background image

Manual

2100-523

Page

39 of 41

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,
with the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer to

Figure 26.  

Remove these two bolts from the motor and control assembly

while holding the motor in a way that will prevent the motor or control
from falling when the bolts are removed.  If an ECM2.0 control is being
replaced (recognized by an aluminum casting rather that a deep-drawn
black steel can housing the electronics), remove only the hex-head bolts.

DO NOT REMOVE THE TORX-HEAD SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside
the control.  Carefully rotate the control to gain access to the plug at
the control end of the wires.  With thumb and forefinger, reach the
latch holding the plug to the control and release it by squeezing the
latch tab and the opposite side of the connector plug and gently pulling
the plug out of the connector socket in the control.  

DO NOT PULL

ON THE WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K ohms.

Refer to Figure 27.  

(Measure to unpainted motor end plate.)  If any

motor lead fails this test, do not proceed to install the control module.

THE MOTOR IS DEFECTIVE AND MUST BE REPLACED.

Installing the new control module will cause it to fail also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

  Finish installing the replacement control per

one of the three following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM

2.3 CONTROL

 (control containing black potting for water protection in

black deep-drawn steel case with no vents in the bottom of the can),
locate the two through-bolts and plastic tab that are packed with the
replacement control.  Insert the plastic tab into the slot at the perimeter
of the open end of the can so that the pin is located on the inside of the
perimeter of the can.  Rotate the can so that the tab inserts into the tab
locater hole in the endshield of the motor.  Using the two through-bolts
provided with the replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT
OF THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM

2.3 CONTROL

, the plastic tab and shorter through-bolts are not needed.

The control can be oriented in two positions 180° apart.  

MAKE SURE

THE ORIENTATION YOU SELECT FOR REPLACING THE
CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS
WILL BE LOCATED DOWNWARD IN THE APPLICATION SO
THAT WATER CANNOT RUN DOWN THE CABLES AND INTO
THE CONTROL.

  Simply orient the new control to the motor's

endshield, insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE

BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0

CONTROL 

(It is recommended that ECM 2.3 controls be used for all

replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT

FORCE THE CONNECTOR.

  It plugs in very easily when properly

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as follows:

a. Unit is as far INTO the blower housing as possible.
b.Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8

o’clock positions when the blower is positioned in its final
location and orientation.

d.Add a drip loop to the cables so that water cannot enter the motor

by draining down the cables.  

Refer to Figure 28.

The installation is now complete.  Reapply the AC power to the HVAC
equipment and verify that the new motor control module is working
properly.  Follow the manufacturer's procedures for disposition of the old
control module.

Figure 27

Figure 26

Figure 28

Summary of Contents for QTEC Q24A1D Series

Page 1: ...g Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 523 Supersedes NEW File Vol II Tab 14 Date 08 20 09 Models Q24A1D Q30A1D Q36A1D Q42A1D Q48A1D Q60A1D QTEC SERIES PACK...

Page 2: ...3 QTEC General Information QTEC Model Nomenclature 4 Shipping Damage 8 Unit Removal From Skid 8 Handling Unit After Removal From Skid 9 General 9 Minimum Installation Height 9 Duct Work 11 Filters 11...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commercial Ven...

Page 5: ...1 V 0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0...

Page 6: ...2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 2 4 Q 5 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 5 3 5 3 8 5 3 8 0 5 0 5 0 6 0 9 8 8 6 4 0 1 0 1 8 8 8 5 5 2 0 6 5 2 6 0 1 0 1 0 1 Z 0...

Page 7: ...Manual 2100 523 Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...

Page 8: ...ed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the...

Page 9: ...ate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to...

Page 10: ...Manual 2100 523 Page 10 of 41 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Page 11: ...ustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be...

Page 12: ...m the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be insta...

Page 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Page 14: ...Manual 2100 523 Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Page 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Page 16: ...Manual 2100 523 Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Page 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Page 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Page 19: ...k both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessar...

Page 20: ...breaker panel See Figure 15 WIRING LOW VOLTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation re...

Page 21: ...R terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of...

Page 22: ...o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o...

Page 23: ...5 4 3 2 1 Plug 4 8 R C Rc 12 11 10 9 C R W2 E C R W2 W1 G A Y1 4 3 5 6 Y1 G F 1 2 3 Blue Yellow Brown White Orange Yellow Blue Brown 2 Red White Red White H200 Thermostat Black White Humidistat 8403...

Page 24: ...8 4102 073 4 R Plug 2 C 1 Yellow 2 12 Purple White Brown Temp and Humidity Controller Pink Y1 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000A or...

Page 25: ...Blue 9 D YO 10 Orange A 7 PART 8403 060 5 Black White G 3 Brown White 6 8 4102 074 11 R Y1 Plug 2 C 1 Yellow 4 2 12 Brown W1 E Temp and Humidity Controller W2 Purple White FIGURE 19 UNIT MOUNTED THERM...

Page 26: ...nge 5 Part 8403 060 6 Black White 24VAC 10 D Y0 9 Blue Red White Controller Brown White A 7 Purple White Brown 2 Green 4 Out Yellow Black Brown Red Red White Orange CO2 Controller Part 8403 056 Temp a...

Page 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 28: ...or to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will...

Page 29: ...ockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer th...

Page 30: ...e mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be...

Page 31: ...he unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist...

Page 32: ...Manual 2100 523 Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 33: ...Manual 2100 523 Page 33 of 41 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 34: ...the thermostat on units with E climate control option It is energized by applying power to the F terminal of the low voltage strip on units with G climate control options On climate option I it is ene...

Page 35: ...Manual 2100 523 Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...

Page 36: ...Manual 2100 523 Page 36 of 41 FIGURE 25 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM...

Page 37: ...o c e s 0 1 n i h t i w d n a l a n i m r e t p u d e e p s C C C n e e w t e b r a e p p a d l u o h s r e w o p 0 1 r e t f a r e p m u j p u d e e p s e v o m e R s d n o c e s e v i t c e f e d r...

Page 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 39: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Page 40: ...shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 29 FAN BLADE SETTING TABLE 6 FAN BLADE DIMENSIONS L E D O M A N O I...

Page 41: ...0 0 5 1 4 0 0 7 5 2 0 0 0 0 4 0 0 3 5 2 0 0 5 8 3 0 0 6 4 2 0 0 0 7 3 0 0 0 4 2 0 0 4 5 3 0 0 3 3 2 0 0 9 3 3 0 0 5 2 2 0 0 3 2 3 0 0 8 1 2 D 1 A 2 4 Q 5 7 2 6 g n i l o o C l a t o T g n i l o o C e...

Reviews: