Bard T30S1 Installation Instructions Manual Download Page 18

Manual 2100-547D 

Page  18 of 26

TROUBLESHOOTING

TABLE  3   TROUBLESHOOTING

Sympton

Description, Check & Possible Cause

What & How to Check/Repair

Compressor will 

not start (heating or 

cooling)

1. Check for LED illumination.

Is there an LED illuminated on the board 

(flashing)?

Yes = go to Step #2; No = go to Step #3

2. Check for error codes.

Is the LED flashing a code?

Yes = go to Step #4; No = go to Step #8

3. Check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4. Check codes.

What code is blinking?

Code "1", got to Step #6; Code "2", go to Step #7; Fast Blink, go to Step #5

5. Compressor delay active.

Wait for 5 minute delay or jump board's 

"speed up pins".

Check for proper operation; if still needed, go back to Step #1

6. Low pressure fault.

Check wiring circuit and unit pressures.

7. High pressure fault.

Check wiring circuit and unit pressures.

8. Check for Compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9. No power to board.

The unit either does not have unit voltage, the transformer is bad or the unit wiring 

is incorrect.

10. Check for Compressor output signal.

Is there 24 volts AC between CC and C?

Yes = go to Step #12; No = go to Step #13

11. No "Y" compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor) 

and finally unit wiring.

12. No "CC" compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13. Faulty board.

Replace defrost board.

Fan outdoor 

motor does not run 

(cooling or heating 

except during 

defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)

Replace heat pump control.

Motor defective

Check for open or shorted motor winding. Replace motor.

Motor capacitor defective

Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.

Reversing valve 

does not energize 

(heating only)

Heat pump control defective

Check for 24 V between RV-C and B-C.

1. Check circuit control wiring.

2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.

Replace solenoid coil.

Unit will not go into 

defrost (heating 

only)

Temperature sensor or heat pump control 

defective

Disconnect temperature sensor from board and jumper across "SPEEDUP" 

terminals and "SEN JMP" terminals. This should cause the unit to go through a 

defrost cycle within one minute.

1. If unit goes through defrost cycle, replace temperature sensor.

2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not come 

out of defrost 

(heating only)

Temperature sensor or heat pump control 

defective

Jumper across "SPEEDUP" terminal. This should cause the unit to come out of 

defrost within one minute.

1. If unit goes through defrost cycle, replace temperature sensor.

2. If unit does not go through defrost cycle, replace heat pump control.

SOLID STATE HEAT PUMP CONTROL 

TROUBLESHOOTING PROCEDURE

 1. 

NOTE:

 

A thorough understanding of the defrost  

    cycle sequence is essential.  Review that section  

    earlier in this manual prior to troubleshooting the  

    control.  

Turn on AC power supply to unit.

  2.  Turn thermostat blower switch to “fan on” – the  

    indoor blower should start.  (If it doesn’t,  

 

    troubleshoot indoor unit and correct problem.)
  3.  Turn thermostat blower to “auto” position.  Indoor  

    blower should stop.  

NOTE:

 

Many models have a  

    1-minute blower time delay on “off” command;  

    wait for this to time-out.

  4.  Set system switch to “heat” or “cool”.  Adjust    

    thermostat to call for heat or cool.  The indoor    

    blower, compressor  and outdoor fan should start.

NOTE:  If there was no power to 24 volt transformer,    

 

the compressor and outdoor fan motor will    

 

not start for 5 minutes.  This is because of  

 

 

the compressor short cycle protection. 

LED BLINK CODES

  BLINK 

FUNCTION

  Slow 

Normal function (1.0 sec on/1.0 sec off)

  Fast 

ASCD timer active (0.1 sec on/0.1 sec off)

  1 

Low pressure switch failure

  2 

High pressure switch failure/“Soft” Lockout

  3 

Defrost mode active

  4 

High pressure switch failure/“Hard” Lockout

Summary of Contents for T30S1

Page 1: ... HEAT PUMPS Standard Dehumidification MODELS T30S1 T30S1D T36S1 T36S1D T42S1 T42S1D T48S1 T48S1D T60S1 T60S1D Manual 2100 547D Supersedes 2100 547C File Tab 17 Date 08 13 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Page 2: ...ctrical Specifications T S Dehum 23 Table 7 Indoor Blower Performance 24 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions Wall Mounting Information 6 Mounting the Unit 6 Placement 6 Clearances Required 6 Minimum Clearances 6 Wi...

Page 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 T...

Page 4: ...r Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a variance with instructions inst...

Page 5: ...ct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 inch throwaway filter is standard with each unit The filter slides into po...

Page 6: ... wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips and to allow proper airflow to the outdoor coil Additional clearance may be required to meet local or national codes 2 Care should be taken to ensure that the recirculation and...

Page 7: ... location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The brackets are secured to the unit base with two 2 screws and secured to the isolation plate with a 1 4 nut Remove and dispose of the two 2 screws and brackets Re install the 1 4 nut once bracket is removed Mo...

Page 8: ...EARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL STRUCTURE TOP MIS 311 C Wall Opening and Hole Location View Right Side View WALL HEATER ACCESS SEAL WITH ...

Page 9: ...LY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Opening FOAM AIR SEAL SUPPLIED SEAL WITH BEAD OF CAULKING A...

Page 10: ...s This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Page 11: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Page 12: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Page 13: ... left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups See Tables 6A 6B for Electrical Specifications WIRING LOW VOLTAGE WIRING 230 208V 1 phas...

Page 14: ...ltiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out o...

Page 15: ...r However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting prope...

Page 16: ... heat pump defrost control board has an option of 30 60 or 90 minute setting By default this unit is shipped from the factory with the defrost time on the 60 minute pin If circumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refer to Figure 8 There is a cycle speed up jumper on the control This can be used for testing purp...

Page 17: ... 26 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIGURE 8 DEFROST CONTROL BOARD ...

Page 18: ...ly Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP...

Page 19: ...9 16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102 0 5570 11 0 122089 27 0 37652 65 0 13474 103 0 5446 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 50...

Page 20: ...y testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge th...

Page 21: ...34 80 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151 459 153 485 154 511 156 539 159 567 T48S 75 deg DB 62 deg WB Low SIde High Side 137 326 138 339 139 356 140 375 141 398 143 423 144 450 146 482 148 515 150 551 80 deg DB 67 deg WB Low SIde High S...

Page 22: ... 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1 B00 B0Z B09 B15 B18 230 2...

Page 23: ...10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1DA00 A0Z DA05 DA10 DA15 DA20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 ...

Page 24: ...hown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires wiring modification consult Installation Instructions Wiring Diagram CFM output on Cooling or Electric Heat Model Rated ESP Max ESP Blower Only Cooling Heating 1st Stage Cooling Heating 2nd Stage Ele...

Page 25: ... it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed C...

Page 26: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly Follow the manufacturer s procedures for disposition of the old control module Figure 25 Figure 24 Figure 26 TROUBLESHOOTING GE ECM MOTORS ...

Reviews: