background image

Manual 2100-653A
Page 

41 of 44

Manual

2100-522B

Page

36 of 38

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              

Use the shorter 

bolts and 

alignment pin 

supplied when 

replacing an 

ECM 2.0 

control.

Figure 3

ECM 

2.3/2.5

Power Connector

(5-pin)

Control Connector

(16-pin)

Hex-head Screws

Motor Connector

(3-pin)

Motor Connector

(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats

Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower

motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,

with the motor, be removed from the furnace/air handler.  (Follow the

manufacturer’s procedures).  Unplug the two cable connectors to the motor.

There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate  the  two  standard  ¼"  hex  head  bolts  at  the  rear  of  the  control

housing  (at  the  back  end  of  the  control  opposite  the  shaft  end).   

Refer  to

Figure  24.   

Remove  these  two  bolts  from  the  motor  and  control  assembly

while  holding  the  motor  in  a  way  that  will  prevent  the  motor  or  control

from  falling  when  the  bolts  are  removed.    If  an  ECM2.0  control  is  being

replaced  (recognized  by  an  aluminum  casting  rather  that  a  deep-drawn

black  steel  can  housing  the  electronics),  remove  only  the  hex-head  bolts.

DO  NOT  REMOVE  THE  TORX-HEAD  SCREWS.

5. The  control  module  is  now  free  of  mechanical  attachment  to  the

motor  endshield  but  is  still  connected  by  a  plug  and  three  wires  inside

the  control.    Carefully  rotate  the  control  to  gain  access  to  the  plug  at

the  control  end  of  the  wires.    With  thumb  and  forefinger,  reach  the

latch  holding  the  plug  to  the  control  and  release  it  by  squeezing  the

latch  tab  and  the  opposite  side  of  the  connector  plug  and  gently  pulling

the  plug  out  of  the  connector  socket  in  the  control.   

DO  NOT  PULL

ON  THE  WIRES.    GRIP  THE  PLUG  ONLY.

6. The  control  module  is  now  completely  detached  from  the  motor.

Verify  with  a  standard  ohmmeter  that  the  resistance  from  each  motor

lead  (in  the  motor  plug  just  removed)  to  the  motor  shell  is  >100K  ohms.

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If any

motor  lead  fails  this  test,  do  not  proceed  to  install  the  control  module.

THE  MOTOR  IS  DEFECTIVE  AND  MUST  BE  REPLACED.

Installing  the  new  control  module  will  cause  it  to  fail  also.

7. Verify  that  the  replacement  control  is  correct  for  your

application.    Refer  to  the  manufacturer's  authorized  replacement  list.

USING  THE  WRONG  CONTROL  WILL  RESULT  IN

IMPROPER  OR  NO  BLOWER  OPERATION.

    Orient  the  control

module  so  that  the  3-wire  motor  plug  can  be  inserted  into  the  socket  in

the  control.    Carefully  insert  the  plug  and  press  it  into  the  socket  until

it  latches.   

A  SLIGHT  CLICK  WILL  BE  HEARD  WHEN

PROPERLY  INSERTED.

    Finish  installing  the  replacement  control  per

one  of  the  three  following  paragraphs,  8a,  8b  or  8c.

8a. 

IF  REPLACING  AN  ECM  2.0  CONTROL

  (control  in  cast

aluminum  can  with  air  vents  on  the  back  of  the  can) 

WITH  AN  ECM

2.3  CONTROL

  (control  containing  black  potting  for  water  protection  in

black  deep-drawn  steel  case  with  no  vents  in  the  bottom  of  the  can),

locate  the  two  through-bolts  and  plastic  tab  that  are  packed  with  the

replacement  control.    Insert  the  plastic  tab  into  the  slot  at  the  perimeter

of the open end of the can so that the pin is located on the inside of the

perimeter of the can.  Rotate the can so that the tab inserts into the tab

locater  hole  in  the  endshield  of  the  motor.    Using  the  two  through-bolts

provided  with  the  replacement  control,  reattach  the  can  to  the  motor.

THE  TWO  THROUGH-BOLTS  PROVIDED  WITH  THE

REPLACEMENT  ECM  2.3  CONTROL  ARE  SHORTER  THAN

THE  BOLTS  ORIGINALLY  REMOVED  FROM  THE  ECM  2.0

CONTROL  AND  MUST  BE  USED  IF  SECURE  ATTACHMENT

OF  THE  CONTROL  TO  THE  MOTOR  IS  TO  BE  ACHIEVED.

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8b. 

IF  REPLACING  AN  ECM  2.3  CONTROL

 

WITH  AN  ECM  2.3

CONTROL

,  the  plastic  tab  and  shorter  through-bolts  are  not  needed.    The

control  can  be  oriented  in  two  positions  180°  apart.   

MAKE  SURE  THE

ORIENTATION  YOU  SELECT  FOR  REPLACING  THE

CONTROL  ASSURES  THE  CONTROL'S  CABLE  CONNECTORS

WILL  BE  LOCATED  DOWNWARD  IN  THE  APPLICATION  SO

THAT  WATER  CANNOT  RUN  DOWN  THE  CABLES  AND  INTO

THE  CONTROL.

    Simply  orient  the  new  control  to  the  motor's  endshield,

insert bolts, and tighten.  

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8c. 

IF  REPLACING  AN  ECM  2.0  CONTROL  WITH  AN  ECM  2.0

CONTROL 

(It  is  recommended  that  ECM  2.3  controls  be  used  for  all

replacements), 

the  new  control  must  be  attached  to  the  motor  using

through  bolts  identical  to  those  removed  with  the  original  control.   

DO

NOT  OVERTIGHTEN  THE  BOLTS.

9. Reinstall  the  blower/motor  assembly  into  the  HVAC  equipment.

Follow  the  manufacturer's  suggested  procedures.

10.  Plug  the  16-pin  control  plug  into  the  motor.    The  plug  is  keyed.

Make  sure  the  connector  is  properly  seated  and  latched.

11.  Plug  the  5-pin  power  connector  into  the  motor.    Even  though  the

plug  is  keyed, 

OBSERVE  THE  PROPER  ORIENTATION.    DO  NOT

FORCE  THE  CONNECTOR.

    It  plugs  in  very  easily  when  properly

oriented.   

REVERSING  THIS  PLUG  WILL  CAUSE  IMMEDIATE

FAILURE  OF  THE  CONTROL  MODULE.

12.  Final  installation  check.    Make  sure  the  motor  is  installed  as  follows:

a. Unit  is  as  far  INTO  the  blower  housing  as  possible.

b. Belly  bands  are  not  on  the  control  module  or  covering  vent  holes.

c. Motor  connectors  should  be  oriented  between  the  4  o’clock  and  8

o’clock  positions  when  the  blower  is  positioned  in  its  final

location  and  orientation.

d. Add  a  drip  loop  to  the  cables  so  that  water  cannot  enter  the  motor

by  draining  down  the  cables.   

Refer  to  Figure  26.

The  installation  is  now  complete.    Reapply  the  AC  power  to  the  HVAC

equipment  and  verify  that  the  new  motor  control  module  is  working

properly.    Follow  the  manufacturer's  procedures  for  disposition  of  the  old

control  module.

Figure 25

Figure 24

Figure 26

Figure 28

Figure 29

Figure 30

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower 
motor you need to take the following steps:
1. You MUST have the correct replacement module.  The controls 
are factory programmed for specific operating modes.  Even though 
they look alike, different modules may have completely different 
functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT 

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler 
being serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER 

APPLIED. 

 

To avoid electric shock from the motor’s capacitors, 

disconnect power and wait at least 5 minutes before opening motor.
3. It is usually not necessary to remove the motor from the blower 
assembly.  However, it is recommended that the whole blower 
assembly, with the motor, be removed from the furnace/air handler.  
(Follow the manufacturer’s procedures).  Unplug the two cable 
connectors to the motor.  There are latches on each connector.  

DO 

NOT PULL ON THE WIRES.

  

The plugs remove easily when properly 

released.
4. Locate the two standard ¼" hex head bolts at the rear of the 
control housing (at the back end of the control opposite the shaft 
end).  

Refer to Figure 28.  

Remove these two bolts from the 

motor and control assembly while holding the motor in a way that 
will prevent the motor or control from falling when the bolts are 
removed.  If an ECM2.0 control is being replaced (recognized by an 
aluminum casting rather that a deep-drawn black steel can housing 
the electronics), remove only the hex-head bolts.  

DO NOT REMOVE 

THE TORX-HEAD SCREWS.

5. The control module is now free of mechanical attachment to the 
motor endshield but is still connected by a plug and three wires 
inside the control.  Carefully rotate the control to gain access to the 
plug at the control end of the wires.  With thumb and forefinger, 
reach the latch holding the plug to the control and release it by 
squeezing the latch tab and the opposite side of the connector 
plug and gently pulling the plug out of the connector socket in the 
control.  

DO NOT PULL ON THE WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.  
Verify with a standard ohmmeter that the resistance from each 
motor lead (in the motor plug just removed) to the motor shell is 
>100K ohms.  

Refer to Figure 29.  

(Measure to unpainted motor 

end plate.)  If any motor lead fails this test, do not proceed to 
install the control module.  

THE MOTOR IS DEFECTIVE AND MUST 

BE REPLACED.

  Installing the new control module will cause it to 

fail also.
7. Verify that the replacement control is correct for your 
application.  Refer to the manufacturer's authorized replacement 
list.  

USING THE WRONG CONTROL WILL RESULT IN IMPROPER 

OR NO BLOWER OPERATION. 

 Orient the control module so 

that the 3-wire motor plug can be inserted into the socket in the 
control.  Carefully insert the plug and press it into the socket until 
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY 

INSERTED.

  Finish installing the replacement control per one of the 

three following paragraphs, 8a, 8b or 8c.
8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast 

aluminum can with air vents on the back of the can) 

WITH AN ECM 

2.3 CONTROL

 (control containing black potting for water protection 

in black deep-drawn steel case with no vents in the bottom of the 
can), locate the two through-bolts and plastic tab that are packed 
with the replacement control.  Insert the plastic tab into the slot at 
the perimeter of the open end of the can so that the pin is located 
on the inside of the perimeter of the can.  Rotate the can so that 
the tab inserts into the tab locater hole in the endshield of the 
motor.  Using the two through-bolts provided with the replacement 
control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE 

REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN THE 

BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 CONTROL 

AND MUST BE USED IF SECURE ATTACHMENT OF THE 

CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS. 

8b. 

IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 

CONTROL

, the plastic tab and shorter through-bolts are not needed.  

The control can be oriented in two positions 180° apart.  

MAKE 

SURE THE ORIENTATION YOU SELECT FOR REPLACING THE 

CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS WILL 

BE LOCATED DOWNWARD IN THE APPLICATION SO THAT WATER 

CANNOT RUN DOWN THE CABLES AND INTO THE CONTROL.

  

Simply orient the new control to the motor's endshield, insert bolts, 
and tighten.  

DO NOT OVERTIGHTEN THE BOLTS

.

8c. 

I

F REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0 

CONTROL

 

(It is recommended that ECM 2.3 controls be used for all 

replacements), 

the new control must be attached to the motor using 

through bolts identical to those removed with the original control.  

DO 

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.  
Follow the manufacturer's suggested procedures.
10. Plug the 16-pin control plug into the motor.  The plug is keyed.  
Make sure the connector is properly seated and latched.
11. Plug the 5-pin power connector into the motor.  Even though 
the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT 

FORCE THE CONNECTOR.

  It plugs in very easily when properly 

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE 

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as 
follows:
    a. Unit is as far INTO the blower housing as possible.
    b. Belly bands are not on the control module or covering vent 

holes.

    c. Motor connectors should be oriented between the 4 o’clock 

and 8 o’clock positions when the blower is positioned in its 
final location and orientation.

    d. Add a drip loop to the cables so that water cannot enter the 

motor by draining down the cables.  

Refer to Figure 30.

The installation is now complete.  Reapply the AC power to the HVAC 
equipment and verify that the new motor control module is working 
properly.  Follow the manufacturer's procedures for disposition of the 
old control module.

