Manual 2100-711F
Page
40 of 45
TABLE 16
Indoor Blower Performance
E.S.P.
1
(In. H
2
O)
Balanced Climate
TM
Speed
Default LO Cooling &
Heating/Ventilation
Speed
2
Optional MED
Cooling & Heating
Speed
Optional HI Cooling
& Heating Speed
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
W42HC
0.00
1205
1065
1575
1460
1745
1640
1815
1690
0.10
1050
955
1485
1400
1665
1560
1740
1630
0.15
980
900
1440
1360
1625
1520
1705
1600
0.20
915
845
1400
1325
1585
1485
1665
1570
0.25
1360
1280
1550
1450
1630
1535
0.30
1315
1235
1510
1415
1590
1500
0.40
1240
1140
1435
1345
1515
1430
.050
1165
1030
1360
1275
1435
1355
W48HC
0.00
1320
1270
1745
1665
1895
1800
1985
1860
0.10
1225
1160
1700
1615
1850
1760
1915
1810
0.15
1180
1110
1675
1585
1825
1735
1880
1780
0.20
1130
1060
1650
1555
1795
1705
1845
1755
0.25
1615
1520
1765
1675
1815
1720
0.30
1580
1480
1735
1640
1780
1690
0.40
1500
1400
1665
1565
1715
1620
.050
1410
1305
1595
1480
1655
1545
W60HC
0.00
1485
1490
1985
1890
2075
2005
2165
2030
0.10
1430
1365
1920
1830
2015
1950
2085
1985
0.15
1400
1305
1890
1800
1985
1920
2050
1960
0.20
1360
1250
1855
1765
1955
1885
2015
1935
0.25
1820
1730
1920
1855
1985
1910
0.30
1785
1690
1890
1820
1955
1880
0.40
1715
1605
1825
1750
1900
1820
.050
1645
1515
1755
1675
1855
1750
1
E.S.P. is the total combined external static pressure of both the supply and return ducts or grills.
2
This is the speed set at the factory.