Manual 2100-757
Page
11 of 17
FIGURE 7
8403-096 CO
2
Sensor Set Up
ON
OFF
OFF
OFF
ON
4
6
5
2
3
ON
1
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
IT HAS BEEN CONFIGURED.
DIP SWITCH TO "OFF" AFTER
CONTROLLER MOVE
NOTE: MENU
DIP SWITCH MUST
BE IN "ON" POSITION #5
TO CHANGE ANY
SETTINGS WITH
THE SIDE BUTTONS.
TO LOCK THE CO2
DIP SWITCHES MUST BE
POSITIONED AS SHOWN
FOR PROPER OPERATION
MIS-4025 C
Settings
Recommended Default
RON
(RELAY ON SET POINT)
725
ROF
(RELAY OFF SET POINT)
700
DSP
(DISPLAY
CONFIGURATION)
C
CT
UNI
(UNITS SELECTION)
US
US
COL
(CO2 LOW OUTPUT
RANGE)
700
0
COH
(CO2 HIGH OUTPUT
RANGE)
1500
2000
TOL
(TEMP. LOW OUTPUT
RANGE)
Not Used
TOH
(TEMP. HIGH OUTPUT
RANGE)
Not Used
BAR
(BAROMETRIC
PRESSURE)
See Instructions with
Controller For High
Altitude Installations
CAL
(CALIBRATION)
Used for Field Calibration
Summary of Contents for WGSCRVS-3C
Page 4: ...Manual 2100 757 Page 4 of 17 FIGURE 1 Call for Blower Operation without Ventilation...
Page 5: ...Manual 2100 757 Page 5 of 17 FIGURE 2 Call for Ventilation...
Page 12: ...Manual 2100 757 Page 12 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...
Page 13: ...Manual 2100 757 Page 13 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...
Page 14: ...Manual 2100 757 Page 14 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...