Manual 2100-594 

Page  18 of 19

TABLE  5 

COOLING PRESSURE TABLE

Air Temperature Entering Outdoor Coil °F

Low side pressure  ± 4 PSIG                                                         

High side pressure ± 10 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating charge 

being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.

NOTE: 

Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated check  

 

condenser fan wiring.  See “Condenser Fan Operation”.

  Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

  Based on 75C copper wire.  All wiring must conform to the National Electrical Code and all local codes.

  These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National Electrical code (latest version),  

  Article 310 for power conductor sizing.
  

   Caution

: When more than one field power circuit is run through one conduit, the conductors must be derated.  Pay special attention to note 8 of Table 310  

  regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

 *  Top outlet supply option is available only factory installed and only on the selected models.
    

IMPORTANT:

  While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in  

 

 

accordance with the National Electrical Code and all local codes.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

W48A2/L2

75/62

Low Side

High Side

117

355

119

378

121

403

123

427

125

454

127

482

129

510

131

539

133

570

135

603

80/67

Low Side

High Side

125

364

127

388

129

413

132

438

134

466

136

494

138

523

140

553

142

585

144

618

85/72

Low Side

High Side

129

377

131

402

134

427

137

453

139

482

141

511

143

541

145

572

147

605

149

640

W60A2/L2

75/62

Low Side

High Side

122

346

124

371

126

396

128

421

130

447

131

473

133

499

135

526

137

553

138

580

80/67

Low Side

High Side

131

355

133

380

135

406

137

432

139

458

140

485

142

512

144

539

146

567

148

595

85/72

Low Side

High Side

136

367

138

393

140

420

142

447

144

474

145

502

147

530

149

558

151

587

153

616

MODEL

Rated 

Volts & 

Phase

No. Field 

Power 

Circuits

Single Circuit

Minimum 

Circuit 

Ampacity

Maximum 

External Fuse 

or Ckt. Brkr.

Field 

Power 

Wire Size

Ground 

Wire

W48A/L23-A0Z 230/208-1

1

39

50

8

10

W60A/L23-A0Z

-A05

-A10

230/208-3

1

1

1

42

42

60

60

60

60

8

8

6

10

10

10

TABLE  6

 Electrical Specifications — W**A and W**L Series

Summary of Contents for W48A23

Page 1: ...INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W48A23 W48L23 W60A23 W60L23 Manual 2100 594 Supersedes NEW File Volume III Tab 16 Date 04 23 13 Bard Manufacturing Company Inc Bryan Ohio 4350...

Page 2: ...e 8 Electric Heat 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Condensate Drain 5 Filters 5 In...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...ting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any wa...

Page 5: ...ls Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Page 6: ...lly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 3 Locate and mark l...

Page 7: ...iew Ventilation Air Supply Air Opening Bracket Installation Return Air Opening Electric Heat Electrical Drain Built In Slope Top 2 Pitch Panel Built In Heater Access Circuit Breaker Disconnect Access...

Page 8: ...Opening Supply Left Side View Installation Air Opening Return Heat Electric Top 2 Pitch Built In Slope Bracket Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Entrances...

Page 9: ...HING FOUR SIDES OF SUPPLY REQUIRED DIMENSIONS TO MAINTAIN IT IS RECOMMENDED THAT A BEAD OF TOP FLASHING AT TIME OF INSTALLATION COMBUSTIBLE MATERIALS THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR OPE...

Page 10: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Page 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Page 16: ...manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardle...

Page 17: ...is unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The...

Page 18: ...s are in a raceway Top outlet supply option is available only factory installed and only on the selected models IMPORTANT While this electrical data is presented as a guide it is important to electric...

Page 19: ...W48A23 W48L23 ARE NOT APPROVED FOR USE WITH ELECTRIC HEAT W60A23 W48A23 Part Number Description CMC 15 Start Kit X X WMCB 09A WMCB 08A Circuit Breaker Kit Circuit Breaker Kit X X Model W60A23 240V 1 2...

Reviews: