background image

Manual 2100-573A
Page

20 of 21

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly, with
the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer to

Figure 9.  

Remove these two bolts from the motor and control

assembly while holding the motor in a way that will prevent the motor
or control from falling when the bolts are removed.  If an ECM2.0
control is being replaced (recognized by an aluminum casting rather
that a deep-drawn black steel can housing the electronics), remove
only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD

SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside the
control.  Carefully rotate the control to gain access to the plug at the
control end of the wires.  With thumb and forefinger, reach the latch
holding the plug to the control and release it by squeezing the latch tab
and the opposite side of the connector plug and gently pulling the plug out
of the connector socket in the control.  

DO NOT PULL ON THE

WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor lead
(in the motor plug just removed) to the motor shell is >100K ohms.  

Refer

to Figure 10.  

(Measure to unpainted motor end plate.)  If any motor

lead fails this test, do not proceed to install the control module.  

THE

MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing

the new control module will cause it to fail also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

   Finish installing the replacement control per

one of the three following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM 2.3

CONTROL

 (control containing black potting for water protection in

black deep-drawn steel case with no vents in the bottom of the can), locate
the two through-bolts and plastic tab that are packed with the replacement
control.  Insert the plastic tab into the slot at the perimeter of the open end
of the can so that the pin is located on the inside of the perimeter of the
can.  Rotate the can so that the tab inserts into the tab locater hole in the
endshield of the motor.  Using the two through-bolts provided with the
replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN THE
BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3

CONTROL

, the plastic tab and shorter through-bolts are not needed.  The

control can be oriented in two positions 180° apart.  

MAKE SURE THE

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL
ASSURES THE CONTROL'S CABLE CONNECTORS WILL BE
LOCATED DOWNWARD IN THE APPLICATION SO THAT
WATER CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL.

  Simply orient the new control to the motor's endshield,

insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM

2.0 CONTROL 

(It is recommended that ECM 2.3 controls be used for

all replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT

FORCE THE CONNECTOR.

  It plugs in very easily when properly

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as follows:

a. Unit is as far INTO the blower housing as possible.
b. Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8

o’clock positions when the blower is positioned in its final
location and orientation.

d. Add a drip loop to the cables so that water cannot enter the motor

by draining down the cables.  

Refer to Figure 11.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Figure 10

Figure 9

Figure 11

Summary of Contents for HA4S3

Page 1: ...3A Supersedes 2100 573 File Volume III Tab 16 Date 07 09 12 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned 0 6 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Models HA4S3 HL4S2 HA5S3 HL5S2 ...

Page 2: ...ll Mounting Information 8 Mounting the Unit 8 Typical Installations 8 Wiring Main Power 8 9 12 Wiring Low Voltage Wiring 12 Dirty Filter Switch Relay 12 Start Up General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High Low Pressure Switch 14 Service Hints 15 Compressor Control Module 15 Adjustments 16 Motor Start Device 16 Pressure Service P...

Page 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York...

Page 4: ... 2 n i e l b a l i a v a e r a s r e t a e h c i r t c e l e e s e h T 1 See Table 3 for Heater Availability by Model VOLTS PHASE A 230 208 1 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 08 8 KW 10 10 KW 15 15 KW VENTILATION OPTIONS B Blank off Plate Standard COLOR OPTIONS X Beige Standard 4 Buckeye Gray 5 Desert Brown 8 Dark Bronze A Aluminum S Stainless Steel OUTLET OPTIONS X Front S...

Page 5: ...ockable 4 Pitch Entrance Disconnect Rain Hood Air Built In Inlet Access Panel Low Voltage C Breaker High Voltage Electrical Drain Side View 2 13 C D K J A H I MIS 2762 Electrical Location Shipping Optional Mounting Supply Air Opening Side Wall Return Air Opening Entrances Brackets Built In Top Rain Flashing Bottom Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B I A C K 2 13 H ...

Page 6: ... 8 8 7 3 7 3 6 2 2 5 5 4 5 4 0 3 0 6 8 8 0 1 6 0 1 0 1 0 1 0 1 S 5 L A H Z 0 A 5 0 A 8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 4 4 4 4 3 5 3 6 9 8 0 5 0 5 0 6 0 7 0 9 8 8 6 6 3 0 1 0 1 0 1 8 8 4 4 4 4 6 2 2 5 0 5 0 5 0 3 0 6 8 8 0 1 6 0 1 0 1 0 1 0 1 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors 2 Based on 75 C copper wire ...

Page 7: ...a ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 6 for maximum static pressure available for duct design Design the duct work according to methods given by the Air Conditioning Contractors of America ACCA When duct runs...

Page 8: ... rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil...

Page 9: ...16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1 2 30 E 16 A C C 3 1 8 B Wall Opening and Hole Location View RETURN AIR 1 REQUIRED DIMENSIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN 29 DUCT COMBUSTIBLE MATERIALS A B C D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING...

Page 10: ...Y AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME PLATE OF WALL L THIS STRUCTURAL MEMBER ...

Page 11: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Page 12: ...208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operating condition For wiring size and connections refer to MV4000 Controller Manual 2100 571 DIRTY FILTER SWITCH RELAY These units include a dirty filter switch and relay The alarm output of relay is norm...

Page 13: ...frigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A...

Page 14: ... SWITCH All models covered by this Manual are supplied with a remote reset high pressure switch and low pressure switch If tripped this pressure switch may be reset by turning the thermostat off then back on again IMPORTANT These procedures must be followed at initial start up and at any time power has been removed for 12 hours or longer To prevent compressor damage which may result from the prese...

Page 15: ...utdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go int...

Page 16: ...r low cool when utilizing the charts Alarm Relay Output Alarm terminal is output connection for applications where alarm relay is employed This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure switch cut out and cut in settin...

Page 17: ...oid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil resistance The resistance should be 32 to 60 ohms depending on compressor temperature 4 Next check the molded plug Voltage check Apply control voltage to the plug wires 18 to 28 volt ac The measured dc voltage at the female conn...

Page 18: ... A R E P M E T E R U S S E R P 0 5 o F 5 5 o F 0 6 o F 5 6 o F 0 7 o F 5 7 o F 0 8 o F 5 8 o F 0 9 o F 5 9 o F 0 0 1 o F 5 0 1 o F 0 1 1 o F 5 1 1 o F S 4 A H S 4 L H B D 5 7 B W 2 6 E D I S W O L E D I S H G I H 2 2 1 4 8 1 4 2 1 1 0 2 5 2 1 8 1 2 7 2 1 6 3 2 9 2 1 4 5 2 1 3 1 2 7 2 1 3 1 1 9 2 2 3 1 2 1 3 3 3 1 5 3 3 4 3 1 9 5 3 5 3 1 1 8 3 7 3 1 7 0 4 9 3 1 5 3 4 1 4 1 3 6 4 B D 0 8 B W 7 6 E D...

Page 19: ... it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed C...

Page 20: ...lication Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into the socket in the control Carefully insert the plug and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement con...

Page 21: ...1 M F C S 4 L A H 0 2 0 0 8 0 5 2 8 0 0 1 1 0 0 5 1 0 0 1 1 0 0 5 1 S 5 L A H 0 2 0 0 8 0 0 5 8 0 0 3 1 0 0 7 1 0 0 1 1 0 0 5 1 TABLE 7 OPTIONAL ACCESSORIES HA4S3KA HA5S3KA L E D O M N O I T P I R C S E D 5 0 A S 4 A W H E e g a k c a P r e t a e H X 0 1 A S 4 A W H E e g a k c a P r e t a e H X 5 1 A S 4 A W H E e g a k c a P r e t a e H X 5 0 A S 5 A W H E e g a k c a P r e t a e H X 8 0 A S 5 A...

Reviews: