GENERAL INFORMATION 

Unpacking

Upon receipt of the equipment be sure to compare the 
model number found on the shipping label with the 
accessory identification information on the ordering and 
shipping document to verify that the correct accessory 
has been shipped.
Inspect the carton housing of each ventilator as it is 
received, and before signing the freight bill, verify that 
all items have been received and that there is no visible 
damage. Note any shortages or damage on all copies 
of the freight bill. The receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent. Concealed 
damage not discovered until after loading must be 
reported to the carrier within 15 days of its receipt. 

General

The ventilator should only be installed by a trained 
heating and air conditioning technician. These 
instructions serve as a guide to the technician installing 
the ventilator package. They are not intended as a step-
by-step procedure with which the mechanically inclined 
owner can install the package.
The ventilator housing is shipped in one carton which 
contains the electrical harness, miscellaneous hardware 
and installation instructions.

Description

Commercial room ventilators CRV-F2 and CRV-F3 are 
designed to be used with the specific models with 
"letter" revision codes as designated on the front page 
of this installation instructions manual.
The CRV-F ventilator is an electromechanical vent 
system designed to provide fresh air to meet indoor air 
quality standards.
Commercial room ventilators CRV-F2 and CRV-F3 are 
internally mounted dampers with exhaust designed 
to provide up to 50% fresh air. The damper blade 
is powered by a 24 VAC motor with spring return on 
power loss. The damper is powered open anytime A 
is energized. Blade stop screws are located under the 
fresh air blade and will provide 10 different airflow 
settings.
When installed in the models listed on the front page, 
the CRV-F provides built-in exhaust provisions. When 
the damper blade opens to bring fresh air in, the 
damper also opens an exhaust relief. The exhaust air 
will flow into the condenser section of the unit. The 
condenser fan will help draw exhaust air out when it 
is operating with compressor in cooling or heat pump 
mode.

Application

The amount of outside fresh air brought into the 
structure is dependent on the supply and return duct 
static pressure present in the duct system. Refer to 
Graphs 1-4 on pages 12-13 for ventilation air that 
will be supplied at different blade settings and duct 
static pressures. For duct-free applications with return 
air filter grilles and supply grilles, use 0.00 supply air 
static pressure.

Commercial Room Ventilator Model Nomenclature

CRV  –  F 

CHASSIS SIZE

2 – 1.5 & 2 Ton Models
3 – 2.5 & 3 Ton Models

COMMERCIAL ROOM VENTILATOR

FIXED (24V ON/OFF)

Summary of Contents for CRV-F2

Page 1: ...dels INSTALLATION INSTRUCTIONS CRV F2 CRV F3 Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 691 Supersedes NEW Date 3 1 19 For Use with Bard Single Stage Wall Mount Air C...

Page 2: ...ion 7 Blade Adjustment for Desired Ventilation Air 11 Figures Figure 1 Wall Mount Unit Access Panels 4 Figure 2 Condenser Exhaust Plate with Screen 5 Figure 3 Filter Bracket and Filter Bracket Fill Pl...

Page 3: ...ic models with letter revision codes as designated on the front page of this installation instructions manual The CRV F ventilator is an electromechanical vent system designed to provide fresh air to...

Page 4: ...ner control panel doors save Filter tray discard if applicable Exhaust cover plate discard 4 Install new condenser exhaust plate with screen over opening into condenser section see Figure 2 5 Remove f...

Page 5: ...e 7 6 Install filter bracket fill plate if applicable as shown in Figure 3 on page 6 7 Install provided filter brackets on CRV F assembly see Figure 3 FIGURE 2 Condenser Exhaust Plate with Screen MIS...

Page 6: ...t and Filter Bracket Fill Plate Installation RIGHT HAND UNIT LEFT HAND UNIT INSTALL FILTER BRACKET FILL PLATE WITH 2 SCREWS ONLY FOR 2 3 TON UNITS LONG FILTER BRACKET LONG FILTER BRACKET 4 REGULAR SCR...

Page 7: ...panel see Figure 5 3 Replace the air filters if they were removed airflow direction is up 4 Put mist eliminator filter into place as shown in Figure 6 on page 8 then install the unit filter door 5 Mak...

Page 8: ...G IN THE REAR FRONT SIDE OF THE CONTROL PANEL THE WIRE HARNESS WILL PLUG INTO THE CONTROL PANEL RH SHOWN WHEN INSTALLING CRV F POSITION SO THAT HOLE FROM LIP IS CENTERED OVER HOLE IN CONDENSER GRILLE...

Page 9: ...L 1 D A 4 W1 E SC SC SC Completestat Model CS9B THO or Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A GND MIS 4000 to N C fire alarm circuit if emergency shutdown required 1 Additional wire required fo...

Page 10: ...1 D A 4 W1 E SC SC SC Completestat Model CS9B THO or Model CS9BE THO W2 COM G 24V Y1 Y2 O B L D A GND Demand ventilation control which could include switched CO2 control or secondary MIS 4001 motion...

Page 11: ...tatic pressure drop 2 Supply air duct static pressure drop 3 Indoor blower motor speed 4 Damper blade open position setting Refer to the appropriate graph on the following pages to determine the blade...

Page 12: ...Manual 2100 691 Page 12 of 15 GRAPH 1 W18 Ventilation Delivery GRAPH 2 W24 Ventilation Delivery...

Page 13: ...Manual 2100 691 Page 13 of 15 GRAPH 4 W36 Ventilation Delivery GRAPH 3 W30 Ventilation Delivery...

Page 14: ...691 Page 14 of 15 FIGURE 10 Call for Ventilation With or Without Compressor Operation MIS 3866 OUTDOOR AIR RETURN AIR SUPPLY AIR COOLING COIL EXHAUST AIR CONDENSER AIR ELIMINATOR AIR FILTER MIST COND...

Page 15: ...691 Page 15 of 15 FIGURE 11 Call for Compressor or Fan Only with Ventilation Off SUPPLY AIR AIR FILTER COOLING COIL CONDENSER AIR OUTDOOR AIR ELIMINATOR MIST CONDENSER COIL 100 RETURN AIR DAMPER BLAD...

Reviews: