background image

Manual 2100-585B 

Page  12 of 19

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information and 

maximum fuse or circuit breaker size.  Each outdoor unit is 

marked with a “Minimum Circuit Ampacity”.  This means 

that the field wiring used must be sized to carry that amount 

of current. Depending on the installed KW of electric heat, 

there may be two field power circuits required.  If this is 

the case, the unit serial plate will so indicate.  All models 

are suitable only for connection with copper wire. Each 

unit and/or wiring diagram will be marked “Use Copper 

Conductors Only”.  These instructions 

must be 

adhered to.  

Refer to the National Electrical Code (NEC) for complete 

current carrying capacity data on the various insulation 

grades of wiring material.  All wiring must conform to NEC 

and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) 

for all models including the most commonly used heater 

sizes.  Also shown are the number of field power circuits 

required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay 

Relay Fuse” or circuit breaker that is to be used with 

the equipment.  The correct size must be used for 

proper circuit protection and also to assure that there 

will be no nuisance tripping due to the momentary high 

starting current of the compressor motor.
The disconnect access door on this unit may be locked 

to prevent unauthorized access to the disconnect.  To 

convert for the locking capability, bend the tab located 

in the bottom left-hand corner of the disconnect 

opening under the disconnect access panel straight 

out.  This tab will now line up with the slot in the door.  

When shut, a padlock may be placed through the hole 

in the tab preventing entry.
See “Start Up” section for important information on 

three phase scroll compressor start ups.

See Tables 3 & 4 for Electrical Specifications.

Low Voltage Connection

These units use a 24-volt AC low voltage circuit.  The 

RT

” terminal is the 24V transformer output, and the 

R

” terminal is the 24VAC 

hot

 terminal for the operation 

of the equipment.  “

RT

” and “

R

” are connected with 

brass jumper bar which can be removed and “

RT

” and 

R

” connected to external NC (normally closed) contact 

such as a fire/smoke detector that will cause immediate 

shutdown of the equipment upon activation.

C

” terminal is 

grounded

.

G

” terminal is the 

fan input

.

Y

” terminal is the 

compressor input for cooling

 

1-Stage units only 

W1

” terminal is the 

1st stage electric heat

.

W2

” terminal is the 

2nd stage heat

 (if equipped).

E

”, “

F

”, “

Y2

” & “

A

” Used with EWM-T Economizer.

1

” NO (normally open) lockout alarm.

2

” NC (normally closed) lockout alarm.

3

” COM lockout alarm.

4

” & “

5

” dirty filter alarm NC (normally closed).

6

” Used with MD4000 only; do not use for anything else!

Y1

” & “

7

” Used with EWM-T Economizer; do not use 

for anything else!

8

” & “

9

” ECON Fail Alarm.

WIRING  –  LOW VOLTAGE WIRING 

230/208V, 1 phase and 3 phase equipment dual primary 

voltage transformers.  All equipment leaves the factory 

wired on 240V tap.  For 208V operation, reconnect 

from 240V to 208V tap.  The acceptable operating 

voltage range for the 240 and 208V taps are:

 

TAP RANGE

 

240 

253 – 216

 

208 

220 – 187

NOTE:  The voltage should be measured at the field 

power connection point in the unit and while 

the unit is operating at full load (maximum 

amperage operating condition).

For H model units with Y or Z vent option economizers, 

refer to the MV4000 Series Lead/Lag Controller manual 

2100-571 for low voltage connections diagrams.  

Factory installed Y and Z vent option are wired per 

Figure 7 of 2100-571. 

DIRTY FILTER SWITCH & RELAY

These units include a dirty filter switch and relay.  The 

alarm output of relay is normally closed, open on alarm 

and is connected to terminals 4 and 5 of the unit low 

voltage terminal block.

ECONOMIZER FAIL TIME DELAY RELAY

NOTE:  Applies only to units with economizers.

These units employ a time delay relay used in 

conjunction with the 100% Economizers to provide an 

economizer fail alarm.  The alarm output is connected 

to terminals 8 and 9 of the low voltage terminal block.  

The time delay should be set to no less than 3 minutes 

to ensure no nuisance alarms.

MIS-3054

TIMER TO BE

SET HERE

MIS-3054

Summary of Contents for H42A2-A

Page 1: ...PACKAGED AIR CONDITIONERS Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585B Supersedes 2100 585A Date 10 09 14 H42A2 A H48A2 A H60A2 A...

Page 2: ...ns 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation Inst...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3...

Page 5: ...lls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required...

Page 6: ...es H42 H48 and H60 However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figure 2 for details...

Page 7: ...Bracket Back View P M L O E R S S S S S T N Q B 44 I A C K 2 13 H J N Q P M L O E 44 W 5 88 F G R S S S S S T B D 7 Economizer Air Intake Hood 1 Heat Electric Filter Access Panel MIS 3625 Heater Drai...

Page 8: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Page 9: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Page 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 11: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Page 12: ...24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to exte...

Page 13: ...arge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrig...

Page 14: ...interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The...

Page 15: ...echarge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screw...

Page 16: ...139 554 80 DB 67 WB Low Side High Side 132 328 133 351 135 376 137 401 139 427 141 454 143 481 145 509 147 539 149 568 85 DB 72 WB Low Side High Side 137 339 138 363 140 389 142 415 144 442 146 470 1...

Page 17: ...or 2 42 42 60 86 60 60 60 90 8 8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors Based on 75C copper wire All wir...

Page 18: ...450 1405 0 2 1685 1640 1460 1415 1925 1865 1395 1355 0 3 1590 1550 1390 1345 1870 1815 1340 1300 0 4 1495 1460 1310 1270 1755 1705 1225 1185 0 5 1400 1365 1225 1185 1660 1610 1125 1085 Model Rated CFM...

Page 19: ...Plate X Y EWM5 T 100 Economizer Temperature X Z EWM5 E 100 Economizer Enthalpy X F N A 100 Economizer DC Temperature X G N A 100 Economizer DC Enthalpy X Factory Installed Option Number Field Install...

Reviews: