TABLE 13
Electrical Specifications − W**HC Series
Model
Rated Volts &
Phase
No.
Field
Power
Circuits
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
W42HC-A00, A0Z
A04
A05
A10
A15
230/208-1
1
1
1
1 or 2
1 or 2
32
53
58
84
84
45
60
60
90
90
8
6
6
4
4
10
10
10
8
8
32
58
52
26
50
60
60
45
8
6
6
8
10
10
10
10
W42HC-B00, B0Z
B05
B09
B15
230/208-3
1
1
1
1
24
39
51
51
35
45
60
60
8
8
6
6
10
10
10
10
W42HC-C00, C0Z
C05
C09
C15
460-3
1
1
1
1
12
21
25
26
15
25
30
30
14
10
10
10
14
10
10
10
W48HC-A00, A0Z
A04
A05
A10
A15
A20
230/208-1
1
1
1 or 2
1 or 2
1 or 2
1 or 2
35
56
61
87
87
110
50
60
70
90
90
125
8
6
6
3
3
2
10
10
8
8
8
6
35
35
35
58
26
52
52
52
40
50
50
60
30
60
60
60
8
8
8
6
10
6
6
6
10
10
10
10
10
10
10
10
W48HC-B00, B0Z
B05
B09
B15
B18
230/208-3
1
1
1
1
2
25
40
52
53
N/A
35
50
60
60
N/A
8
8
6
6
N/A
10
10
10
10
N/A
52
28
60
30
6
10
10
10
W48HC-C00, C0Z
C05
C09
C15
460-3
1
1
1
1
12
20
25
26
15
25
30
30
14
10
10
10
14
10
10
10
W60HC-A00, A0Z
A05
A10
A15
A20
230/208-1
1
1 or 2
1 or 2
1 or 2
1 or 2
42
67
93
93
112
60
80
100
100
125
8
4
3
3
2
10
8
8
8
6
41
41
41
60
26
52
52
52
50
50
60
60
30
60
60
60
8
8
8
6
10
6
6
6
10
10
10
10
10
10
10
10
W60HC-B00, B0Z
B09
B15
B18
230/208-3
1
1
1
2
29
56
56
N/A
40
60
60
N/A
8
6
6
N/A
10
10
10
N/A
55
28
60
30
6
10
10
10
W60HC-C00, C0Z
C09
C15
460-3
1
1
1
14
28
28
20
30
30
12
10
10
12
10
10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version),
Article 310 for power conductor sizing.
CAUTION
: When more than one field power circuit is run through one conduit, the conductors must
be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying
conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.
NOTE:
The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-circuit
conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit breaker) in this
model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum calculated value or
Minimum Circuit Ampacity (MCA) listed.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in
accordance with the National Electrical Code and all local codes.