background image

Manual 2100-594 

Page  16 of 19

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling 

in compressor contactor, starting the compressor and 
outdoor motor.  (See 

NOTE

 under Condenser Fan 

Operation if equipped with Low Ambient Control.)  The 
G (indoor motor) circuit is automatically completed 
by the thermostat on any call for cooling operation or 
can be energized by manual fan switch on subbase for 
constant air circulation.  On a call for heating, circuit 
R-W1 make at the thermostat pulling in heat contactor 
for the strip heat and blower operation.  On a call for 
second stage heat, R-W2 makes bringing on second heat 
contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all 
models covered by this manual.  The compressor 
control module is an anti-short cycle/lockout timer with 
high and low pressure switch monitoring and alarm 
relay output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to 
the unit, the 

delay on make

 period begins, which will 

be 2 minutes plus 10% of the 

delay on break

 setting.  

When the delay on make is complete and the high 
pressure switch and low pressure switch is closed, the 
compressor contactor is energized.  Upon shutdown, the 
delay on break timer starts and prevents restart until the 
delay on break and delay on make periods have expired.  

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay on  
break time has expired.  If the high pressure switch 
opens again in this same operating cycle, the unit will 
go into 

manual lockout

 condition and the alarm relay 

circuit will energize.  Recycling the wall thermostat 
resets the manual lockout. 

Low Pressure Switch, Bypass, and Lockout 

Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize 
and go into a soft lockout.  Regardless the state of the 
low pressure switch, the contactor will reenergize after 
the delay on make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is 
powered whenever the compressor is locked out due to 
HPC or LPC sequences as described.

NOTE:  Both high and low pressure switch controls are 

inherently automatic reset devices.  The high 
pressure switch and low pressure switch cut 

out and cut in settings are fixed by specific air 

conditioner unit model.  The lockout features, 
both soft and manual, are a function of the 
Compressor Control Module. 

ADJUSTMENTS
Adjustable Delay on Make and Delay on Break 

Timer

The potentiometer is used to select Delay on Break time 
from 30 seconds to 5 minutes.  Delay on Make (DOM) 
timing on power-up and after power interruptions is 
equal to 2 minutes plus 10% of Delay on Break (DOB) 
setting:

  0.5 minute  (30 seconds)  DOB = 123  second DOM
  1.0 minute  (60 seconds)  DOB = 126  second DOM
  2.0 minute  (120 seconds)  DOB = 132  second DOM
  3.0 minute  (180 seconds)  DOB = 138  second DOM
  4.0 minute  (240 seconds)  DOB = 144  second DOM
  5.0 minute  (300 seconds)  DOB =  150  second DOM

During routine operation of the unit with no power 
interruptions the compressor will operate on demand 
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on 
all units so that the system operating pressures can be 
observed.  A pressure table can be found later in the 
manual covering all models.  It is imperative to match 
the correct pressure table to the unit by model number.  
See Table 5.

Summary of Contents for W48A23

Page 1: ...INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W48A23 W48L23 W60A23 W60L23 Manual 2100 594 Supersedes NEW File Volume III Tab 16 Date 04 23 13 Bard Manufacturing Company Inc Bryan Ohio 4350...

Page 2: ...e 8 Electric Heat 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Condensate Drain 5 Filters 5 In...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...ting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any wa...

Page 5: ...ls Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Page 6: ...lly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 3 Locate and mark l...

Page 7: ...iew Ventilation Air Supply Air Opening Bracket Installation Return Air Opening Electric Heat Electrical Drain Built In Slope Top 2 Pitch Panel Built In Heater Access Circuit Breaker Disconnect Access...

Page 8: ...Opening Supply Left Side View Installation Air Opening Return Heat Electric Top 2 Pitch Built In Slope Bracket Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Entrances...

Page 9: ...HING FOUR SIDES OF SUPPLY REQUIRED DIMENSIONS TO MAINTAIN IT IS RECOMMENDED THAT A BEAD OF TOP FLASHING AT TIME OF INSTALLATION COMBUSTIBLE MATERIALS THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR OPE...

Page 10: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Page 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Page 16: ...manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardle...

Page 17: ...is unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The...

Page 18: ...s are in a raceway Top outlet supply option is available only factory installed and only on the selected models IMPORTANT While this electrical data is presented as a guide it is important to electric...

Page 19: ...W48A23 W48L23 ARE NOT APPROVED FOR USE WITH ELECTRIC HEAT W60A23 W48A23 Part Number Description CMC 15 Start Kit X X WMCB 09A WMCB 08A Circuit Breaker Kit Circuit Breaker Kit X X Model W60A23 240V 1 2...

Reviews: