WALL-MOUNT UNIT ARCHITECTURE (CONT.)
Screen
Menu Item
Range
Default Value
Description
Return Air Temp
Manual Control B003
Off/On
Off
On to manually change temperature seen
by controller
Manual Position
-1000 – 1000
0
Degrees of change in sensor for manual
control
Value
(Temp + Value)
Current temperature plus the value in
manual position
Outdoor Humidity
Manual Control B005
Off/On
Off
On to manually change temperature seen
by controller
Manual Position
-1000 – 1000
0
Degrees of change in sensor for manual
control
Value
(% RH + Value)
Current %RH plus the value in manual
position
Freeze
Manual Control B007
Off/On
Off
On to manually change temperature seen
by controller
Manual Position
-1000 – 1000
0
Degrees of change in sensor for manual
control
Value
(Temp + Value)
Current temperature plus the value in
manual position
Digital Inputs
Power Loss
Manual DI 1
Off/On
Off
"On" to allow artificial manipulation
power loss input
Manual Position
Closed/Open
Closed
Change to "Open" to artifically create
power loss input
D1 Status
Current status of power loss input
(closed means no input)
Filter Switch
Manual DI 2
Off/On
Off
"On" to allow artificial manipulation filter
switch input
Manual Position
Closed/Open
Closed
Change to "Open" to artifically create
filter switch input
D2 Status
Current status of filter switch input
(closed means no input)
High Pressure Switch
Manual DI 3
Off/On
Off
"On" to allow artificial manipulation of
high pressure switch input
Manual Position
Closed/Open
Closed
Change to "Closed" to artifically create
high pressure input
D3 Status
Current status of high pressure input
(open means no input)
Low Pressure Switch
Manual DI 4
Off/On
Off
"On" to allow artificial manipulation of
low pressure switch input
Manual Position
Closed/Open
Closed
Change to "Closed" to artifically create
low pressure input