Manual 2100-614K
Page
53 of 61
CONTROLLER CONNECTIONS DIAGRAM 29
Single Unit with Alarm Board
COPPER
SILVER
OPTIONAL FIELD INSTALLED
1
MIS-4303
Y1
Y2
CU
AG
G1
REMOVE JUMPER
G2
H1
H2
C
W
R
AG
CU
AG
CU
UNIT 2
2
POLARITY SENSITIVE. COPPER
3
LOCKOUT 1
LOCAL
SILVER
A/C #1
LEAD MUST CONNECT TO
SENSOR 12" LEADS
COPPER
SILVER
REFRIGERANT LOCKOUT
24V TERMINALS
REM 1
LOCKOUT 2
G
REM 2
CB
3
OPTIONAL - 48 VDC
+
CONTROLLER
GEN
NUMBER 8612-023A
REMOVE JUMPER
GENERATOR RUN ALARM
HUMIDITY CONTROLLER
CU, AND SILVER LEAD TO AG.
STANDARD LOCAL
35 FOOT TEMPERATURE
"NO" CONTACTS - CLOSE ON RISE
FIRE/SMOKE ALARM CIRCUIT
CONNECTION
FIRE/SMOKE
R
G
W
-
Y2
Y1
HUMIDITY
C
"NC" CONTACTS - OPEN ON ALARM
3
COPPER
NOTE: ALL SENSORS ARE
SENSORS, BARD PART
F2
UNIT 1
2
"NC" CONTACTS - OPEN ON ALARM
48 VDC
F1
1
ADDED WIRES TO KEEP "UNIT 2 POWER LOSS" ALARM OFF
2
2
3
OPTIONAL FIELD INSTALLED
OPTIONAL ALARM BOARD
CONNECTIONS FOR
NOTE: DC BACK-UP POWER
IS POLARITY SENSITIVE AND
MUST BE CONNECTED AS SHOWN
OR CONTROLLER WILL NOT
OPERATE ON DC POWER ONLY
REQUIRES ALARM RELAY IN EACH A/C UNIT WHICH IS PART OF "J" CONTROL MODULE
WIRE PER
CORRECT
DIAGRAM FOR
UNIT BEING
CONNECTED
Single Unit Application for MC4002 with Alarm Board
When connecting an MC4002 with alarm board to a single unit, the unit must be wired to the Unit 1 position on the
MC4002 board. A power loss alarm will appear for Unit 2. To eliminate this nuisance alarm, jumpers must be placed
from Unit 1 “R” terminal to Unit 2 “R” terminal and Unit 1 “C” terminal to unit 2 “C” terminal on the control board
(see Figure 21).
The control must be configured as follows: Number 8 “ALT” must be set to “NO”; Number 9 “LLCO” must be set to
“0”.
Wire the unit according to the correct diagram for the model being applied; see appropriate connection diagram.