background image

Manual 2100-585B 

Page  14 of 19

START UP (Continued)

CONDENSER FAN OPERATION

Applies to H42, H48 and H60 models only.

  

NOTE: 

Certain models may be equipped with a Low Ambient 

Control (LAC), and if so equipped the condenser fan 

motor will have delay start until system refrigerant 

operationg pressure builds up.  After starting, the fan 

motor may or may not cycle depending upon ambient 

conditions.  This is normal operation.

  The condenser fan 

motor on 230/208 volt, one and three phase, 60 HZ units is 

a two-speed motor that comes factory wired on high speed 

for peak performance.  If ambient conditions permit, it can 

be reconnected to low speed (red wire) for lower sound 

level.  See wiring diagram.  

SERVICE HINTS

 1. Caution owner/operator to maintain clean air 

filters at all times.  Also, not to needlessly close off 

supply and return air registers.  This reduces airflow 

through the system, which shortens equipment 

service life as well as increasing operating costs.

  2. Check all power fuses or circuit breakers to be sure 

they are the correct rating.

  3. Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling 

in compressor contactor, starting the compressor 

and outdoor motor.  (See Note under Condenser Fan 

Operation if equipped with Low Ambient Control.)  

The G (indoor motor) circuit is automatically 

completed on any call for cooling operation or can be 

energized by manual fan switch on subbase for constant 

air circulation.  On a call for heating, circuit R-W1 

make at the thermostat pulling in heat contact for the 

strip heat and blower operation.  On a call for second 

stage heat, R-W2 makes bringing on second heat 

contactor, if so equipped.  

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all models 

covered by this manual.  The compressor control module 

is an anti-short cycle/lockout timer with high and low 

pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to 

the unit, the 

delay on make

 period begins, which will 

be 2 minutes plus 10% of the 

delay on break

 setting.  

When the delay on make is complete and the high 

pressure switch and low pressure switch is closed, the 

compressor contactor is energized.  Upon shutdown, the 

delay on break timer starts and prevents restart until the 

delay on break and delay on make periods have expired.  
During routine operation of the unit with no power 

interruptions, the compressor will operate on demand 

with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 

contactor will de-energize immediately.  The lockout timer 

will go into a 

soft lockout

 and stay in soft lockout until 

the high pressure switch closes and the delay on  break 

time has expired.  If the high pressure switch opens again 

in this same operating cycle, the unit will go into 

manual 

lockout

 condition and the alarm relay circuit will energize.  

Recycling the wall thermostat resets the manual lockout. 

Low Pressure Switch, Bypass & Lockout Sequence

If the low pressure switch opens for more than 120 

seconds, the compressor contactor will de-energize 

and go into a soft lockout.  Regardless the state of the 

low pressure switch, the contactor will reenergize after 

the delay on make time delay has expired.  If the low 

pressure switch remains open, or opens again for longer 

than 120 seconds, the unit will go into manual lockout 

condition and the alarm relay circuit will energize.  

Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 

where alarm relay is employed.  This terminal is 

powered whenever the compressor is locked out due to 

HPC or LPC sequences as described.

NOTE:Both high and low pressure switch controls are 

inherently automatic reset devices.  The high pressure 

switch and low pressure switch cut out and cut in 

settings are fixed by specific air conditioner unit 

model.  The lockout features, both soft and manual, 

are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time 

from 30 seconds to 5 minutes.  Delay on Make (DOM) 

timing on power-up and after power interruptions is equal 

to 2 minutes plus 10% of Delay on Break (DOB) setting:

  0.5 minute  (30 seconds)  DOB = 123  second DOM

  1.0 minute  (60 seconds)  DOB = 126  second DOM

  2.0 minute  (120 seconds)  DOB = 132  second DOM

  3.0 minute  (180 seconds)  DOB = 138 second DOM

  4.0 minute  (240 seconds)  DOB = 144  second DOM

  5.0 minute  (300 seconds)  DOB =  150 second DOM
During routine operation of the unit with no power 

interruptions the compressor will operate on demand 

with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High & low pressure service ports are installed on all units 

so that the system operating pressures can be observed.  A 

pressure table can be found later in the manual covering all 

models.  It is imperative to match the correct pressure table 

to the unit by model number.  See Table 2.

Summary of Contents for H42A2-A

Page 1: ...PACKAGED AIR CONDITIONERS Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585B Supersedes 2100 585A Date 10 09 14 H42A2 A H48A2 A H60A2 A...

Page 2: ...ns 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation Inst...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3...

Page 5: ...lls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required...

Page 6: ...es H42 H48 and H60 However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figure 2 for details...

Page 7: ...Bracket Back View P M L O E R S S S S S T N Q B 44 I A C K 2 13 H J N Q P M L O E 44 W 5 88 F G R S S S S S T B D 7 Economizer Air Intake Hood 1 Heat Electric Filter Access Panel MIS 3625 Heater Drai...

Page 8: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Page 9: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Page 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 11: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Page 12: ...24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to exte...

Page 13: ...arge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrig...

Page 14: ...interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The...

Page 15: ...echarge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screw...

Page 16: ...139 554 80 DB 67 WB Low Side High Side 132 328 133 351 135 376 137 401 139 427 141 454 143 481 145 509 147 539 149 568 85 DB 72 WB Low Side High Side 137 339 138 363 140 389 142 415 144 442 146 470 1...

Page 17: ...or 2 42 42 60 86 60 60 60 90 8 8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors Based on 75C copper wire All wir...

Page 18: ...450 1405 0 2 1685 1640 1460 1415 1925 1865 1395 1355 0 3 1590 1550 1390 1345 1870 1815 1340 1300 0 4 1495 1460 1310 1270 1755 1705 1225 1185 0 5 1400 1365 1225 1185 1660 1610 1125 1085 Model Rated CFM...

Page 19: ...Plate X Y EWM5 T 100 Economizer Temperature X Z EWM5 E 100 Economizer Enthalpy X F N A 100 Economizer DC Temperature X G N A 100 Economizer DC Enthalpy X Factory Installed Option Number Field Install...

Reviews: