TABLE 5

Recommended Airflow

TABLE 6

Indoor Blower Performance

TABLE 7

Maximum ESP of Operation 

Electric Heat Only

Values shown are for units equipped with standard 1" throwaway filter or 1" washable filter.
Derate ESP by .15 for 2" pleated filters.

Model

Nominal 

Rated 

CFM  *

Nominal 

Rated 

ESP  *

Recommended 

Airflow Range

Factory Speed 

Connection

W17A, W17L

600

.40

550 - 725

Low

W18A, W18L

550

.45

550 - 725

Low

W24A, W24L

800

.30

700 - 950

Single

W30A, W30L

1000

.30

850 - 1300

High

W36A, W36L

1100

.20

930 - 1350

High

W42A, W42L

1400

.45

1600 - 1150

High

W48A, W48L

1550

.30

1750 - 1285

High

W60A, W60L

1700

.40

1950 - 1375

High

W70A, W70L

1700

.20

1950 - 1375

High

Speed

W17/18

W24

W30

W36

W42/48

W60

W70

High

Low

Single

High

Low

High

Low

High

Low

High

Low

High

Low

ESP

(Inch 

H20)

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

Dry 

Coil

Wet 
Coil

0.0

1045 1025 760

745

990

970 1370 1285 910

885 1415 1275 955

925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400

0.1

1010 970

730

715

945

925 1305 1225 885

860 1350 1215 945

915 1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425 1340

0.2

940

905

700

685

890

870 1225 1135 850

815 1265 1125 925

900 1685 1640 1460 1415 1925 1865 1395 1355 1905 1700 1375 1295

0.3

860

830

670

655

820

800 1115 1020 790

755 1190 1060 875

850 1590 1550 1390 1345 1870 1815 1340 1300 1830 1645 1225 1150

0.4

780

750

610

595

735

720 1005 910

695

660 1085 975

780

755 1495 1460 1310 1270 1755 1705 1225 1185 1725 1550 1140 1070

0.5

665

640

485

455

605

590

865

775

590

560

970

865

640

615 1400 1365 1225 1185 1660 1610 1125 1085 1500 1350 1050 985

Model

W17A/L,

W18A/L, 

W24A/L

W30A/L, W36A/L

W42A/L, W48A/L

W60A/L, W70A/L

Outlet

FRONT

FRONT

TOP

FRONT

FRONT

Speed

Single

High

Low

High

Low

High

Low

High

Low

-A0Z
-A04
-A05
-A08
-A10
-A15
-A20

.50

.50
.50

.50

.50
.50
.50
.40

.50

.50
.50
.45
.35

.50
.50

.50

.50
.45

.35

.50

.50

.50
.50
.50

.50

.50

.50
.50
.45

.50

.50

.50
.50
.50

.50

.50

.50
.50
.40

-B0Z
-B06
-B09
-B15
-B18

.50
.50

.50
.50
.50
.45

.50
.40
.50
.30

.50

.45

.50

.40

.50

.50
.50
.50

.50

.50
.50
.50

.50

.50
.50
.50

.50

.50
.50
.50

-C0Z
-C06
-C09
-C15

.50
.50
.50
.45

.50
.50
.40
.35

.50

.45

.50

.40

.50

.50
.50

.50

.50
.50

.50

.50
.50

.50

.50
.50

* Rated CFM and ESP on factory speed connection.

Summary of Contents for W17A2-A

Page 1: ... bardhvac com Manual 2100 581D Supersedes 2100 581C Date 7 21 16 W17L2 A W18L2 A W24L2 A W24L2 B W24L2 F W30L2 A W30L2 B W30L2 C W36L2 A W36L2 B W36L2 C W36L2 F W42L2 A W42L2 B W42L2 C W42L2 F W48L2 A W48L2 B W48L2 C W48L2 F W60L2 A W60L2 B W60L2 C W60L2 F W70L2 A W70L2 B W70L2 C W70L2 F W48A2 A W48A2 B W48A2 C W48A2 E W48A2 F W60A2 A W60A2 B W60A2 C W60A2 E W60A2 F W70A2 A W70A2 B W70A2 C W70A2 F...

Page 2: ... 8 Electric Heat 23 Table 9A Optional Accessories Right Hand 24 Table 9B Optional Accessories Left Hand 25 Table 10 Vent and Control Options 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Air Conditioner Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation 6 Wall Mounting Information 6...

Page 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone ...

Page 4: ...guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in acc...

Page 5: ...ugh RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 throwaway filte...

Page 6: ...HE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not required 2 The unit itself is suitable for 0 clearance but the supply air duct flange and the first 3 of supply air duct require a minimum of 1 4 clearance to combustible m...

Page 7: ...nce Electrical Built In Ventilation Air models Electrical 4 Pitch Filter Access Panel Top Rain Low Voltage Electrical Entrance Standard flush vent door for Access Panel Lockable non ERV Econ Disconnect Electric Heat Front View C Breaker Built In Rain Hood Hood for ECONWMT MIS 3124 B Hood used on ERV and ECONWMS only 11 3 7 88 1 00 11 31 88 Filter Access Panel Air Outlet Front View Condenser Standa...

Page 8: ...NG AT TIME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF W A UNIT SHOWN W L UNIT SUPPLY AIR SU...

Page 9: ...OTES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS DUCT RETURN AIR Right Side View SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location View Return Opening 16 7 8 4 7 16 4 5 8 9 7 8 29 7 8 17 5 8 3 11 16 5 3 8 8 ...

Page 10: ...6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply...

Page 11: ...pply air duct and combustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE 1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SU...

Page 12: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME P...

Page 13: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Page 14: ...ker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bot...

Page 15: ...tiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of...

Page 16: ...ase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse t...

Page 17: ...sets the manual lockout Alarm Relay Output Alarm terminal is output connection for applications where alarm relay is employed This terminal is powered whenever the compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure switch cut out and cut in settings are fi...

Page 18: ...rge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine 9 screws holding fan shroud to condenser and bottom 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service motor fan as needed 7 Reverse steps to reinstall A AIRFLOW MIS 172...

Page 19: ...56 135 483 137 509 137 536 139 565 80 67 Low Side High Side 130 344 133 367 136 391 138 416 140 442 142 468 144 495 146 522 147 550 149 579 85 72 Low Side High Side 135 356 138 380 141 405 143 431 145 457 147 484 149 512 151 540 152 569 154 599 W36A L 75 62 Low Side High Side 120 339 122 366 124 392 126 418 129 446 130 473 132 501 134 529 135 558 136 586 80 67 Low Side High Side 128 348 130 375 13...

Page 20: ... 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30A2 C00 C0Z C06 C09 C15 460 3 1 1 1 1 11 12 17 26 15 15 20 30 14 14 12 10 14 14 12 10 W36A2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 29 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W36A2 B00 ...

Page 21: ... 30 30 50 60 10 10 8 6 10 10 10 10 W24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 W24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30L2 B00 B0Z B09 B15 230 208 3 1 1 1 18 33 51 20 35 60 12 8 6 12 10 10 W30L2 C00 C0Z C09 C15 460 3 1 1 1 11 17 26 15 20 30 14...

Page 22: ... 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425 1340 0 2 940 905 700 685 890 870 1225 1135 850 815 1265 1125 925 900 1685 1640 1460 1415 1925 1865 1395 1355 1905 1700 1375 1295 0 3 860 830 670 655 820 800 1115 1020 790 755 1190 1060 875 850 ...

Page 23: ... Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 14 4 40950 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 5 46100 20 83 2 68260 72 1 51200 ...

Page 24: ...A10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15 X X X X EHWA05 A20 X X X X EHWA05 B09 X X EHWA05 B15 X X X X EHW05A B18 X EHWA05 B18 X X EHWA05A C09 X X X X EHWA05A C15 X X X X EHWA60 A05 X X EHW60A B09 X EHW70A B09 X EHW70A B18 X WMCB 01B X WMCB 02A X WMCB 02...

Page 25: ...EHWA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X EHWA05 B15L X X X X EHWA05A C09L X X X X EHWA05A C15L X X X X EHWA60 A05L X EHWA60 B09L X EHW70A B09L X WMCB 01B X WMCB 02A X WMCB 02B X WMCB 03A X WMCB 04B X WMCB 05A X X WMCB 05B X X WMCB 06B X WMCB...

Page 26: ...ir Damper Standard X BOP 3 Blank Off Plate X MFAD 3 Motorized Fresh Air Damper X CRVS 3 Commercial Ventilator Spring Return X CRVP 3 Commercial Ventilator Power Return X ECONWMS E3 ECONWMT E3 ECONWMT T3 Economizer School Version Enthalpy Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X X ERVF A3 Energy Recovery Ventilator 230 Volt X ERVF C3 Energy Recovery Ventilator 460 Vo...

Reviews: