background image

Manual 2100-640D 

Page 

15 of 32

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or circuit breaker size.  Each 
outdoor unit is marked with a “Minimum Circuit 
Ampacity”.  This means that the field wiring used must 
be sized to carry that amount of current. Depending 
on the installed KW of electric heat, there may be 
two field power circuits required.  If this is the case, 
the unit serial plate will so indicate.  All models are 
suitable only for connection with copper wire. Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions 

must be

 

adhered 

to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C 
copper) for all models including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.

The unit rating plate lists a “Maximum Time Delay 
Relay Fuse” or circuit breaker that is to be used with 
the equipment.  The correct size must be used for 
proper circuit protection and also to assure that there 
will be no nuisance tripping due to the momentary high 
starting current of the compressor motor.

The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left-hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.

See “Start Up” section for important information on 
three phase scroll compressor start ups.

See Tables 7 and 8 on pages 26 and 27 for electrical 
specifications.

WIRING – LOW VOLTAGE WIRING 

All 230/208V 1 phase and 3 phase equipment have 
dual primary voltage transformers.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 
208V taps are:

 

TAP RANGE

 

240 

253 – 216

 

208 

220 – 187

NOTE:

  The voltage should be measured at the field 

power connection point in the unit and while 

the unit is operating at full load (maximum 

amperage operating condition).

For low voltage wiring, an 18 gauge copper, color-coded 
cable is recommended. See Table 4 on page 16 for 
more information.

Low Voltage Connections

These units use a 24-volt AC low voltage circuit.  
The “

RT

” terminal is the 24V transformer output, 

and the “

R

” terminal is the 24VAC 

hot

 terminal 

for the operation of the equipment.  “

RT

” and “

R

” 

are connected with brass jumper bar which can be 
removed and “

RT

” and “

R

” connected to external 

NC (normally closed) contact such as a fire/smoke 
detector that will cause immediate shutdown of the 
equipment upon activation.

C

” terminal is

 

grounded

.

G

” terminal is the 

fan input

.

Y1

” terminal is the 

1st Stage input for cooling.

Y2

” terminal is the 

2nd Stage compressor input for 

cooling (if equipped with an economizer).

“B/

W1

” terminal is the 

1st stage electric heat

.

W2

” terminal is the 

2nd stage heat

 (if equipped).

A

” terminal is the 

ventilation input

.  This terminal 

energizes any factory-installed ventilation option and 
indoor blower.

D

” terminal is the 

dehumidification input

.  If 

installed, this terminal energizes any factory installed 
dehumidification option.

For units equipped with an alarm relay:

"L/1" terminal is the 

normally closed contact on the 

relay.

"2" terminal is the 

normally open contact on the relay.

"3" terminal is the 

common contact on the relay.

LOW VOLTAGE CONNECTIONS FOR DDC CONTROL

Standard Units

Units w/

Economizers

Fan Only

Energize G

Energize G

1st Stage 
Cooling Mode

Energize Y1, G

Energize Y1, G

2nd Stage 
Cooling Mode

Energize Y1, Y2, G

1st Stage Heating

Energize B/W1

Energize B/W1

2nd Stage Heating

(if employed)

Energize B/W1, W2

Energize B/W1, W2

Ventilation

Energize A

Energize A

Dehumidification

(if employed)

Energize D

Energize D

Summary of Contents for W72LA-A

Page 1: ...o 43506 www bardhvac com Manual 2100 640D Supersedes 2100 640C Date 11 15 17 W18LA A W24LA A W24LA B W24LA F W30LA A W30LA B W30LA C W30LA F W36LA A W36LA B W36LA C W36LA F W42LA A W42LA B W42LA C W42...

Page 2: ...ecommended Airflow 28 Table 10 Indoor Blower Performance 28 Table 11 Maximum ESP Electric Heat Only 28 Table 12 Electric Heat 29 Table 13 Vent and Control Options 30 Table 14A Optional Accessories Rig...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...tended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 fo...

Page 5: ...r Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be o...

Page 6: ...nit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is pro...

Page 7: ...R S S S 44 E T B N L Disconnect Rain Hood Built In Lockable Low Voltage Access Panel Entrance Heater Electrical Entrance Access Cond Inlet Panel Air Electrical High Voltage Drain Side View 4 Pitch C...

Page 8: ...AULKING ALONG PANEL FOAM AIR SEAL DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNT...

Page 9: ...LY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD...

Page 10: ...9 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MO...

Page 11: ...ROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN...

Page 12: ...ply air duct and combustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in...

Page 13: ...ORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL...

Page 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Page 15: ...All 230 208V 1 phase and 3 phase equipment have dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable...

Page 16: ...stage Heat Electronic Programmable Non Programmable HP or Conventional Auto or Manual changeover Dehumidification Output CS9B THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Convent...

Page 17: ...rogrammable and fan set to be programmed fan for the A output to function during scheduled occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidi...

Page 18: ...nly See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installed jumper Remove jumper and connect to...

Page 19: ...o being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the ch...

Page 20: ...nal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occu...

Page 21: ...gize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm rela...

Page 22: ...3362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back and forth...

Page 23: ...r is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground a...

Page 24: ...harge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws holding fan shroud to condenser...

Page 25: ...38 402 140 427 142 454 145 482 147 512 149 542 151 573 153 605 W36A L 75 62 Low Side High Side 117 323 120 346 122 370 124 394 127 419 129 446 131 473 134 500 136 528 137 558 138 587 80 67 Low Side Hi...

Page 26: ...58 26 60 30 6 10 10 10 W30AA B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 19 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30AA C00 C0Z C06 C09 C12 C15 460 3 1 1 1 1 1 9 12 17 21 26 15 15 20 25 30 14 14 12 10...

Page 27: ...0 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30LA A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 26 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LA B00 B0Z B09 B15 230...

Page 28: ...1940 1750 1700 2105 2010 1540 1460 2255 2155 2075 2015 1995 1930 0 1 965 950 700 690 960 925 1385 1320 930 920 1340 1260 940 930 1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395 2185 2095 2...

Page 29: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12...

Page 30: ...VPC2 Energy Recovery Ventilator 460 Volt X BFAD 3 Barometric Fresh Air Damper Standard X BOP 3 Blank Off Plate X WMFADP3 Motorized Fresh Air Damper X WCRVPS3 Commercial Ventilator Spring Return X WECO...

Page 31: ...W3TA B06 X EHW3TA B09 X X EHW3TA B15 X X EHW3TA C06 X X EHW3TA C09 X X EHW3TA C12 X X EHW3TA C15 X X EHW4TA A05 X X EHWA05 A10B X X X EHWA05 A15B X X X EHWA05 A20B X X X EHW4TA B06 X X X EHWA05 B09B X...

Page 32: ...A10L X X EHW3TA A15L X X EHW3TA B09L X X EHW3TA B15L X X EHW3TA C09L X X EHW3TA C15L X X EHW4TA A05L X X X EHWA05 A10LB X X X EHWA05 A15LB X X X EHW4TA B06L X X X EHWA05 B09LB X X EHW6TA B06L X EHWA0...

Reviews: