while this test is performed. The wiring terminals
are easily removed by pulling them from the iSeries
Smart Actuator. Using the information found in
Table 15, estimate the temperature measured by
the sensor. The sensor and thermometer readings
should be close. If the test meter reads a very high
TABLE 15
Temperature F vs. Resistance R of Temperature Sensor
F
R
F
R
F
R
F
R
-25.0
196871
13.0
56985
53.0
19374
89.0
7507
-24.0
190099
14.0
55284
52.0
18867
90.0
7334
-23.0
183585
15.0
53640
53.0
18375
91.0
7165
-22.0
177318
16.0
52051
54.0
17989
92.0
7000
-21.0
171289
17.0
50514
55.0
17434
93.0
6840
-20.0
165487
18.0
49028
56.0
16984
94.0
6683
-19.0
159904
19.0
47590
57.0
16547
95.0
6531
-18.0
154529
20.0
46200
58.0
16122
96.0
6383
-17.0
149355
21.0
44855
59.0
15710
97.0
6239
-16.0
144374
22.0
43554
60.0
15310
98.0
6098
-15.0
139576
23.0
42295
61.0
14921
99.0
5961
-14.0
134956
24.0
41077
62.0
14544
100.0
5827
-13.0
130506
25.0
39898
63.0
14177
101.0
5697
-12.0
126219
26.0
38757
64.0
13820
102.0
5570
-11.0
122089
27.0
37652
65.0
13474
103.0
5446
-10.0
118108
28.0
36583
66.0
13137
104.0
5326
-9.0
114272
29.0
35548
67.0
12810
105.0
5208
-8.0
110575
30.0
34545
68.0
12492
106.0
5094
-7.0
107010
31.0
33574
69.0
12183
107.0
4982
-6.0
103574
32.0
32634
70.0
11883
108.0
4873
-5.0
100260
33.0
31723
71.0
11591
109.0
4767
-4.0
97064
34.0
30840
72.0
11307
110.0
4663
-3.0
93981
35.0
29986
73.0
11031
111.0
4562
-2.0
91008
36.0
29157
74.0
10762
112.0
4464
-1.0
88139
37.0
28355
75.0
10501
113.0
4367
0.0
85371
38.0
27577
76.0
10247
114.0
4274
1.0
82699
39.0
26823
77.0
10000
115.0
4182
2.0
80121
40.0
26092
78.0
9760
116.0
4093
3.0
77632
41.0
25383
79.0
9526
117.0
4006
4.0
75230
42.0
24696
80.0
9299
118.0
3921
5.0
72910
43.0
24030
81.0
9077
119.0
3838
6.0
70670
44.0
23384
82.0
8862
120.0
3757
7.0
68507
45.0
22758
83.0
8653
121.0
3678
8.0
66418
46.0
22150
84.0
8449
122.0
3601
9.0
64399
47.0
21561
85.0
8250
123.0
3526
10.0
62449
48.0
20989
86.0
8057
124.0
3452
11.0
60565
49.0
20435
87.0
7869
12.0
58745
50.0
19896
88.0
7686
resistance, there may be a broken wire, a poor wiring
connection or a defective sensor. If the resistance
is very low, the wiring may be shorted, there may be
moisture in the sensor or the sensor may be defective.
To test for a defective sensor, measure the resistance
directly at the sensor location.
Summary of Contents for Q-TEC Series
Page 16: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 17: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 22: ......
Page 32: ......
Page 92: ...Manual 2100 738A Page 60 of 71 FIGURE 36 Water Source Heat Pump Cooling Cycle...
Page 93: ...Manual 2100 738A Page 61 of 71 FIGURE 37 Water Source Heat Pump Heating Cycle...
Page 105: ......
Page 107: ......
Page 111: ......
Page 125: ...Manual 2110 1558 Page 14 of 23 OPTIONAL CLIMATE CONTROLS SEXP 560 3 2 1...
Page 127: ...Manual 2110 1558 Page 16 of 23 OPTIONAL CLIMATE CONTROLS 1 3 2 4 SEXP 639 5...
Page 129: ...Manual 2110 1558 Page 18 of 23 OPTIONAL CLIMATE CONTROLS 6 4 2 3 1 5 SEXP 646...
Page 131: ...Manual 2110 1558 Page 20 of 23 OPTIONAL CLIMATE CONTROLS SEXP 645 4 3 2 5 6 1...
Page 135: ......