Bard PH13242-A Installation Instructions Manual Download Page 12

Manual

2100-468E

Page

12 of 27

AIR FILTERS

Air filters for the return air side of the system are not
provided as part of the various types of applications for these
models, and must be field supplied and installed as part of
the final installation.

Prior thought should be given to return air location and
placement of the air filter(s).  The air filter(s) must be of
adequate size and readily accessible to the operator of the
equipment.  Filters must be adequate in size and properly
maintained for proper operation.  If this is not done,
excessive energy use, poor performance, and multiple
service problems will result.  

It is impossible to oversize air

filters.  

Generous sizing will result in cleaner air and coils as

well as lower operating costs and extend the time between
required changes.  Table 5 shows minimum filter areas and
recommended filter sizes.  Actual filter sizes can vary with
the installation due to single or multiple returns utilizing a
filter/grille arrangement or being placed immediately ahead
of the indoor coil face in the return air duct.

5.

OTHER INSTALLATIONS

 – Many other

installations are possible with the packaged heat
pump.  No matter what the installation, always
consider the following facts:

A. Insure that the discharge air is not obstructed in

any way so as to cause operation difficulties.

B. The indoor coil drain pan is equipped with a

coupling that must be piped through a condensate
drain trap to a suitable drain.

C. Always mount the unit is such a position that it

may be easily reached for servicing and
maintenance.

D. Insure that the unit is clear so that proper air flow

over the outdoor coil will be maintained.

If this unit is operated in cooling below a 55° outdoor
ambient temperature, the installation of low ambient
controls (CMH-15) to unit is required.

CONDENSATE DRAIN TRAP

It is very important to provide a trap in the condensate
drain line to allow a positive liquid seal in the line and
assure correct drainage from the coil condensate pan.

Install condensate drain trap shown in Figure 5.  Use drain
connection size or larger.  Do not operate unit without
trap.  Unit must be level or slightly inclined toward drain.

With a trap installed on a unit located in an unconditioned
area, water in the trap may freeze.  It is recommended that
the trap material be of a type that will allow for expansion
of water when it freezes.

FIGURE  5

CONDENSATE DRAIN TRAP

NOTE: If roof hood accessory is to be used, information

on air filters may be found under that heading in
this manual.  Air filters are supplied as part of
that package.

TABLE  5

FILTERS REQUIRED AND SIZE

.

o

N

l

e

d

o

M

r

e

t

li

F

m

u

m

i

n

i

M

a

e

r

A

e

e

r

F

m

u

m

i

n

i

M

e

z

i

S

d

e

d

n

e

m

m

o

c

e

R

4

2

3

1

H

P

0

3

3

1

H

P

6

3

3

1

H

P

s

e

h

c

n

I

e

r

a

u

q

S

3

0

4

)

t

e

e

F

e

r

a

u

q

S

8

.

2

(

1

x

0

2

x

4

1

)

2

(

2

4

3

1

H

P

8

4

3

1

H

P

0

6

3

1

H

P

s

e

h

c

n

I

e

r

a

u

q

S

3

7

4

)

t

e

e

F

e

r

a

u

q

S

3

.

3

(

1

x

0

2

x

6

1

)

2

(

Summary of Contents for PH13242-A

Page 1: ...anual 2100 468E Supersedes 2100 468D File Volume II Tab 11 Date 05 28 09 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned MODELS PH13242 A PH13302 A PH13362 A PH...

Page 2: ...onnections 26 Figure 13 Wiring Connections Voltage 27 Start Up and Operation General 17 Topping Off System Charge 17 Safety Practices 17 Start Up Notes 17 Three Phase Scroll Compressor Start Up Inform...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels...

Page 5: ...c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2...

Page 6: ...0 2 0 4 2 X 1 X 1 9 0 B 3 2 3 P H E 3 8 0 2 0 4 2 X 5 1 B 3 2 3 P H E 3 8 0 2 0 4 2 X 2 5 0 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X 1...

Page 7: ...e v O x a M t n e r r u C n o i t c e t o r P 2 d l e i F r e w o P g n i r i W 3 d n u o r G e z i S e r i W 5 0 A 3 2 3 P H E 0 1 A 3 2 3 P H E 5 1 A 3 2 3 P H E 1 8 0 2 0 4 2 1 8 0 2 0 4 2 1 8 0 2...

Page 8: ...air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324 1330 1336 5 875 32 875 13 875 3...

Page 9: ...while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct a suitable raised mounting platform See...

Page 10: ...e and ressor Blower Motor Heater Package Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if dis...

Page 11: ...ORMS Both legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown...

Page 12: ...pped with a coupling that must be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Ins...

Page 13: ...pecified maintain the reversing valve energized when switched into heating mode does not cycle with demand TABLE 7 THERMOSTAT WIRE SIZE t a t s o m r e h T s e r u t a e F t n a n i m o d e r P 8 5 0...

Page 14: ...o Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material The unit rating plate lists a Maximum Time Delay Fuse or HACR ty...

Page 15: ...irable not advantageous in terms of efficiency Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas...

Page 16: ...0 3 2 1 B 2 6 3 3 1 H P 9 0 0 3 2 3 A 2 2 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 2 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 8 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 8 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 0 6 3 1 H P 0 1 5 0 0 3...

Page 17: ...arges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks ha...

Page 18: ...e room thermostat is in the On position and the blower is already in operation then the motor will ramp up to the required speed for cooling HEATING 1st Stage On a call for heating from the room therm...

Page 19: ...urer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to el...

Page 20: ...o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n e p o r o f k c e h...

Page 21: ...7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4...

Page 22: ...power fuses or circuit breakers to be sure that they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential PRESSURE SERVICE PO...

Page 23: ...g i H 7 3 1 2 5 2 8 3 1 6 7 2 0 4 1 9 9 2 1 4 1 3 2 3 2 4 1 7 4 3 4 4 1 0 7 3 5 4 1 4 9 3 6 4 1 0 2 4 8 4 1 6 4 4 9 4 1 2 7 4 1 5 1 8 9 4 2 5 1 4 2 5 3 5 1 0 5 5 5 8 B D 2 7 B W e d i S w o L e d i S...

Page 24: ...w o L e d i S h g i H 6 3 1 1 5 2 7 3 1 4 7 2 9 3 1 8 9 2 0 4 1 1 2 3 1 4 1 4 4 3 3 4 1 8 6 3 4 4 1 1 9 3 5 4 1 2 2 4 5 4 1 2 5 4 6 4 1 3 8 4 6 4 1 3 1 5 7 4 1 4 4 5 8 4 1 5 7 5 5 8 B D 2 7 B W e d i...

Page 25: ...y around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint FIGURE 11 BRAZING DIAG...

Page 26: ...within the ranges as listed on the unit serial plate If higher than allowed additional duct work is needed e If the motor does not shut off at the end of the cycle wait for any programmed delays to t...

Page 27: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Reviews: