background image

Manual 2100-757B

Page 

9 of 17

Ventilator Checkout

Blade Adjustment for Desired Ventilator Air

The amount of ventilation air supplied by the 
commercial room ventilator is dependent on four 
factors.
a.  Return air duct static pressure drop
b.  Supply air duct static pressure drop
c.  Indoor blower motor speed
d.  Damper blade open position setting
 To determine the amount of fresh air that will be 

supplied to the structure, first determine the pressure 
drops of the supply and return air ducts. For free blow 
application with return air filter grille and supply grille, 
assume .05 supply static and .10 return static.

 Determine on what speed the evaporator motor is 

running.

 Refer to the graphs found on pages 12-14 to 

determine the blade setting necessary to achieve the 
ventilation air required at the supply and return static 
duct pressure drops that are applicable.

NOTE:

 The ventilation air shown in the graphs on pages 

12-14 is without the condenser fan running. 

When the condenser fan is running, the 

ventilation air will increase slightly.

WGCRVS Model Checkout

1.  Open blower door and remove filters to gain 

access to the CRV control board (8201-167) 
located behind the front fill partition on top of the 
ventilator.

2.  Resupply power to unit.
3.  Energize the evaporator blower by switching 

thermostat to the manual fan position with heat/
cool in OFF position.

4.  Ventilator should open to the position set by the 

OCC potentiometer on the CRV control board (see 
Figure 6 on page 10). Cycle OCC potentiometer 
to full open through full close. Observe damper 
blade operation throughout travel to assure free, 
unobstructed movement.

5.  Adjust OCC potentiometer until desired blade 

setting is reached with power applied to unit. See 
the graphs found on pages 12-14 for required 
blade setting versus ventilator air for the unit 
installed.

6.  De-energize the evaporator blower. Damper blade 

should close.

7.  Re-install filter.

WGCRVS Sequence of Operation

This ventilation option includes a control board with 
blade positioning potentiometers along with an input 
for a 2-10V input signal (see Figure 6 on page 10).
Adjustable potentiometers:

“PP” Potentiometer setting:

 This potentiometer can be 

used to adjust the blade setting for outdoor air intake 
during a pre-purge cycle. The pre-purge cycle time is 
based on the setting of the pre-purge timer.

“OCC” Potentiometer setting:

 This potentiometer can 

be used to adjust the blade setting for outdoor air 
intake when the “A” terminal is energized on the low 
voltage terminal strip indicating occupancy or demand.

“Y1” Potentiometer setting:

 

Not applicable on this 

model.

“Y2” Potentiometer setting:

 

Not applicable on this 

model.

Pre-Purge Feature

Pre-purge is used to ventilate a specified CFM amount 
before occupants enter the room or structure. The 
control board has a built-in pre-purge timer that can 
be set to 30, 60 and 90 minute intervals by moving 
the jumper (see Figure 6 on page 10). This timer will 
start when the jumper is installed and the A terminal 
is energized on the low voltage terminal strip. Blade 
adjustment can be made on the PP potentiometer. 
Once the timer has timed out, the board will default 
to the occupied setting and this blade position can 
be adjusted on the OCC potentiometer. If the timer is 
set to 0 (off—shipped position), the occupied setting 
is instantaneous and the pre-purge setting (PP) is no 
longer in the sequence.

Occupied Setting

Occupied is used to ventilate a specified CFM amount 
when occupants enter the room or structure. The 
control board will energize the occupied setting 
after the pre-purge cycle, or if pre-purge is disabled 
immediately when the A terminal is energized on the 
low voltage strip. Blade adjustment can be made on the 
OCC potentiometer.

Y1 Setting

Not applicable on this model

Y2 Setting

Not applicable on this model

2-10V Operation

A CO

2

 sensor or other device sending a 2-10V signal 

can be used to control the damper motor. Two control 
methods are available to control the damper motor:
•  Method 1: The control board will accept a 

2-10VDC signal with a resistive load greater than 
5000 ohms. Bard CO

2

 sensor part #8403-096 can 

be used when the 2-10V output is connected to 

Summary of Contents for WGCRVS-3C

Page 1: ...nufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 757B Supersedes 2100 757A Date 11 14 22 For Use with Bard Single Stage W G4 Units Commercial Room Ventilator with Exhaust and CO2...

Page 2: ...for Blower Operation w o Ventilation 4 Figure 2 Call for Ventilation 5 Figure 3 Removal of Vent Option Panel 6 Figure 4 Loose Piece Wire Harness Plug Install 7 Figure 5 Ventilator Installed in Unit 8...

Page 3: ...reported to the carrier within 15 days of its receipt Description The ventilators are designed to be used with Bard 2 5 ton single stage wall mount gas electric units They are electromechanical vent...

Page 4: ...Manual 2100 757B Page 4 of 17 FIGURE 1 Call for Blower Operation without Ventilation...

Page 5: ...Manual 2100 757B Page 5 of 17 FIGURE 2 Call for Ventilation...

Page 6: ...nit see Figure 3 3 Remove and save existing unit air filter and screw from front center grille see Figure 5 on page 8 for screw location 4 Remove and discard the exhaust cover plate 5 Replace the exha...

Page 7: ...ontrol box 9 Connect leads with fork terminal to corresponding points on terminal strip See wiring diagrams later in this manual or on ventilator Plug connector into corresponding hole in filter rack...

Page 8: ...INSET Plug mating plug from WGCRV into plug in filter partition When installing WGCRV position so that hole in front lip is centered over hole in condenser grill to insert a self drilling screw Mist E...

Page 9: ...ontrol board with blade positioning potentiometers along with an input for a 2 10V input signal see Figure 6 on page 10 Adjustable potentiometers PP Potentiometer setting This potentiometer can be use...

Page 10: ...or directly from the device providing the 2 10VDC modulating signal The gray wire connected to CO2 V IN on the control board must be spliced with the white wire ran to the damper motor V OUT on contro...

Page 11: ...TO CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY...

Page 12: ...Manual 2100 757B Page 12 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...

Page 13: ...Manual 2100 757B Page 13 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...

Page 14: ...Manual 2100 757B Page 14 of 17 Fresh Air CFM Fresh Air CFM Fresh Air CFM...

Page 15: ...and connect to N C fire alarm circuit if emergency shutdown required 3 2 Wire required for dehumidification models only 1 For vent operation thermostat must be configured for programmable events per...

Page 16: ...r to the up position Connect wire to lower U terminal for vent operation Only applies to 8403 090 1 Jumper needs added when using 8403 047 humidistat RED WHITE BLACK WHITE ORANGE BROWN WHITE GRAY CRVS...

Page 17: ...1 GRAY 2 jumper is used from A to G Move Brown White wire landing from COM to NC if CONTROL PANEL 1 40 43 9 PIN MOLEX PLUG FEMALE 9 PIN MOLEX PLUG MALE 39 2 1 4056 266 D 30 0 CRV CONTROL BOARD 60 90 R...

Reviews: