background image

Manual 2100-509E 

Page 

6 of 17

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked 
for external signs of shipping damage.  If damage is 
found, the receiving party must contact the last carrier 
immediately, preferably in writing, requesting inspection 
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed 
by trained, experienced service and installation 
technicians.

The refrigerant system is completely assembled and 
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.  
Flanges are provided for attaching the supply and return 
air ducts.

These instructions explain the recommended method to 
install the air cooled self-contained unit and the electrical 
wiring connections to the unit.

These instructions and any instructions packaged with 
any separate equipment required to make up the entire 
air conditioning system should be carefully read before 
beginning the installation.  Note particularly “Starting 
Procedure” and any tags and/or labels attached to the 
equipment.

While these instructions are intended as a general 
recommended guide, they do not supersede any national 
and/or local codes in any way.  Authorities having 
jurisdiction should be consulted before the installation 
is made.  See Page 3 for information on codes and 
standards.

Size of unit for a proposed installation should be based 
on heat loss/gain calculation made according to methods 
of Air Conditioning Contractors of America (ACCA).  
The air duct should be installed in accordance with the 
Standards of the National Fire Protection Association 
for the Installation of Air Conditioning and Ventilating 
Systems of Other Than Residence Type, NFPA No. 
90A, and Residence Type Warm Air Heating and Air 
Conditioning Systems, NFPA No. 90B.  Where local 
regulations are at a variance with instructions, installer 
should adhere to local codes.

j

  Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

 

Based on 75°C copper wire.  All wiring must conform to NEC and all local codes.

 

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National  

  

Electrical Code (latest revision), article 310 for power conductor sizing.

CAUTION:

  When more than one field power conductor circuit is run through one conduit, the conductors must be 

derated.  Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 

conductors are in a raceway.

TABLE  2

ELECTRICAL HEAT SPECIFICATIONS

SINGLE CIRCUIT

Models

Rated Volts 

and  

Phase

No. Field 

Power 

Circuits

Minimum 

Circuit 

Ampacity

j

Maximum 

External Fuse 

or Circuit 

Breaker

Field Power 

Wire Size

Ground  

Wire Size

W12A2-A00

A03

A05

230/208-1

1

1

1

9

20

28

15

20

30

14

12

10

14

12

10

W12A1-K00

K02

115-1

1

1

20

29

30

30

10

10

10

10

Summary of Contents for W12A2-A

Page 1: ...TED PACKAGE AIR CONDITIONERS Model W12A2 A W12A1 K INSTALLATION INSTRUCTIONS Manual 2100 509E Supersedes 2100 509D File Volume III Tab 16 Date 08 20 12 Bard Manufacturing Company Inc Bryan Ohio 43506...

Page 2: ...4 Adjustments 15 Pressure Service Ports 15 Troubleshooting Fan Blade Setting Dimension 16 Refrigerant Charge 16 Pressure Table 17 Optional Field Installed Accessories 17 Figures Figure 1 Unit Dimensio...

Page 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Page 4: ...MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VOLTS PHASE A 230 208 60 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW VENTILATION OPTIONS X Barometric Fresh...

Page 5: ...osition is Blow Thru Condenser Airflow Flanges Built In Side Wall Mounting Shipping Location Top Rain Flashing field convertible position Optional Electrical Position of return air flanges are interch...

Page 6: ...tandards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be install...

Page 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Page 8: ...cations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wi...

Page 9: ...Manual 2100 509E Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...Manual 2100 509E Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 11: ...Manual 2100 509E Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 12: ...ta lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits required for the various models with heaters The...

Page 13: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 14: ...on make is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart...

Page 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Page 16: ...the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance...

Page 17: ...6 379 138 405 141 432 142 460 143 490 80 deg DB 67 deg WB Low Side High Side 128 298 133 318 138 340 142 364 143 387 148 415 151 443 152 472 153 503 85 deg DB 72 deg WB Low Side High Side 132 308 138...

Reviews: