FIGURE  14

DEFROST CONTROL BOARD

Be careful not to touch any other terminals with the
instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

terminals shorted for  the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.

Otherwise the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a  0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor

mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances it is helpful to
the service technician to override or speed up this timing
period, and shorting out the 

SPEEDUP

 terminals for a few

seconds can do this.

Summary of Contents for WH381

Page 1: ...ED PACKAGE HEAT PUMPS Models WH381 WH431 WH491 INSTALLATION INSTRUCTIONS Manual 2100 342I Supersedes 2100 342H File Tab 17 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Movi...

Page 2: ...ns 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Condensate Drains 8 Figure 4 Mounting Instructi...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Page 4: ...URE MODEL NUMBER CONTROL MODULES CAPACITY 38 3 Ton 43 3 Ton 49 4 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blan...

Page 5: ...p p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H W 1 3 4 H W 1 9 4 H W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6...

Page 6: ...S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H W 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8...

Page 7: ...ach unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are al...

Page 8: ...n open or vented type system to assure proper drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh air damper asse...

Page 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 4 and 4A for details WARNING Failur...

Page 10: ...Manual 2100 342I Page 10 of 24 FIGURE 4 MOUNTING INSTRUCTIONS...

Page 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Page 12: ...Manual 2100 342I Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 13: ...Manual 2100 342I Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left...

Page 15: ...zation of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points NOTE The additional LAB low ambient bypass relay is required to pr...

Page 16: ...eration of the electric heat until outdoor temperatures have reached a certain design point This won t allow the electric heat to come on as second stage heating unless the outdoor temperature is belo...

Page 17: ...ing See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there wil...

Page 18: ...ergizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B terminal being constantly energized from R A thermostat demand for heat completes...

Page 19: ...he defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit...

Page 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Page 21: ...0 6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3...

Page 22: ...e d o M n o i s n e m i D A 1 8 3 H W 1 3 4 H W 1 9 4 H W 0 0 1 l e d o M 1 8 3 H W 1 3 4 H W 1 9 4 H W W K h g i H d e e p S d e M d e e p S w o L d e e p S h g i H d e e p S d e M d e e p S 5 0 A 3...

Page 23: ...n I 2 O 1 8 3 H W 1 9 4 H W 1 3 4 H W d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i...

Page 24: ...h g i H 7 7 3 0 2 7 7 8 1 2 7 7 4 3 2 8 7 0 5 2 9 7 7 6 2 0 8 5 8 2 2 8 4 0 3 4 8 4 2 3 6 8 4 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 0 8 0 1 2 0 8 6 2 2 0 8 2 4 2 1 8 9 5 2 2 8...

Reviews: