Manual 2100-522B
Page

30 of 38

6. Some service requires the need to remove the unit

from the wall including replacement of the indoor
coil and/or the outdoor coil.  Also servicing the
outdoor fan motor or fan blade will require
removing the unit from the wall if the unit is
installed at a height that is not easily accessible
from the outside of the building.

In order to remove the unit from the wall the
following procedure must be used:

a. Turn off power to the unit at the remote

location.  Some units may have more than one
power supply.

b. Disconnect field wiring at unit terminal block

and remove from unit.

c. Disconnect condensate drain.

d. Remove the lower skirting around the unit.

e. Remove wall mounting brackets from wall on

each side of the unit.

f. If unit is attached to duct work, remove upper

cabinet extension by removing the top center
screw only from the cabinet side panel.

g. Remove screws that attach the duct work to

the unit flanges.

This unit is equipped with four rollers
mounted to the base.  For ease of pulling unit
out from the wall, you may want to remove
the bottom service door which requires
removal of the return air panel, and grip the
front flange of the base pan then pull straight
out.

7. Annual maintenance is required to make sure that

all of the systems are functioning properly.

a. Check to make sure that the drains are not

obstructed in any way.

b. Remove any debris in the condenser section of

the unit.

c. Inspect and clean mist eliminator as described

below.

d. Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve.  The
mist eliminator is constructed of an aluminum frame
and mesh.  The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall.  This requires that the ventilation package must
be removed.

It is recommended that the mist eliminator be inspected
annually and serviced as required.  The mist eliminator
can be inspected from the outside of the building by
looking through the outdoor grille.  The mist eliminator
can be serviced from the outside by using a vacuum
cleaner.  The outdoor grille must be removed.  Use the
vacuum to remove dirt and debris from the surface of
the mist eliminator.  If additional cleaning is required,
the mist eliminator will have to be removed from the
sleeve.

The ventilation package will have to be removed to gain
access tot he mist eliminator.  If the blank off plate
option is used, it is not necessary to service the mist
eliminator.  The steps necessary to remove each of the
vent options are listed on the following pages.

The mist eliminator can be cleaned by washing with
soap and water.  The excess water should be shaken off
the mist eliminator before it is reinstalled.

VENT OPTIONS

BAROMETRIC FRESH AIR DAMPER  (Standard)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
fresh air damper assembly can be seen on the back of
the unit.  See Figure 21.

1. The fresh air damper is attached to the back of the

unit with one screw on either side of the
assembly.  Both of the screws must be removed.

2. Once the mounting screws are removed, tilt the

assembly down and lift it out.

The mist eliminator can be seen through the opening.
The mist eliminator must be raised up and the bottom
can be pulled toward the front of the unit.

ECONOMIZER OR COMMERCIAL ROOM
VENTILATOR  (Option)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
economizer (EIFM) or commercial room ventilator
(CRV) can be seen after the panel has been removed.
The CRV or EIFM must be removed to gain access to
the mist eliminator.

1. The two mounting screws in the front of the

EIFM or CRV must be removed.

2. The power connectors for the CRV (located on

the right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector
and pull straight out.  Unplug both of the
connectors.

3. Slide the EIFM or CRV straight out of the unit.

Summary of Contents for Q-TEC Q24A1

Page 1: ...Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 522B Supersedes 2100 522A File Vol II Tab 14 Date 12 15 11 Models Q24A1 Q30A1 Q36A1 Q42A1 Q48A1 Q60A1 Q TEC SERIES PAC...

Page 2: ...t In Electric Heat Table 5 Table 2 Electrical Specifications 6 Table 3 Operating Voltage Range 20 Table 4 Wall Thermostats 22 Table 5 Fan Blade Dimensions 37 Table 6 Indoor Blower Performance 37 Table...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...conomizer Not available on dehumidification versions P Commercial Ventilator Motorized w Exhaust Power Return V Commercial Ventilator Motorized w Exhaust Spring Return R Energy Recovery Ventilator w I...

Page 5: ...2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0 5 0 8 3 6 1 0 9 2...

Page 6: ...A 0 3 Q 5 0 A 0 1 A 1 8 0 2 0 3 2 1 1 1 5 2 2 3 7 5 5 3 5 3 0 6 8 8 6 0 1 0 1 0 1 Z 0 B 1 A 0 3 Q 6 0 B 9 0 B 2 1 B 3 8 0 2 0 3 2 1 1 1 1 8 1 5 2 4 3 3 4 5 2 5 2 5 3 5 4 0 1 0 1 8 6 0 1 0 1 0 1 0 1 Z...

Page 7: ...Manual 2100 522B Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...

Page 8: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Page 9: ...nstructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularl...

Page 10: ...Manual 2100 522B Page 10 of 38 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Page 11: ...ly adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension c...

Page 12: ...the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be instal...

Page 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Page 14: ...Manual 2100 522B Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Page 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Page 16: ...Manual 2100 522B Page 16 of 38 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Page 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Page 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Page 19: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Page 20: ...th copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying c...

Page 21: ...and the C terminal is grounded G terminal or pin 6 of P2 is the fan input If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2 must be energized for proper op...

Page 22: ...o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o...

Page 23: ...ized ventilation options are installed 1 Y2 W1 R C W2 Y1 E 1 2 G Y2 A Y1 W2 C R W1 E 1 G Y2 Y W2 C R W 2 3 4 5 6 7 8 9 11 12 10 F Rc G 2 3 BROWN PURPLE RED WHITE BLUE YELLOW TERMINAL BLOCK 8403 060 1...

Page 24: ...ion X or A the CS2000A or other field provided means to control ventilation must be used if any of the motorized ventilation options are installed W1 E 3 Purple L Orange Red White Blue 9 G 6 5 Black W...

Page 25: ...FIGURE 19 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION W1 E 8403 060 D THERMOSTAT OPTION Y2 12 Plug 2 Brown G Purple Orange C Blue 9 10 6 5 Black White A 3 11 8 4102 070 4 R Y1 7 Red Wh...

Page 26: ...og Part 8201 062 W1 E Y2 Orange Red White Red Black Blue 9 10 6 Part 8403 060 5 Black White G 3 11 8 4102 071 R Y1 Plug 2 C W2 1 Yellow 12 Purple Brown 7 A Out Part 8403 056 Controller Brown White 2 4...

Page 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 28: ...event compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light a...

Page 29: ...lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer t...

Page 30: ...e mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be...

Page 31: ...the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mis...

Page 32: ...Manual 2100 522B Page 32 of 38 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 33: ...Manual 2100 522B Page 33 of 38 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 34: ...ppm See Figure 23 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed Pressure curves can be found later in th...

Page 35: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 36: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Page 37: ...igerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the un...

Page 38: ...1 4 5 4 6 3 1 1 8 4 7 3 1 8 0 5 9 3 1 4 3 5 0 4 1 1 6 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 2 1 6 5 3 6 2 1 3 8 3 2 3 1 1 1 4 7 3 1 9 3 4 1 4 1 0 4 4 5 4 1 3 9 4 7 4 1 1 2 5 9 4 1 8 4 5 0...

Reviews: