Manual 2100-646
Page
4 of 26
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
HA
4S
4
K
A
05
B
P
X
X
X
J
TABLE 1
Electric Heat Table
See Table 3 for heater availability by model
Nominal
KW
At 240V
At 208V
Kw
1-Ph Amps
Btuh
Kw
1-Ph Amps
Btuh
5.0
5.0
20.8
17,065
3.75
18.0
12,799
8.0
8.0
33.3
27,304
6.00
28.8
20,478
10.0
10.0
41.7
34,130
7.50
36.1
25,598
15.0
15.0
62.5
51,195
11.25
54.1
38,396
These electric heaters are available in 230/208V units only.
VOLTS & PHASE
A – 230/208-1
KW
0Z – No KW
w/Circuit Breaker
or Pull Disconnect
05 – 5 KW
08 – 8 KW
10 – 10 KW
15 – 15 KW
VENTILATION OPTIONS
B – Blank-Off Plate
(No Ventilation)
Y – 100% Economizer
(Temperature)
Z – 100% Economizer
(Enthalpy)
COLOR OPTIONS
X – Beige (Standard)
4 – Buckeye Gray
5 – Desert Brown
8 – Dark Bronze
A – Aluminum
S – Stainless Steel
OUTLET OPTIONS
X – Front (Standard)
COIL OPTIONS
X – Standard
1 – Phenolic Coated
Evaporator
2 – Phenolic Coated
Condenser
3 – Phenolic Coated
Evaporator and
Condenser
CONTROL MODULES
J – Only
MODEL NUMBER
HA – Right Hand
HL – Left Hand
CAPACITY
4S – 4 Ton
5S – 5 Ton
REVISION
FILTER OPTIONS
P – 2" Pleated MERV 8
K
– Accumulator