background image

Manual    2100-356
Page        17

FAN BLADE SETTING DIMENSIONS

Shown in the drawing below are the correct fan blade
setting dimensions for proper air delivery across the outdoor
coil.

Any service work requiring removal or adjustment in the fan
and/or motor area will require that the dimensions below be
check and blade adjusted in or out on the motor shaft
accordingly.

REMOVAL OF THE FAN SHROUD

1. Disconnect all power to unit.

2. Remove the screws holding both grilles, one on each

side of unit, and remove grilles.

3. Remove screws (9) holding fan shroud to condenser and

bottom.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud assembly

out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating
plate.  Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 7.

FIGURE  10

The above suction line temperatures are based upon 80° F
dry bulb/67° F wet bulb (50% R.H.) temperature and rated
airflow across the evaporator during cooling cycle.

TABLE  6

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

D

1

4

2

H

W

0

0

.

1

MIS-1190

TABLE  7

(Temperatures °F)

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

D

O

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

2

8

e

r

u

t

a

r

e

p

m

e

T

D

1

4

2

H

W

0

0

8

9

5

-

7

5

7

6

-

5

6

TABLE  8

INDOOR BLOWER PERFORMANCE

 CFM 

230V

.

P

.

S

.

E

H

n

I

2

O

D

1

4

2

H

W

y

r

D

t

e

W

0

.

1

.

2

.

3

.

4

.

5

.

6

.

0

2

0

1

0

6

9

5

6

8

0

2

8

5

3

7

5

1

6

-

-

-

5

7

9

5

0

9

0

0

8

5

3

7

0

5

6

5

3

5

-

-

-

TABLE  9

RATED CFM AND ESP

*

  

Rated CFM and ESP on high speed tap.

l

e

d

o

M

d

e

t

a

R

*

M

F

C

d

e

t

a

R

*

P

S

E

d

e

d

n

e

m

m

o

c

e

R

e

g

n

a

R

w

o

l

f

r

i

A

D

1

4

2

H

W

0

0

8

0

2

.

0

5

9

0

0

7

l

e

d

o

M

P

S

E

D

1

4

2

H

W

0

0

A

4

0

A

8

0

A

0

5

.

0

5

.

0

4

.

D

1

4

2

H

W

0

0

B

6

0

B

0

5

.

0

5

.

D

1

4

2

H

W

0

0

C

6

0

C

0

5

.

0

5

.

Values shown are for units equipped with
standard throwaway filter or 1” washable
filter.  Derate ESP by .15 for 2” pleated filter.

TABLE  10

MAXIMUM ESP OF OPERATION

Summary of Contents for WH241D

Page 1: ...LATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMP MODELS WH241D Manual 2100 356 File Volume III Tab 17 Date 10 01 99 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as pl...

Page 2: ...ircuit Diagram H P Cooling Mode 20 Figure 12 Circuit Diagram H P Dehumidification 20 Start Up 12 Important Installer Note 12 Crankcase Heaters 12 Service Hints 12 Sequence of Operation 12 Pressure Ser...

Page 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contrac...

Page 4: ...codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air These instructions explain the recommended method to install the...

Page 5: ...n r u t e R E F G I J K L M N O P Q R S T A B C D D 1 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6...

Page 6: ...energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure available for duct design Design the duct work according to methods given by the Air Conditioning Cont...

Page 7: ...kets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh ai...

Page 8: ...as shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend...

Page 9: ...Manual 2100 356 Page 7 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353...

Page 10: ...Manual 2100 356 Page 8 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...Manual 2100 356 Page 9 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 550...

Page 12: ...unit rating plate for wire sizing information and maximum fuse or HACR type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must...

Page 13: ...E SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5...

Page 14: ...motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A 24V solenoid coil on reversing va...

Page 15: ...compressor will be de energized by the evaporator defrost sensor until the coil temperature rises above 57 degrees PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units...

Page 16: ...Manual 2100 356 Page 14 FIGURE 9 DEFROST CONTROL BOARD MIS 1174...

Page 17: ...h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F g n i l o o c n u r t o n s e o d t p e c x e g n i t a e h r o t s o r f e d g n i r u d e...

Page 18: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Page 19: ...in a suction line temperature 6 from compressor as shown in Table 7 FIGURE 10 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across...

Page 20: ...Outdoor Coil F Low Side Pressure 2 PSIG High Side Pressure 5 PSIG Tables are based upon rated CFM airflow across the evaporator coil and should be found under section titled Refrigerant Charge elsewhe...

Page 21: ...B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r...

Page 22: ...OIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASS Y 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM INDOOR COIL RE...

Reviews: