TABLE 5A
Cooling Pressures
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring.
See “Condenser Fan Operation”.
Air Temperature Entering Outdoor Coil °F
TABLE 5B
Heating Pressures (All Temperatures °F)
Model
Return Air
Temperature
Pressure
75
80
85
90
95
100
105
110
115
120
T30S
75 deg. DB
62 deg. WB
Low SIde
High Side
124
319
127
333
130
350
133
370
135
392
137
416
137
443
138
473
139
505
140
540
80 deg. DB
67 deg. WB
Low SIde
High Side
133
327
136
342
139
359
142
379
144
402
146
427
147
454
148
485
149
518
150
554
85 deg. DB
72 deg. WB
Low SIde
High Side
138
338
141
354
144
372
147
392
149
416
151
442
152
470
153
502
154
536
155
573
Model
Return Air
Temperature
Pressure
0
5
10
15
20
25
30
35
40
45
50
55
60
65
T30S
70 Deg.
Low Side
High Side
44
286
49
289
53
293
59
299
65
306
71
314
78
323
86
333
94
344
103
357
113
371
123
386
133
402
145
419