8403-066 ECU Series Controller:

Lead/Lag Unit Operation

SUPPLEMENTAL INSTRUCTIONS

Bard Manufacturing Company, Inc. 

Bryan, Ohio 43506
www.bardhvac.com

Manual: 7960-780
Supersedes: 

NEW

Date: 9-2-16

FIGURE 1

ECU Series Controller Buttons and Home, Overide and Configuration Screens

Software version R1.3.5.1 or newer. Earlier versions 

allowed two units to rotate.

Lead/Lag Overview

The Bard 8403-066 ECU Series Controller has an 
additional lead/lag feature that allows up to four units* 
to operate in a unit rotational mode. Once programmed, 
the ECU Series controller operation will rotate cooling 
and heating setpoints for up to four units every 24 
hours. It is important to verify all ECU Series controllers 
used are set to the correct time and date. Please refer 
to the user manual to verify the time and date setting 
for each ECU Series controller.

Navigate the menus and change settings by pressing a 
combination of the four arrow buttons and the ENTER 
button.

• 

ENTER

 button to select and/or exit value editing

• 

UP

 or 

DOWN

 button to move among entries

• 

RIGHT

 or 

LEFT

 button to move among value fields

• 

LEFT

 button to return to the home screen

Accessing the Lead/Lag Setup Menu

To access the lead/lag setup menu:

1. Press 

RIGHT button to access Main Menu screen.

2. Press 

DOWN button to scroll to ADVANCED. Press 

ENTER button.

3.  In the ADVANCED menu screen, press DOWN 

button to scroll to LEAD/LAG. Press ENTER button.

4.  Controller will ask for Admin Level Password. Use 

UP, DOWN and RIGHT buttons to enter BARD or 
1914. Press ENTER button.

Lead/Lag Menu Options

Once the LEAD/LAG menu is accessed, the following 
settings are available:

•  The ability to enable the lead/lag feature.
•  Identify the unit # the ECU Series controller will be 

connected to.