Manual 7960-811
Page
12 of 13
DEHUMIDIFICATION RELAY LOGIC BOARD
Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
If jumper on RLB is set to “1-2 full-time dehumidification”, outputs will energize. This is the factory default
setting. If jumper is set to “2-3 occupied dehumidification only”, outputs will be off.
24V Terminal
Block Connections
G
Y1
D
W1
A
W2
Outputs From Board
Inputs to Board
G
Y
D
W2
A1
G1
TWV
YO
Cooling Mode
Unoccupied
X
X
X
X
Cooling Mode
Occupied
X
X
X
X
X
Cooling Mode
w / Dehum
X
X
X
X
X
1st Stage Heating
Unoccupied
X
X
1st Stage Heating
Occupied
X
X
X
1st Stage Heating
w / Dehum
X
X
X
X
2nd Stage Heating
Unoccupied
X
X
X
2nd Stage Heating
Occupied
X
X
X
X
2nd Stage Heating
w / Dehum
X
X
X
X
X
X
Dehumidification
Unoccupied
X
Dehumidification
Occupied
X
X
X
X
X