Screen
Menu Item
Range
Default Value
Description
D4 Status
Current status of low pressure input
(open means no input)
Blower Status
Manual DI 5
Off/On
Off
"On" to allow artificial manipulation of
blower status input
Manual Position
Closed/Open
Closed
Change to "Closed" to artifically create
blower status input
D5 Status
Current status of blower status input
(open means no input)
Damper Switch
Manual Status DI 6
Off/On
Off
"On" to allow artificial manipulation of
damper switch status input
Manual Position
Closed/Open
Closed
Change to "Closed" to artificially create
damper switch status input
D3 Status
Current status of damper switch status
input (open means no input)
Relay Outputs
Cooling Stg 1
Manual Relay 2
Off/On
Off
"On" to allow artificial manipulation of
cooling stage 1 relay action
Manual Position
Off/On
Off
Change to "On" to artificially force
cooling stage 1 relay
Relay 2 Status
Off/On
Off
Current status of cooling stage 1 relay
(off means no relay action)
Cooling Stg 2
Manual Relay 3
Off/On
Off
"On" to allow artificial manipulation of
cooling stage 2 relay action
Manual Position
Off/On
Off
Change to "On" to artificially force
cooling stage 2 relay
Relay 3 Status
Off/On
Off
Current status of cooling stage 2 relay
(off means no relay action)
Heating
Manual Relay 6
Off/On
Off
"On" to allow artificial manipulation of
heating relay action
Manual Position
Off/On
Off
Change to "On" to artificially force heat-
ing relay
Relay 6 Status
Off/On
Off
Current status of heating relay (off
means no relay action)
HVAC 2 Fail Alarm
Manual Relay 4
Off/On
Off
Manual Position
Off/On
Off
Relay 4 Status
Off/On
Off
Blower
Manual Relay 7
Off/On
Off
"On" to allow artificial manipulation of
blower relay action
Manual Position
Off/On
Off
Change to "On" to artificially force blower
relay