background image

Manual 2100-547G 

Page 

18 of 26

SERVICE

TABLE  3 – Troubleshooting

Sympton

Description, Check & Possible Cause

What & How to Check/Repair

Compressor will not 
start (heating or 
cooling)

1. Check for LED illumination.

Is there an LED illuminated on the board 
(flashing)?

Yes = go to Step #2; No = go to Step #3

2. Check for error codes.

Is the LED flashing a code?

Yes = go to Step #4; No = go to Step #8

3. Check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4. Check codes.

What code is blinking?

Code "1", got to Step #6; Code "2", go to Step #7; Fast Blink, go to Step #5

5. Compressor delay active.

Wait for 5 minute delay or jump board's 
"speed up pins".

Check for proper operation; if still needed, go back to Step #1

6. Low pressure fault.

Check wiring circuit and unit pressures.

7. High pressure fault.

Check wiring circuit and unit pressures.

8. Check for Compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9. No power to board.

The unit either does not have unit voltage, the transformer is bad or the unit wiring 
is incorrect.

10. Check for Compressor output signal.

Is there 24 volts AC between CC and C?

Yes = go to Step #12; No = go to Step #13

11. No "Y" compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor) 
and finally unit wiring.

12. No "CC" compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13. Faulty board.

Replace defrost board.

Fan outdoor motor 
does not run (cool-
ing or heating except 
during defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)
Replace heat pump control.

Motor defective

Check for open or shorted motor winding. Replace motor.

Motor capacitor defective

Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.

Reversing valve 
does not energize 
(heating only)

Heat pump control defective

Check for 24 V between RV-C and B-C.
1. Check circuit control wiring.
2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.
Replace solenoid coil.

Unit will not go into 
defrost (heating 
only)

Temperature sensor or heat pump control 
defective

Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals 
and "SEN JMP" terminals. This should cause the unit to go through a defrost cycle 
within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not come 
out of defrost 
(heating only)

Temperature sensor or heat pump control 
defective

Jumper across "SPEEDUP" terminal. This should cause the unit to come out of 
defrost within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.

SOLID STATE HEAT PUMP CONTROL 

TROUBLESHOOTING PROCEDURE

1. 

NOTE:

 

A thorough understanding of the defrost 

cycle sequence is essential.  Review that section 

(page 16) prior to troubleshooting the control.  

Turn on AC power supply to unit.

2.  Turn thermostat blower switch to “fan on”— 

the indoor blower should start.  (If it doesn’t, 
troubleshoot indoor unit and correct problem.)

3.  Turn thermostat blower to “auto” position.  Indoor 

blower should stop.  

NOTE:

 

Many models have a 

1-minute blower time delay on “off” command; 

wait for this to time out.

4.  Set system switch to “heat” or “cool”.  Adjust 

thermostat to call for heat or cool.  The indoor  
blower, compressor  and outdoor fan should start.

NOTE: 

If there was no power to 24 volt transformer, 

the compressor and outdoor fan motor will not 

start for 5 minutes.  This is because of the 

compressor short cycle protection.

LED BLINK CODES

BLINK

FUNCTION

Slow

Normal function (1.0 sec on/1.0 sec off)

Fast

Compressor Delay timer active  
(0.1 sec on/0.1 sec off)

1

Low pressure switch failure

2

High pressure switch failure/“Soft” Lockout

3

Defrost mode active

4

High pressure switch failure/“Hard” Lockout

Summary of Contents for T30S1-B

Page 1: ...1 B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547G Supersedes 2100 547F Date 8 3 16 T...

Page 2: ...Electrical Specifications T S Dehum 23 Table 7 Indoor Blower Performance 24 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Dama...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the Nationa...

Page 5: ...2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient si...

Page 6: ...ng upon wall construction Be sure to observe required clearance if combustible wall PLACEMENT 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to contro...

Page 7: ...ting location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base at the front and rear of the compressor The bra...

Page 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Page 9: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 10: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Page 14: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 15: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 16: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Page 17: ...ooling mode with outdoor fan off Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay...

Page 18: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 19: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 20: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Page 21: ...0 deg DB 67 deg WB Low SIde High Side 139 326 141 348 142 371 143 394 144 419 146 443 148 469 149 494 151 521 154 548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151...

Page 22: ...3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1 C0Z C06 C09 C15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10 T60S1 A00 A0Z A05 A10 A15 A20 230 208 60 1 1 1 or 2 1 or 2...

Page 23: ...0 10 10 10 10 10 T48S1DB00 B0Z DB06 DB09 DB15 230 208 60 3 1 1 1 1 28 46 55 55 40 50 60 60 8 8 6 6 10 10 10 10 T48S1DC0Z DC06 DC09 DC15 460 60 3 1 1 1 1 14 23 28 29 20 25 30 30 12 10 10 10 12 10 10 10...

Page 24: ...own is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan mode Requires...

Page 25: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 26: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Reviews: