background image

Manual 2100-653A
Page 

20 of 44

the electric heaters will turn off and the airflow will be 
reduced and the system will continue to dehumidify until 
humidistat is satisfied.  

If the unit is running in heat pump mode and the 
humidistat calls for dehumidification, the 
dehumidification mode takes precedence over the heat 
pump heating mode.  The unit will not return to the 
heating mode until 2nd stage heating is called for.

Climate control 

Option I

 is an electronic, programmable 

thermostat with humidistat and a CO

2

 controller.  The 

subbase of the thermostat and CO

2

 controller are factory 

wired to the front panel of the unit.  See Figure 20 for 
wiring diagram.  This unit has a refrigerant reheat circuit 
that is controlled by a 3 way valve.

When the humidity is above the setpoint of the 
humidistat, the compressor circuit and the 3 way valve 
are energized and the evaporator airflow is reduced.  The 
3 way valve directs hot discharge gas into a separate 
desuperheating condenser circuit that reheats the 
conditioned air before it is delivered to the room.  When 
the humidistat is satisfied, the system switches back to 
normal air conditioning mode.

If the thermostat calls for cooling during dehumidification 
mode, the call for cooling takes precedence over the 
dehumidification and the unit will cool until the thermostat 
is satisfied.  Once the call for cooling is satisfied, the unit 
may continue to dehumidify.

If the thermostat calls for heat when the unit is in the 
dehumidification mode, the electric heaters will energize and 
the evaporator airflow will return to the heating airflow.  When 
the thermostat is satisfied, the electric heaters will turn off 
and the airflow will be reduced and the system will continue 
to dehumidify until humidistat is satisfied.

If the unit is running in heat pump mode and the 
humidistat calls for dehumidification, the 
dehumidification mode takes precedence over the heat 
pump heating mode.  The unit will not return to the 
heating mode until 2nd stage heating is called for.

The CO

2

 controller will energize the vent option and the 

ID blower when the room CO

2

 levels rise over set level.  

Default CO

2

 setpoint is 950 ppm.  See Figure 24.

Climate control 

Options J & K

 are an electronic, 

programmable thermostat, humidistat and CO

2

 controller

 

"J" model only

) with BACnet, MS/TP or Ethernet 

connections.

When the humidity is above the setpoint of the humidistat, 
the compressor circuit and the 3-way valve are energized 
and the evaporator airflow is reduced.  The 3-way valve 
directs hot discharge gas into a separate desuperheating 
condenser circuit that reheats the conditioned air before it is 
delivered to the room.  When the humidistat is satisfied, the 
system switches back to normal air conditioning mode.

If the thermostat calls for cooling during dehumidification 
mode, the call for cooling takes precedence over the 

dehumidification and the unit will cool until the thermostat 
is satisfied.  Once the call for cooling is satisfied, the unit 
may continue to dehumidify.

If the thermostat calls for heat when the unit is in the 
dehumidification mode, the electric heaters will energize 
and the evaporator airflow will return to the heating airflow.  
When the thermostat is satisfied, the electric heaters will 
turn off and the airflow will be reduced and the system will 
continue to dehumidify until humidistat is satisfied.

If the unit is running in heat pump mode and the 
humidstat calls for dehumidification, the dehumidification 
mode takes precedence over the heat pump heating mode.  
The unit will not return to the heating mode until 2nd 
stage heating is called for.

On Option J Models only

, the CO

2

 sensor in the controller 

will energize the vent option and the ID blower when the 
room CO

2

 levels rise over set level.  Default CO

2

 setpoint is 

950 ppm.

NOTE:

  On Option X, field-provided means to control 

ventilation must be used if any of the motorized 

ventilation options are installed.

LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltage circuit.  
The 

“R”

 terminal is the 

hot

 terminal and the 

“C”

 terminal 

is 

grounded.

“G”

 terminal or pin 6 of P2 is the 

fan input

.  If the climate 

control option is abandoned and connections are made 
directly to P2 pin 6 of P2 must be energized for proper 
operation.

“Y1”

 terminal or pin 7 of P2 is the 

compressor input

.

“W1”

 terminal or pin 8 of P2 is the 

fist stage heat.

“R”

 terminal or pin 10 of P2 is 

24 VAC hot

.

“C”

 terminal or pin 11 of P2 is 

24 VAC grounded.

Terminal 

“1”

 or pin 4 of P2 is the dehumidification circuit.

Terminal 

“2”

 or pin 12 of P2 is the dehumidification 

circuit.  A contact must connect terminals 1 and 2.

“W2”

 terminal or pin 9 of P2 is 

second stage heat

 (if  

equipped).  If the unit is equipped with an optional 
hot water coil plenum box or electric heat these will be 
energized by this terminal.

LOW VOLTAGE CONNECTIONS 

FOR DDC CONTROL

 

Fan Only 

Energize G

 

Cooling Mode 

Energize Y, G

 

Heat Pump Heating 

Energize Y, G, B

 

2nd State Heating 

Energize G, W2, Y, B

 

    (if employed)

 

Ventilation 

Energize G, O1

 

Dehumidification 

Energize 4

 

Emergency Heat 

Energize B, W2, E, G

Summary of Contents for Q-TEC Q30H3DA

Page 1: ...ryan Ohio 43506 www bardhvac com Manual No 2100 653A Supersedes 2100 653 Date 10 11 17 Q TECTM SERIES PACKAGED HEAT PUMP Models Q24H3DA Q24H3DB Q24H3DC Q30H3DA Q30H3DB Q30H3DC Q36H3DA Q36H3DB Q36H3DC...

Page 2: ...actory Built In Electric Heat 4 Table 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats and Controls 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of...

Page 3: ...nd Summer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Con...

Page 4: ...glass P 2 Pleated Q 36 H 3 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 43 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW COIL OPTIONS X Standard 1 Phenolic c...

Page 5: ...25 30 30 14 10 10 10 14 10 10 10 Q48H3DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 37 62 87 87 50 70 90 90 8 6 3 3 10 8 8 8 37 37 37 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48...

Page 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...

Page 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid see Figure 3 B The unit can be tipped forward and slid down the...

Page 8: ...any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels a...

Page 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...

Page 10: ...Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for duct...

Page 11: ...rain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall When...

Page 12: ...RE 11 Rear Drain Top View Wall maximum 10 for rear drain Couplings not shown but recommended for ease of removability for service Sleeve Drain Line Wall Bracket Unit FIGURE 10 Standard Rear Drain FIGU...

Page 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Page 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Page 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Page 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Page 17: ...13A Unit Mounting Method 1 Bottom Trim Piece Bottom Trim Extension Mounting Bracket Side Trim 2 PCS Side Trim 2 PCS Cabinet Side Panel Enlarged view of mounting bracket showing sleeve to cabinet atta...

Page 18: ...sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim...

Page 19: ...cuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conduct...

Page 20: ...way valve are energized and the evaporator airflow is reduced The 3 way valve directs hot discharge gas into a separate desuperheating condenser circuit that reheats the conditioned air before it is...

Page 21: ...ble speed ECM motor The motor is designed to maintain rated airflow up to the maximum static allowed It is important that the blower motor plugs are not plugged in or unplugged while the power is on F...

Page 22: ...6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 17 Term Block 8403 081 8 WHEN USING 8403 081 TSJDT WITH 15KW HEAT 2 FACTORY INSTALLED JUMPER 1 G Thermostat Black White Red White Brown Blue Yellow Orange...

Page 23: ...PER E TO W2 ON LOW VOLTAGE TERMINAL BLOCK WHEN Thermostat 12 3 With X Thermostat Option And Demand Ventilation USING 8403 081 THERMOSTAT WITH UNIT WITH 15KW OF HEAT Dehumidification Wiring Diagram MIS...

Page 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White...

Page 25: ...OUT CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White TEMP OUT Red White 8403 060 With I Thermostat Option Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E G A Y1 Red Yellow Orange Yellow Bl...

Page 26: ...2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White Black Red Ye...

Page 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 28: ...e to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contacto...

Page 29: ...he cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease in pulling unit out from the wall it may be des...

Page 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q TEC Energy Recovery Ventilator Option Before starti...

Page 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...

Page 32: ...Manual 2100 653A Page 32 of 44 FIGURE 23 QERV Removal Mounting Screws Front Fill Lower Blower Assembly Blower Connector Power Connectors...

Page 33: ...ft spring to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capi...

Page 34: ...FOR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inac...

Page 35: ...Upper and lower service doors must be attached to obtain proper reading This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader valve core r...

Page 36: ...ll remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate defrost jumper sen...

Page 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Page 38: ...V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into def...

Page 39: ...74 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 138...

Page 40: ...otor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop fi...

Page 41: ...ion and orientation d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVA...

Page 42: ...ty of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity see Table 8 The following pressure tables show nomina...

Page 43: ...DB 67 WB Low Side High Side 134 341 135 363 136 387 137 412 138 439 140 468 141 498 143 530 144 563 146 598 85 DB 72 WB Low Side High Side 139 353 140 376 141 401 142 426 143 454 145 484 146 515 148...

Page 44: ...1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X X X X X X X X X X 2nd Sta...

Reviews: