Commercial Room Ventilator (CRV) No Hood 

Installation

1.  Insert CRV into opening in the wall mount unit 

between the filter rack and the condenser section, 
being careful not to tear the unit insulation.  Fully 
seat CRV assembly to rear of the cavity.  Slide the 
CRV toward the control panel so that it lines up 
with the return air opening in the rear of the wall 
mount unit (see Figure 5 on page 8).

2.  Insert and lock in the 12-pin plug end of the wire 

assembly into the front side of the unit’s control 
panel (see Figure 5). 

3.  Replace the air filters if they were removed (airflow 

direction is up).

4.  The next step involves installing the unit’s filter 

door and putting the mist eliminator filter into 
place (see Figure 6 on page 8).

5.  With the lower vent option door removed, locate 

the control board.  Then, make all the required 
thermostat connections per the applicable 
connection diagram found on pages 11 or 12, and 
restore power to the unit.

6.  Make any necessary changes required to 

the potentiometers to achieve the minimum 
continuous airflow and demand airflow desired (see 
Figure 7 on page 10.

7.  Then, replace the lower vent option door with the 

four (4) screws provided as shown in Figure 6. 

FIGURE 4

Extension Cable Installation

NOTE:

 Incorporated with the WCRVPS*P is one piece of 20˝ split tubing.  The tubing will cover the wire assembly routed to 

the actuator.  The tubing and wires will be routed under the actuator assembly.

MIS-3864

F0R 5-TON SECURE

ORIENTATION FOR

RIGHT HAND UNITS

ORIENTATION FOR

LEFT HAND UNITS

WITH CABLE TIE

UNIT CONTROL PANEL.

CONNECTOR WILL PLUG IN TO THE FRONT SIDE OF THE

CONTROL USING THE TWO SCREWS. THE 12-PIN

PART #7950-009

12 PIN CONNECTOR FROM CRV STEP CONTROL

WILL PLUG INTO THE FRONT SIDE OF THE UNIT

CONTROL PANEL
FOR LEFT HAND MODELS, REMOVE SCREWS HOLDING

CRV STEP CONTROL BRACKET. ROUTE CONTROL

UNDER CENTER ACTUATOR SUPPORT BRACKET, AND

THEN TO LEFT SIDE OF DAMPER ASSEMBLY, RE-SECURE

ROUTE THE 20" LONG EXTENSION

CABLE ACROSS THE TOP OF THE

DAMPER ASSEMBLY

MIS-3864

FOR 5 TON, SECURE 

WITH CABLE TIE 

PART #7950-009

ORIENTATION FOR 

LEFT HAND UNITS

ROUTE THE 20" LONG EXTENSION CABLE 
ACROSS THE TOP OF THE DAMPER ASSEMBLY

ORIENTATION FOR 
RIGHT HAND UNITS

12-PIN CONNECTOR FROM CRV STEP 
CONTROL WILL PLUG INTO THE FRONT 
SIDE OF THE UNIT CONTROL PANEL.

FOR LEFT HAND MODELS, REMOVE 
SCREWS HOLDING CRV STEP CONTROL 
BRACKET. ROUTE CONTROL UNDER 
CENTER ACTUATOR SUPPORT BRACKET 
AND THEN TO LEFT SIDE OF DAMPER 
ASSEMBLY; RE-SECURE CONTROL 
USING THE TWO SCREWS. THE 12-PIN 
CONNECTOR WILL PLUG IN TO THE 
FRONT SIDE OF THE UNIT CONTROL 
PANEL.

Summary of Contents for WCRVPS2P

Page 1: ...S5P WCRVPS6P Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 667 Supersedes NEW Date 2 14 17 For Use with Bard Single Stage Wall Mount Air Conditioner and Heat Pump Models...

Page 2: ...on 8 Figure 6 Vent Door Assembly 8 Figure 7 CRV Control Board 10 Figure 8 Required Control Connections for CRV with Air Conditioners 11 Figure 9 Required Control Connections for CRV with Heat Pumps 12...

Page 3: ...d as a step by step procedure with which the mechanically inclined owner can install the package The ventilator housing is shipped in one carton which contains the electrical harness miscellaneous har...

Page 4: ...applicable Exhaust cover plate discard 4 Install new condenser exhaust plate with screen over opening into condensor section see Figure 2 5 Remove filter brackets if necessary Two types of filter brac...

Page 5: ...e 7 6 Install filter bracket fill plate if applicable as shown in Figure 3 on page 6 7 Install provided filter brackets on WCRVPS P assembly see Figure 3 MIS 3633 FIGURE 2 Condenser Exhaust Plate with...

Page 6: ...t and Filter Bracket Fill Plate Installation MIS 3863 SHORT FILTER BRACKET 4 REGULAR SCREWS LONG FILTER BRACKET LEFT HAND UNIT RIGHT HAND UNIT INSTALL FILTER BRACKET FILL PLATE WITH 2 SCREWS ONLY FOR...

Page 7: ...shown in Figure 6 FIGURE 4 Extension Cable Installation NOTE Incorporated with the WCRVPS P is one piece of 20 split tubing The tubing will cover the wire assembly routed to the actuator The tubing a...

Page 8: ...NEL SIDE ALIGNING IT WITH THE RETURN AIR OPENING IN THE REAR CONTROL PANEL RH SHOWN THE WIRE HARNESS 12 PIN PLUG END FROM THIS LOCATION ON THE VENT PACKAGE WILL PLUG INTO THE FRONT SIDE OF THE CONTROL...

Page 9: ...his can be accomplished by adjusting Potentiometer R1 on the CRV control board by aligning the damper position per the charts included on pages 14 17 see Figure 7 on page 10 The factory default blade...

Page 10: ...UST MINIMUM R1 POT R2 ADJUST DEMAND VENTILATION WHEN NON MODULATION CO2 CONTROL POT R7 ADJUST MINIMUM OCCUPIED AIRFLOW CAN ONLY BE SET WHEN CO2 CONTROL IS READING BELOW 700 PPM OCC PARK TERMINAL TO TH...

Page 11: ...t Model CS9B THO or Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A GND Blue Yellow Orange Red 6 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 Factory installed jumper...

Page 12: ...odel CS9B THO or Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A GND Blue Yellow Orange Red 1 Additional wire required for dehumidification models 2 Not needed below 15KW Factory installed jumper Remove...

Page 13: ...700 0 COH 1500 2000 TOL Not Used TOH Not Used BAR See Instrution with Controller For High Altitude Installations CAL Used for Field Calibration 1 Damper should be at the required minimum occupied vent...

Page 14: ...tiometer R2 6 For more accurate adjustment use a flowhood over the intake opening to measure and adjust the airflow operation Potentiometer R1 Adjusts the minimum constant airflow during occupied cond...

Page 15: ...W24AA Part Flow Ventilation Delivery GRAPH 3 W30AA and W36AA Part Flow Ventilation Delivery 0 100 200 300 400 500 600 700 800 1 2 3 4 5 6 7 8 9 10 Ventilation CFM DAMPER POSITION Supply and Return Gri...

Page 16: ...Manual 2100 667 Page 16 of 19 GRAPH 4 W42AA and W48AA Part Flow Ventilation Delivery GRAPH 5 W60AA Part Flow Ventilation Delivery...

Page 17: ...Manual 2100 667 Page 17 of 19 GRAPH 5 W72AA Part Flow Ventilation Delivery...

Page 18: ...ildings Actuator motor 24 volt power open spring return with built in torque limiting switch Commercial Room Ventilator Sequence of Operation On a call for occupied conditions CRV opens to a position...

Page 19: ...667 Page 19 of 19 FIGURE 12 Call for Compressor or Fan Only with Ventilation Off SUPPLY AIR AIR FILTER COOLING COIL CONDENSER AIR OUTDOOR AIR ELIMINATOR MIST CONDENSER COIL 100 RETURN AIR DAMPER BLAD...

Reviews: