TABLE 11
Indoor Blower Performance
TABLE 13
Maximum ESP of Operation – Electric Heat Only
Values shown are for units equipped with standard 1"
throwaway filter or 1" washable filter.
Derate ESP by .15 for 2" pleated filters.
Model
W12AB
Outlet
Front
Speed
High
Low
-A0Z
-A03
-A05
.35
.35
.35
.35
.35
.35
-K00
-K02
.35
.35
.35
.35
-D0Z
-D03
.35
.35
.35
.35
TABLE 12
Electric Heat
TABLE 14
Vent and Control Options
Part
Number
Description
All
Models
CMA-39
Low Ambient Control
X
BOP-1A
Blank Off Plate
X
BFAD-1
Barometric Fresh Air Damper
X
CRVS-1B
Commercial Ventilator - Spring Return
X
JIFM-1B
Economizer with Exhaust
X
E.S.P.
1
(In. H
2
O)
Balanced Climate
TM
Speed
Rated/Ventilation
Speed
2
Optional HI Cooling &
Heating Speed
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
W12AB-B
W12AB-D
0.00
330
325
465
460
545
525
0.10
315
305
450
435
495
470
0.15
305
290
435
420
465
445
0.20
285
270
415
400
440
415
0.25
260
250
395
380
410
390
0.30
375
355
380
360
0.40
315
305
320
305
0.50
245
245
255
245
W12AB-K
0.00
335
320
455
450
510
505
0.10
295
280
450
435
525
505
0.15
270
255
435
420
515
495
0.20
250
235
415
405
500
480
0.25
225
215
395
385
480
460
0.30
370
365
455
435
0.40
330
325
395
370
0.50
300
295
340
305
1
E.S.P. is the total combined external static pressure of both the supply and return ducts or grills.
2
This is the speed set at the factory.
Models
KW
W12AB-A
W12AB-K
W12AB-D
240V
208V
120V
240V
220V
A
BTU
A
BTU
A
BTU
A
BTU
A
BTU
02
18.3
7,985
03
15.0
12,760
13.0
9,705
15.0
12,760
13.8
10,735
05
20.8
17,540
18.1
13,275
With blower watts included