Summary of Contents for Q-TEC Q30H3DA

Page 1: ...ryan Ohio 43506 www bardhvac com Manual No 2100 653A Supersedes 2100 653 Date 10 11 17 Q TECTM SERIES PACKAGED HEAT PUMP Models Q24H3DA Q24H3DB Q24H3DC Q30H3DA Q30H3DB Q30H3DC Q36H3DA Q36H3DB Q36H3DC...

Page 2: ...actory Built In Electric Heat 4 Table 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats and Controls 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of...

Page 3: ...nd Summer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Con...

Page 4: ...glass P 2 Pleated Q 36 H 3 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 43 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW COIL OPTIONS X Standard 1 Phenolic c...

Page 5: ...25 30 30 14 10 10 10 14 10 10 10 Q48H3DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 37 62 87 87 50 70 90 90 8 6 3 3 10 8 8 8 37 37 37 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48...

Page 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...

Page 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid see Figure 3 B The unit can be tipped forward and slid down the...

Page 8: ...any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels a...

Page 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...

Page 10: ...Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for duct...

Page 11: ...rain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall When...

Page 12: ...RE 11 Rear Drain Top View Wall maximum 10 for rear drain Couplings not shown but recommended for ease of removability for service Sleeve Drain Line Wall Bracket Unit FIGURE 10 Standard Rear Drain FIGU...

Page 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Page 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Page 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Page 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Page 17: ...13A Unit Mounting Method 1 Bottom Trim Piece Bottom Trim Extension Mounting Bracket Side Trim 2 PCS Side Trim 2 PCS Cabinet Side Panel Enlarged view of mounting bracket showing sleeve to cabinet atta...

Page 18: ...sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim...

Page 19: ...cuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conduct...

Page 20: ...way valve are energized and the evaporator airflow is reduced The 3 way valve directs hot discharge gas into a separate desuperheating condenser circuit that reheats the conditioned air before it is...

Page 21: ...ble speed ECM motor The motor is designed to maintain rated airflow up to the maximum static allowed It is important that the blower motor plugs are not plugged in or unplugged while the power is on F...

Page 22: ...6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 17 Term Block 8403 081 8 WHEN USING 8403 081 TSJDT WITH 15KW HEAT 2 FACTORY INSTALLED JUMPER 1 G Thermostat Black White Red White Brown Blue Yellow Orange...

Page 23: ...PER E TO W2 ON LOW VOLTAGE TERMINAL BLOCK WHEN Thermostat 12 3 With X Thermostat Option And Demand Ventilation USING 8403 081 THERMOSTAT WITH UNIT WITH 15KW OF HEAT Dehumidification Wiring Diagram MIS...

Page 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White...

Page 25: ...OUT CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White TEMP OUT Red White 8403 060 With I Thermostat Option Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E G A Y1 Red Yellow Orange Yellow Bl...

Page 26: ...2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White Black Red Ye...

Page 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 28: ...e to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contacto...

Page 29: ...he cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease in pulling unit out from the wall it may be des...

Page 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q TEC Energy Recovery Ventilator Option Before starti...

Page 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...

Page 32: ...Manual 2100 653A Page 32 of 44 FIGURE 23 QERV Removal Mounting Screws Front Fill Lower Blower Assembly Blower Connector Power Connectors...

Page 33: ...ft spring to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capi...

Page 34: ...FOR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inac...

Page 35: ...Upper and lower service doors must be attached to obtain proper reading This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader valve core r...

Page 36: ...ll remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate defrost jumper sen...

Page 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Page 38: ...V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into def...

Page 39: ...74 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 138...

Page 40: ...otor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop fi...

Page 41: ...ion and orientation d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVA...

Page 42: ...ty of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity see Table 8 The following pressure tables show nomina...

Page 43: ...DB 67 WB Low Side High Side 134 341 135 363 136 387 137 412 138 439 140 468 141 498 143 530 144 563 146 598 85 DB 72 WB Low Side High Side 139 353 140 376 141 401 142 426 143 454 145 484 146 515 148...

Page 44: ...1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X X X X X X X X X X 2nd Sta...

Reviews: