t a e H X 6 0 C 2 4 H W H E s e g a k c a P r e t a e H X 5 0 A 4 0 H W H E s e g a k c a P r e t a e H X...

Page 25: ...t a e H e g a t S t s 1 d e i p u c c O X X X X X X g n i t a e H e g a t S t s 1 m u h e D w X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c o n U X X X X X X X X X g n i t a e H e g a...

Reviews: