INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.  Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 3.

2.  On wood frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

MOUNTING THE UNIT

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

2.  The unit itself is suitable for 0" clearance, but the 

supply air duct flange and the first 3' of supply 
air duct require a minimum of 1/4" clearance to 
combustible material.  However, it is generally 
recommended that a 1" clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material.  See Figure 3 
for details on opening sizes.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location.  See Figures 3A and 
3B.

4.  Mount bottom mounting bracket.

5.  Hook top rain flashing, attached to front-right of 

supply flange for shipping, under back bend of top.

6.  Position unit in opening and secure with 5/16" lag 

bolts; use 7/8" diameter flat washers on the lag bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top.  See Figures 3A and 3B.

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

PLACEMENT

1.  On side-by-side installations, maintain a minimum 

of 20" clearance on right side to allow access to 
control panel and heat strips, and to allow proper 
airflow to the outdoor coil.  Additional clearance 
may be required to meet local or national codes.

2.  Care should be taken to ensure that the 

recirculation and obstruction of condenser 
discharge air does not occur.  Recirculation of 
condenser discharge air can be from either a 
single unit or multiple units.  Any object such 
as shrubbery, a building or a large object can 
cause obstructions to the condenser discharge 
air.  Recirculation or reduced airflow caused 
by obstructions will result in reduced capacity, 
possible unit pressure safety lockouts and reduced 
unit service life.

 

For units with a blow-through condenser, such as 
the T**S 11 EER units, it is recommended there 
be a minimum distance of 15' between the front of 
the unit and any barrier or 20' between the fronts 
of two opposing (facing) units.

REQUIRED STEPS AFTER FINAL 

PLACEMENT (T48S & T60S UNITS ONLY)

The compressor is secured to the unit base for 
shipping.  Although unit will perform as designed 
with the compressor secured in place, there may be 
noticeable additional noise and vibration.  To obtain 

        WARNING

Failure to provide the 1/4" clearance between 

the supply duct and a combustible surface 

for the first 3ʹ of duct can result in fire causing 

damage, injury or death.

        WARNING

Failure to bolt the unit to the wall could result 

in the unit falling, causing injury or death!  

Follow all mounting instructions.

Clearances Required for Service Access

and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

T30S

15"

20"

T36S, T42S, T48S, T60S

20"

20"

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST 3'

CABINET

T30S

1/4"

0"

T36S, T42S, T48S, T60S

Summary of Contents for T30S1-B

Page 1: ...1 B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547G Supersedes 2100 547F Date 8 3 16 T...

Page 2: ...Electrical Specifications T S Dehum 23 Table 7 Indoor Blower Performance 24 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Dama...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the Nationa...

Page 5: ...2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient si...

Page 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Page 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Page 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Page 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Page 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Page 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Page 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Page 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Page 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Page 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Page 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Page 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Reviews: