Bard T30S1 Installation Instructions Manual Download Page 16

Manual 2100-547D 

Page  16 of 26

SEQUENCE OF OPERATION

COOLING STAGE 1

  –  Circuit R-Y makes at thermostat 

pulling in compressor contactor, starting the compressor and 

outdoor motor.  The G (indoor motor) circuit is automatically 

completed on any call for cooling operation or can be energized 

by manual fan switch on subbase for constant air circulation.

COOLING STAGE 2

  –  Circuit R-Y1 makes at the thermostat 

energizing the 2nd stage solenoid in the compressor.  Default 

position is not energized.  Compressor will run at low capacity 

until this solenoid is energized.

HEATING STAGE 1

  – A 24V solenoid coil on reversing 

valve controls heating cycle operation.  Two thermostat options, 

one allowing “Auto” changeover from cycle to cycle and 

the other constantly energizing solenoid coil during heating 

season and thus eliminating pressure equalization noise except 

during defrost, are to be used.  On “Auto” option a circuit is 

completed from R-B and  R-Y on each heating “on” cycle, 

energizing reversing valve solenoid and pulling in compressor 

contactor starting compressor and outdoor motor.  R-G also 

make starting indoor blower motor.  Heat pump heating cycle 

now in operation.  The second option has no “Auto” changeover 

position, but instead energizes the reversing valve solenoid 

constantly whenever the system switch on subbase is placed in 

“Heat” position, the “B” terminal being constantly energized 

from R.  A thermostat demand for Stage 1 heat completes R-Y 

circuit, pulling in compressor contactor starting compressor and 

outdoor motor.  R-G also make starting indoor blower motor.

HEATING STAGE 2

  – Circuit R-Y2 makes at the thermostat 

energizing the 2nd stage solenoid in the compressor.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units 

so that the system operating pressures can be observed.  

Pressure tables can be found later in the manual covering all 

models.  It is imperative to match the correct pressure table to 

the unit by model number.  See Tables 5A & 5B.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the 

solid state heat pump control.

When the outdoor temperature is in the lower 40°F temperature 

range or colder, the outdoor coil temperature is 32°F or below.  

This coil temperature is sensed by the coil temperature sensor 

mounted near the bottom of the outdoor coil.  Once coil 

temperature reaches 30°F or below, the coil temperature sensor 

sends a signal to the control logic of the heat pump control and 

the defrost timer will start accumulating run time.

After 30, 60 or 90 minutes of heat pump operation at 30°F or below, 

the heat pump control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back 

to the cooling cycle, the outdoor motor stops, electric heaters 

are energized, and hot gas passing through the outdoor coil 

melts any accumulated frost.  When the temperature rises to 

approximately 57°F, the coil temperature sensor will send a 

signal to the heat pump control which will return the system to 

heating operations automatically.

If some abnormal or temporary condition such as a high wind 

causes the heat pump to have a prolonged defrost cycle, the 

heat pump control will restore the system to heating operation 

automatically after 8 minutes.

The heat pump defrost control board has an option of 30, 60 

or 90-minute setting.  By default, this unit is shipped from 

the factory with the defrost time on the 60 minute pin.  If 

circumstances require a change to another time, remove the 

wire from the 60-minute terminal and reconnect to the desired 

terminal.  Refer to Figure 8.

There is a cycle speed up jumper on the control.  This can be 

used for testing purposes to reduce the time between defrost 

cycle operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or another 

¼ inch QC, to short between the 

SPEEDUP 

terminals to 

accelerate the HPC timer and initiate defrost.

Be careful not to touch any other terminals with the instrument 

used to short the 

SPEEDUP

 terminals.  It may take up to 10 

seconds with the 

SPEEDUP

 terminals shorted for the speedup 

to be completed and the defrost cycle to start.

As soon as the defrost cycle kicks in remove the shorting 

instrument from the SPEEDUP terminals. 

 Otherwise the 

timing will remain accelerated and run through the 1-minute 

minimum defrost length sequence in a matter of seconds and 

will automatically terminate the defrost sequence.

There is an initiate defrost jumper (sen jump) on the control 

that can be used at any outdoor ambient during the heating 

cycle to simulate a 0° coil temperature.

This can be used to check defrost operation of the unit without 

waiting for the outdoor ambient to fall into the defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a 

¼ inch QC terminal works best) the defrost sensor mounted 

on the outdoor coil is shunted out & will activate the timing 

circuit.  This permits the defrost cycle to be checked out in 

warmer weather conditions without the outdoor temperature 

having to fall into the defrost region. 

In order to terminate the defrost test the 

SEN JMP

 jumper must 

be removed.  If left in place too long, the compressor could 

stop due to the high pressure control opening because of  high 

pressure condition created by operating in the cooling mode 

with outdoor fan off.   Pressure will rise fairly fast as there is 

likely no actual frost on the outdoor coil in this artificial test 

condition.

There is also a 5-minute compressor time delay function built into 

the HPC.  This is to protect the compressor from short cycling 

conditions.  The board’s LED will have a fast blink rate when in 

the compressor time delay.  In some instances, it is helpful to the 

service technician to override or speed up this timing period, and 

shorting out the 

SPEEDUP

 terminals for a few seconds can do this.

Low Pressure Switch Bypass Operation

 - The control has a 

selectable (SW1) low pressure switch bypass set up to ignore 

the low pressure switch input during the first (30, 60, 120 or 180 

seconds) of “Y” operation.

After this period expires, the control will then monitor the low 

pressure switch input normally to make sure that the switch is 

closed during “Y” operation.

High Pressure Switch Operation

 - The control has a built-in lockout 

system that allows the unit to have the high pressure switch trip up 

to two times in one hour and only encounter a “soft” lockout.  A 

“soft” lockout shuts the compressor off and waits for the pressure 

switch to reset, which at that point then allows the compressor to 

be restarted as long as the 5-minute short cycle timer has run out.  

If the high pressure switch trips a third time within one hour, the 

unit is in “hard” lockout indicating something is certainly wrong 

and it will not restart itself.

Summary of Contents for T30S1

Page 1: ... HEAT PUMPS Standard Dehumidification MODELS T30S1 T30S1D T36S1 T36S1D T42S1 T42S1D T48S1 T48S1D T60S1 T60S1D Manual 2100 547D Supersedes 2100 547C File Tab 17 Date 08 13 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Page 2: ...ctrical Specifications T S Dehum 23 Table 7 Indoor Blower Performance 24 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions Wall Mounting Information 6 Mounting the Unit 6 Placement 6 Clearances Required 6 Minimum Clearances 6 Wi...

Page 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 T...

Page 4: ...r Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a variance with instructions inst...

Page 5: ...ct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 inch throwaway filter is standard with each unit The filter slides into po...

Page 6: ... wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips and to allow proper airflow to the outdoor coil Additional clearance may be required to meet local or national codes 2 Care should be taken to ensure that the recirculation and...

Page 7: ... location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The brackets are secured to the unit base with two 2 screws and secured to the isolation plate with a 1 4 nut Remove and dispose of the two 2 screws and brackets Re install the 1 4 nut once bracket is removed Mo...

Page 8: ...EARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL STRUCTURE TOP MIS 311 C Wall Opening and Hole Location View Right Side View WALL HEATER ACCESS SEAL WITH ...

Page 9: ...LY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Opening FOAM AIR SEAL SUPPLIED SEAL WITH BEAD OF CAULKING A...

Page 10: ...s This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Page 11: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Page 12: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Page 13: ... left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups See Tables 6A 6B for Electrical Specifications WIRING LOW VOLTAGE WIRING 230 208V 1 phas...

Page 14: ...ltiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out o...

Page 15: ...r However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting prope...

Page 16: ... heat pump defrost control board has an option of 30 60 or 90 minute setting By default this unit is shipped from the factory with the defrost time on the 60 minute pin If circumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refer to Figure 8 There is a cycle speed up jumper on the control This can be used for testing purp...

Page 17: ... 26 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIGURE 8 DEFROST CONTROL BOARD ...

Page 18: ...ly Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP...

Page 19: ...9 16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102 0 5570 11 0 122089 27 0 37652 65 0 13474 103 0 5446 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 50...

Page 20: ...y testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge th...

Page 21: ...34 80 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151 459 153 485 154 511 156 539 159 567 T48S 75 deg DB 62 deg WB Low SIde High Side 137 326 138 339 139 356 140 375 141 398 143 423 144 450 146 482 148 515 150 551 80 deg DB 67 deg WB Low SIde High S...

Page 22: ... 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1 B00 B0Z B09 B15 B18 230 2...

Page 23: ...10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1DA00 A0Z DA05 DA10 DA15 DA20 230 208 60 1 1 1 or 2 1 or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 ...

Page 24: ...hown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires wiring modification consult Installation Instructions Wiring Diagram CFM output on Cooling or Electric Heat Model Rated ESP Max ESP Blower Only Cooling Heating 1st Stage Cooling Heating 2nd Stage Ele...

Page 25: ... it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed C...

Page 26: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly Follow the manufacturer s procedures for disposition of the old control module Figure 25 Figure 24 Figure 26 TROUBLESHOOTING GE ECM MOTORS ...

Reviews: