Temperature Range: Cool 66-90F (19-32C), Heat 60-80F (16-27C) 

 

Temporary Temperature Override feature: 45-minute default setting, adjustable in 5-minute increments  

 

Humidity control: Dehumidification only, Range 50-75%, Span is 5-10%. Requires special HVAC system with 
dehumidification circuit 

 

Pre-purge capability: Span 0-7200 seconds, default is 0 

 

CO2 control: Range 500-2000 ppm, Span 50-500 ppm 

 

Can optionally display space humidity, CO2, and outdoor temperature  

 

Dedicated ventilation output 

 

Outdoor sensor option, Bard PN 8403-061, can be used to: 

o

 

Limit minimum outdoor temperature for cooling operation 

o

 

Limit minimum outdoor temperature for heat pump operation (compressor lockout)  

o

 

Inhibit electric heat operation for heat pumps above selected outdoor temperature 

 

Remote indoor sensor option, Bard PN 8403-062, can be used to with following options: 

o

 

Use remote indoor sensor only  

o

 

Average remote indoor sensor and on-board sensor  

o

 

Highest of connected sensors 

o

 

Lowest of connected sensors 

 

Vertical mount, mounts to standard 2x4 handy-box installed vertically or horizontally 

 

Off-white 

 

 

 
 

Controller Connections:  

Terminal legend 

          Terminal 

 

      Function   

    

 

 

           Type   

Form 

Dehumidification 

Output 

24VAC        SPST RELAY 

SC 

24VAC to Relay Outputs D, A, W2 

Power 

 

Ventilation Call 

Output 

24VAC        SPST RELAY 

W2 

2

nd

 Stage Heating 

Output 

24VAC        SPST RELAY 

W1/E 

1

st

 Stage Heating/Emer. Heat 

Output 

24VAC        SPST RELAY 

SC 

24VAC to Relay Outputs W1/E, Y2, Y1 

Power 

 

Y2 

2

nd

 Stage Compressor 

Output 

24VAC        SPST RELAY 

Y1 

1

st

 Stage Compressor 

Output 

24VAC        SPST RELAY 

Y0 

Economizer  

Output 

24VAC        SPST RELAY 

SC 

24VAC to Relay Outputs YO, O/B, G 

Power 

 

O/B 

Reversing Valve 

Output 

24VAC        SPST RELAY 

Indoor Blower 

Output 

24VAC        SPST RELAY 

IN9 

Not Used 

 

 

ROS 

Remote Occupancy Sensor 

Input 

Dry Contact (Input to GND) 

GND 

 

 

 

REM 

Remote Temperature Sensor 

Input 

10K Type II Thermistor 

+B 

Communications 

 

 

-A 

Communications 

 

 

OAT 

Outdoor Air Temperature Sensor 

Input 

10K Type II Thermistor 

LAS 

Leaving Air Temperature Sensor 

Input 

10K Type II Thermistor 

GND 

Control Ground 

 

 

Lockout Alarm 

Input 

Dry Contact (Input to GND) 

Com 

24VAC Common 

Power 

 

24V 

24VAC Hot 

Power 

 

 
 
 

Bard Manufacturing Company, Inc. 
Bryan, Ohio 43506 
www.bardhvac.com 

Form No. 

F1943 

May, 2012 

 

Supersedes:

  

F1943-212

 