Bard CRVMP-5 Installation Instructions Manual Download Page 13

Manual 2100-457D 

Page 

13 of 16

ADDING OPTIONAL CO

2

 CONTROL 

SENSOR

Adding an optional Bard Part #8403-067 to this control 
will maximize the capabilities of this vent by only 
supplying fresh air intake to maintain CO

2

 levels.  This 

has multiple benefits.

• Minimizes ventilation load on structure as it only 
brings in what is required to maintain CO

2

 levels 

lowering reconditioning requirements (not having to 
heat/cool as much outside air).

• Will self-adjust for various occupancy levels so 
that you are not bringing in fresh air beyond need.  
For example, if a room is designed for a maximum 
occupancy of 40 persons  (the standard ventilation 
control would have to be set for that occupancy), but 
the room typically only contains 25 persons.  This 
control will self-adjust the amount of fresh air intake 
from 600 to 375 CFM automatically (based upon 15 
CFM per person standard rate to ASHRAE standards).

BASIC INSTALLATION

  1.  Make sure power is turned off to the unit

  2.  Follow steps beginning on page 2 for installation 

for standard control and vent assembly, then 
proceed with the following steps.

  3.  Run (4) wire thermostat wire from the unit to the 

desired CO

2

 sensor location.

  4.  Follow Figure 6 to configure the CO

2

 sensor for 

proper operation.

  5.  Connect the thermostat wiring from the CO

2

 sensor 

to step control assembly following the wiring 
diagram (enclosed in Literature Assembly or on 
ventilator).

  6.  Connect the orange wire from the “A” terminal 

of the units low voltage connection strip to the 
“OCC” terminal on the step control board.

  7.  To check operation, restore power to the unit.

  8.  Make sure that thermostatic control is in 

“occupied” mode of operation calling for 
ventilation.

  9.  Have someone stand in front of the CO

2

 sensor and 

breathe on it.  The display should show an increase 
in CO

2

 ppm and the damper blade in the ventilation 

package should increase (may be good to have a 
helper - one to breathe on control and one to 
observe damper).

Summary of Contents for CRVMP-5

Page 1: ...EL CRVMP 5 For Use with Bard 3 through 5 Ton WA S Series Wall Mount Air Conditioners INSTALLATION INSTRUCTIONS Manual 2100 457D Supersedes 2100 457C File Volume III Tab 19 Date 01 24 14 Bard Manufactu...

Page 2: ...igures Figure 1 Removal of Exterior Panels 4 Figure 2 Remove Air Filter Exhaust Cover Plate 5 Figure 3 Install Ventilator 6 Figure 4 Step Control Installation 8 Figure 5 Damper Control Board 9 Figure...

Page 3: ...eived and that there is no visible damage Note any shortages or damage on all copies of the freight bill The receiving party must contact the last carrier immediately preferably in writing requesting...

Page 4: ...embly which includes the integral ventilator with attached electrical harness step control assembly and miscellaneous hardware WARNING Open and lock unit disconnect switch before installing this acces...

Page 5: ...00 457D Page 5 of 16 FIGURE 2 REMOVE AIR FILTER AND EXHAUST COVER PLATE 3 Remove and save existing unit air filter and screws from front center grille See Figure 2 4 Remove and discard the exhaust cov...

Page 6: ...ntilator into the unit to the far left side clearing the right filter bracket Once the ventilator is fully inserted slide the ventilator to the right until it is tight against the back of the control...

Page 7: ...he control panel through the wire looms and route them into the low voltage box through the bushing See Figure 4 Make connections following the wiring diagram enclosed in Literature Assembly or on ven...

Page 8: ...t damper blade for required ventilation See next section 16 Replace mist eliminator filter Be sure that it is installed with the drain holes to the bottom 17 Remove blank off plate or barometric fresh...

Page 9: ...TENTIOMETER FOR STAGE 1 HEATING OR COOLING DAMPER POSITION G AND Y1 CONTROL SIGNALS FOR STAGE 2 HEATING OR COOLING DAMPER POSITION G Y1 AND Y2 CONTROL SIGNALS R3 ADJUSTMENT POTENTIOMETER R1 ADJUSTMENT...

Page 10: ...See Figure 5 C Using a small screwdriver adjust potentiometer until damper position aligns with numerical location on the label interior of the sheet metal damper assembly 2 Set the damper position fo...

Page 11: ...Ventilation Airflow CFM Vent Position WA3S Ventilation Airflow Stage 2 Operation Blower Only Stage 1 Operation 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30...

Page 12: ...Page 12 of 16 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Ventilation Airflow CFM Vent Position WA5S Ventilation Airflow Stage 2 Operation Stage 1 Operat...

Page 13: ...rd rate to ASHRAE standards BASIC INSTALLATION 1 Make sure power is turned off to the unit 2 Follow steps beginning on page 2 for installation for standard control and vent assembly then proceed with...

Page 14: ...on with Controller For High Altitude Installations CAL Used for Field Calibration 1 Damper should be fully closed at 700 ppm if not Potentiometer R7 can be adjusted clockwise CW to close it If it is f...

Page 15: ...ir damper built in with positive closed position Provides exhaust air capability to prevent pressurization of tight buildings Actuator motor 24 volt power open spring return with built in torque limit...

Page 16: ...al 2100 457D Page 16 of 16 A call for cooling cycles the compressor and dampers remain in the ventilation mode On loss of blower operation CRV closes fully See Figure 8 FIGURE 8 CALL FOR COOLING OPERA...

Reviews: