background image

Manual 2100-420H
Page

12 of 34

FRESH AIR INTAKE

This unit is equipped with a fresh air damper assembly.
The damper blade is locked in the closed position when
the unit is shipped from the Factory.  To allow the
damper to operate remove the two plastic locking pins,
one on each end of the blade.  This will allow for
maximum fresh airflow.  The damper blade will now
open when the indoor blower is operating.  If less than
maximum fresh airflow is required, reinsert the plastic
pins to limit damper blade opening to desired level.
Two extra pins are provided (taped to the inside of the
assembly) which may be used to hold the blade in some
position other than minimum or maximum position.
This fresh air assembly is located in the rear of  the unit
and to gain access to make these adjustments remove
the air filter service door.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets are based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

For details on energy recovery ventilation see separate
section.

CONDENSATE DRAIN

There are two drain connections on the unit.  The rear
drain is the primary drain, and is located on the right
lower rear panel of the unit.  The optional side drain is
located on the bottom right side of the unit.  The side
drain is shipped with a plug installed.

The 

side drain

 requires a water trap for proper drainage.

See Figure 9.  The drain can be routed through the floor
or through the wall.  

If the drain is to be routed

through an unconditioned space, it must be protected
from freezing

 The drain line must be able to be

removed from the unit if it is necessary to remove the
unit from the wall.  When the side drain is used, the
plug must be removed and installed in the rear drain
outlet.

The 

rear drain

 can be used with wall thickness of up to

10 inches where a water trap can be installed between
the unit and the interior wall.  See Figure 10.  The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket.  The drain can
be routed through the floor or through the wall.  If the
drain is routed through the wall, the drain line must be
positioned such that it will not interfere with  the sleeve
flange or the grille.  See Figure 11.  

If the drain is to be

routed through an unconditioned space, it must be
protected from freezing

.

Optional rear drain kits, both standard and heated
versions, are available to facilitate easy installation, and
also removability of heat pump for service.  The
standard version provides a connection that allows the
evaporator condensate to drain independently bypassing
the lower drain pan.  Note that on models equipped with
a refrigerant subcooler in the lower drain pan may
experience a slight decrease in cooling performance and
efficiency.

FIGURE  10

STANDARD REAR DRAIN

FIGURE  9

OPTIONAL SIDE DRAIN (SIDE VIEW)

INSTALLATION

QT

EC

 UNIT

Summary of Contents for QTEC QH243

Page 1: ...62 QH422 QH482 QH602 QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 420H Supersedes 2100 4...

Page 2: ...2 Air Seal on Bottom of Unit 8 Figure 3 Removal of Unit From Skid 8 Figure 4 Unit on Appliance Cart for Moving 9 Figure 5 Installation With Free Blow Plenum 10 Figure 6 Ducted Application 10 Figure 7...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...0 0 1 4 0 5 1 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 QTEC Series General Information QTEC MODEL NOMENCLATURE QH 36 2 A 10 X X X X X X SPECIAL UNITS L Low Ampacity Circuit REVISION VOLTS PHA...

Page 5: ...R I C R E K A E R B 2 D L E I F R E W O P E R I W E Z I S 2 D N U O R G E R I W E Z I S 3 M U M I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A...

Page 6: ...H Q 6 0 B 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 6 2 4 4 3 5 3 5 0 4 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C 2 8 4 H Q 6 0 C 9 0 C 5 5 1 C 3 0 6 4 1 1 1 1 4 1 3 2 7 2 7 2 5 1 5 2 0 3 0 3 4 1 0 1 0 1 0...

Page 7: ...Manual 2100 420H Page 7 of 34 FIGURE 1 UNIT DIMENSIONS...

Page 8: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Page 9: ...eparate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attache...

Page 10: ...Manual 2100 420H Page 10 of 34 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Page 11: ...ither free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the fro...

Page 12: ...cated on the bottom right side of the unit The side drain is shipped with a plug installed The side drain requires a water trap for proper drainage See Figure 9 The drain can be routed through the flo...

Page 13: ...pressure device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL E...

Page 14: ...to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of ste...

Page 15: ...mplete current carrying capacity data on the various insulation grades of wiring material All wiring must conform to NEC and all local codes The electrical data lists fuse and wire sizes 75 C copper f...

Page 16: ...talled ventilation option E terminal or pin 3 of P2 is the emergency heat input This terminal energizes the emergency heat relay R O F S N O I T C E N N O C E G A T L O V W O L L O R T N O C C D D y l...

Page 17: ...t a e H e g a t s 3 l o o C e g a t s 3 c i n o r t c e l E e l b a m m a r g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0...

Page 18: ...16 REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION NOTE On option X or A the CS2000A1 or other field provided means to control ventilation must be used if any of the motorized ventilation option...

Page 19: ...4 FIGURE 17 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION NOTE On option X or A the CS2000A1 or other field provided means to control ventilation must be used if any of the motorized vent...

Page 20: ...Manual 2100 420H Page 20 of 34 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION...

Page 21: ...sor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compre...

Page 22: ...side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to remove t...

Page 23: ...t be raised up and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS BAROMETRIC FRESH AIR DAMPER Standard Before starting make sure the power has been turned off The retur...

Page 24: ...Manual 2100 420H Page 24 of 34 FIGURE 19 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 25: ...Manual 2100 420H Page 25 of 34 FIGURE 20 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 26: ...ontrol panel The lockout circuit will hold compressor off line When the system problem is corrected the unit operation can be restored by turning of the main power supply off and then back on or reset...

Page 27: ...another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP t...

Page 28: ...h t l o r t n o c p m u p t a e h e h t n o 1 L o t C d n a Y o t C m o r f t n e s e r p s i V 4 2 f I l o r t n o c p m u p t a e h e h t e c a l p e r C C t a t n e s e r p s i V 4 2 o n d n a d e...

Page 29: ...1 9 1 2 6 2 1 9 8 0 2 2 1 8 0 1 8 1 1 2 7 2 4 1 1 5 7 5 0 1 1 0 1 0 7 0 1 4 7 5 3 0 1 0 6 2 0 0 1 4 6 0 7 9 1 8 9 3 9 8 0 0 1 9 9 3 1 8 8 1 7 3 5 8 9 9 6 2 8 1 2 1 0 8 2 3 6 7 7 0 3 2 5 7 0 1 9 2 7 0...

Page 30: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 31: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Page 32: ...with a refrigerant charge resulting in a Super Heat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate L E D O M A N O I S N...

Page 33: ...B W 2 6 e d i S w o L e d i S h g i H 4 7 2 1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9...

Page 34: ...4 3 9 1 5 4 9 9 1 9 4 5 0 2 4 5 1 1 2 8 5 7 1 2 2 6 2 2 2 7 6 8 2 2 2 6 3 H Q 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9...

Reviews: